Dry arc suppression reactors (Petersen coils) 150 kVAr to 4 MVAr, up to 36 kV
The dry arc suppression reactor, or Petersen coil, compensates earth fault current in compensated power networks. Rated power is 150 kVAr to 4 MVAr, voltage up to 36 kV, connection group ZNyn11, with vacuum resin or glass-fibre roving windings.
- Rated power
- 150 kVAr to 4 MVAr
- Rated voltage
- up to 36 kV
- Connection group
- ZNyn11
- Max. operating altitude
- 1000 m above sea level
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
A dry arc suppression reactor, also called a Petersen coil after its inventor W. Petersen, compensates the earth fault current in compensated power networks. The name refers to its effect: it makes it easier to extinguish the arc of an earth fault current.
Two technologies are used: vacuum resin, and roving reinforced with glass fibre. These reactors often work with earthing transformers and are used where equipment filled with insulating liquid is undesirable, for environmental reasons and because no oil pan is needed. A current transformer is added to measure earth fault currents at the neutral point of the reactor.
The production range is 150 kVAr to 4 MVAr at rated voltage up to 36 kV, with connection group ZNyn11. Maximum operating altitude is 1000 m above sea level, ambient temperature is from -25 to 40 °C, and rated frequency is 50 Hz.
The core is cold-rolled electrical steel with inorganic insulation. Windings are copper or aluminium, made by vacuum technology or by roving with glass fibre. The standard enclosure is IP00; a metal enclosure with a specified IP degree, such as IP20, IP21, IP23, IP31, IP33 or IP54, is made on request. Temperature sensing uses PT100 or PTC probes together with protection.
Standard fittings are thermal protection, PT100 sensors, HV terminals on the coils, flat busbar LV terminals, a rating plate, a wheeled chassis, lifting lugs and earthing terminals on the chassis. Optional items are anti-vibration pads, surge arresters, an enclosure, fans, connector bushings and an additional winding (for AWSCz purposes). Design, tests and tolerances follow PN EN 60076-1 and PN EN 60076-11, and units with other parameters are made by individual agreement.
Technical specifications
| Rated power | 150 kVAr to 4 MVAr |
|---|---|
| Rated voltage | up to 36 kV |
| Connection group | ZNyn11 |
| Max. operating altitude | 1000 m above sea level |
| Ambient temperature range | -25 to 40 °C |
| Rated frequency | 50 Hz |
| Core | cold-rolled electrical steel with inorganic insulation |
| Windings | copper or aluminium, vacuum technology or roving with glass fibre |
| Enclosure | standard IP00; metal enclosure with specified IP degree (IP20, IP21, IP23, IP31, IP33, IP54 etc.) on request |
| Sensors | PT100 or PTC probes with protection |
| Standards | PN EN 60076-1, PN EN 60076-11 |
How it compares with similar models
| Parameter | Dry arc suppression reactors (Petersen coils) 150 kVAr to 4 MVAr, up to 36 kV | Dry-type earthing transformers 150 kVA to 4 MVA, up to 36 kV, ZNyn11 | Oil-filled earthing transformers 150 kVA to 4 MVA, up to 36 kV, ZNyn11 | BTUZ resin earthing transformer, 150 kVA to 4 MVA, up to 36 kV |
|---|---|---|---|---|
| Rated power | 150 kVAr to 4 MVAr | 150 kVA to 4 MVA | 150 kVA to 4 MVA | 150 kVA to 4 MVA |
| Rated voltage | up to 36 kV | up to 36 kV | up to 36 kV | Up to 36 kV |
| Rated frequency | 50 Hz | 50 or 60 Hz | 50 Hz | 50 or 60 Hz |
| Windings | copper or aluminium, vacuum technology or roving with glass fibre | copper or aluminium, vacuum technology or roving with glass fibre | round or profiled wire with class H varnish insulation, copper or aluminium | Copper or aluminium, vacuum or roving technique with glass fibre |
| Enclosure | standard IP00; metal enclosure with specified IP degree (IP20, IP21, IP23, IP31, IP33, IP54 etc.) on request | standard IP00; metal enclosure with specified IP degree (IP20, IP21, IP23, IP31, IP33, IP54 etc.) on request | — | IP 00 as standard, optional metal enclosure (IP20, IP21, IP23, IP31, IP33, IP54 etc.) |
| Standards | PN EN 60076-1, PN EN 60076-11 | PN EN 60076-1, PN EN 60076-11, PN EN 60076-6 | PN EN 60076-1, PN EN 60289 | — |
Request a price and lead time
Dry arc suppression reactors (Petersen coils) 150 kVAr to 4 MVAr, up to 36 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the reactor used for?
It compensates earth fault current in compensated networks and helps to extinguish the arc of an earth fault current.
What winding technologies are used?
Vacuum resin and roving reinforced with glass fibre. Windings are copper or aluminium.
Can earth fault current be measured at the neutral?
Yes. A current transformer is added to measure earth fault currents at the neutral point of the reactor.