International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

Dry arc suppression reactors (Petersen coils) 150 kVAr to 4 MVAr, up to 36 kV

The dry arc suppression reactor, or Petersen coil, compensates earth fault current in compensated power networks. Rated power is 150 kVAr to 4 MVAr, voltage up to 36 kV, connection group ZNyn11, with vacuum resin or glass-fibre roving windings.

Rated power
150 kVAr to 4 MVAr
Rated voltage
up to 36 kV
Connection group
ZNyn11
Max. operating altitude
1000 m above sea level

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

A dry arc suppression reactor, also called a Petersen coil after its inventor W. Petersen, compensates the earth fault current in compensated power networks. The name refers to its effect: it makes it easier to extinguish the arc of an earth fault current.

Two technologies are used: vacuum resin, and roving reinforced with glass fibre. These reactors often work with earthing transformers and are used where equipment filled with insulating liquid is undesirable, for environmental reasons and because no oil pan is needed. A current transformer is added to measure earth fault currents at the neutral point of the reactor.

The production range is 150 kVAr to 4 MVAr at rated voltage up to 36 kV, with connection group ZNyn11. Maximum operating altitude is 1000 m above sea level, ambient temperature is from -25 to 40 °C, and rated frequency is 50 Hz.

The core is cold-rolled electrical steel with inorganic insulation. Windings are copper or aluminium, made by vacuum technology or by roving with glass fibre. The standard enclosure is IP00; a metal enclosure with a specified IP degree, such as IP20, IP21, IP23, IP31, IP33 or IP54, is made on request. Temperature sensing uses PT100 or PTC probes together with protection.

Standard fittings are thermal protection, PT100 sensors, HV terminals on the coils, flat busbar LV terminals, a rating plate, a wheeled chassis, lifting lugs and earthing terminals on the chassis. Optional items are anti-vibration pads, surge arresters, an enclosure, fans, connector bushings and an additional winding (for AWSCz purposes). Design, tests and tolerances follow PN EN 60076-1 and PN EN 60076-11, and units with other parameters are made by individual agreement.

Technical specifications

Rated power150 kVAr to 4 MVAr
Rated voltageup to 36 kV
Connection groupZNyn11
Max. operating altitude1000 m above sea level
Ambient temperature range-25 to 40 °C
Rated frequency50 Hz
Corecold-rolled electrical steel with inorganic insulation
Windingscopper or aluminium, vacuum technology or roving with glass fibre
Enclosurestandard IP00; metal enclosure with specified IP degree (IP20, IP21, IP23, IP31, IP33, IP54 etc.) on request
SensorsPT100 or PTC probes with protection
StandardsPN EN 60076-1, PN EN 60076-11

How it compares with similar models

ParameterDry arc suppression reactors (Petersen coils) 150 kVAr to 4 MVAr, up to 36 kVDry-type earthing transformers 150 kVA to 4 MVA, up to 36 kV, ZNyn11Oil-filled earthing transformers 150 kVA to 4 MVA, up to 36 kV, ZNyn11BTUZ resin earthing transformer, 150 kVA to 4 MVA, up to 36 kV
Rated power150 kVAr to 4 MVAr150 kVA to 4 MVA150 kVA to 4 MVA150 kVA to 4 MVA
Rated voltageup to 36 kVup to 36 kVup to 36 kVUp to 36 kV
Rated frequency50 Hz50 or 60 Hz50 Hz50 or 60 Hz
Windingscopper or aluminium, vacuum technology or roving with glass fibrecopper or aluminium, vacuum technology or roving with glass fibreround or profiled wire with class H varnish insulation, copper or aluminiumCopper or aluminium, vacuum or roving technique with glass fibre
Enclosurestandard IP00; metal enclosure with specified IP degree (IP20, IP21, IP23, IP31, IP33, IP54 etc.) on requeststandard IP00; metal enclosure with specified IP degree (IP20, IP21, IP23, IP31, IP33, IP54 etc.) on request—IP 00 as standard, optional metal enclosure (IP20, IP21, IP23, IP31, IP33, IP54 etc.)
StandardsPN EN 60076-1, PN EN 60076-11PN EN 60076-1, PN EN 60076-11, PN EN 60076-6PN EN 60076-1, PN EN 60289—

Request a price and lead time

Dry arc suppression reactors (Petersen coils) 150 kVAr to 4 MVAr, up to 36 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What is the reactor used for?

It compensates earth fault current in compensated networks and helps to extinguish the arc of an earth fault current.

What winding technologies are used?

Vacuum resin and roving reinforced with glass fibre. Windings are copper or aluminium.

Can earth fault current be measured at the neutral?

Yes. A current transformer is added to measure earth fault currents at the neutral point of the reactor.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search