TDOK Oil-Immersed Compensation Reactor, 150 kVAr to 13 MVAr, up to 36 kV

The TDOK in this range is a three-phase oil-immersed reactor for compensating capacitive currents. It runs from 150 kVAr to 13 MVAr with an on-load tap changer, at up to 36 kV, with ONAN or KNAN cooling.

Rated power
150 kVAr to 13 MVAr (with on-load tap changer)
Auxiliary power
according to customer requirements
Rated voltage
up to 36 kV
Cooling
ONAN, KNAN

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Long cable lines, such as those on wind farms or railway lines, produce capacitive current, and TDOK reactors compensate it. They are connected to the network in three phases. The reactor can carry an on-load or off-load tap changer to match its operating parameters to the compensating current.

Auxiliary windings can be added to supply a substation or switchgear, and the unit can also compensate short-circuit current as an earthing transformer. Combining an adjustable reactor with auxiliary and earthing transformer duties lets it be installed in a substation, for example instead of an auxiliary transformer, without enlarging the substation. The auxiliary power follows the customer's requirements.

In this range the rated power is 150 kVAr to 13 MVAr, with an on-load tap changer. Rated voltage is up to 36 kV, cooling is ONAN or KNAN, the insulation class follows N-EN 60085 and frequency is 50 or 60 Hz. Maximum altitude is 1000 m above sea level; ambient temperature is -25 to 40 °C.

The reactor is built in two versions: hermetic, without a conservator, or with a conservator. The core is cold-rolled transformer steel with inorganic insulation and the windings are copper. The tank is sheet steel, powder-painted or hot-dip galvanised, on a wheeled chassis, and a radiator tank is also possible. The reactor is dried and impregnated with transformer oil by a vacuum method.

To order, the reactor can also be made to the customer’s own specification.

Technical specifications

Rated power150 kVAr to 13 MVAr (with on-load tap changer)
Auxiliary poweraccording to customer requirements
Rated voltageup to 36 kV
CoolingONAN, KNAN
Insulation classaccording to N-EN 60085
Max. operating altitude1000 m above sea level
Ambient temperature range-25 to 40 °C
Rated frequency50 or 60 Hz
Corecold-rolled transformer steel with inorganic insulation
Windingscopper
Tankhermetic (no conservator) or with conservator, powder-painted or hot-dip galvanised

How it compares with similar models

ParameterTDOK Oil-Immersed Compensation Reactor, 150 kVAr to 13 MVAr, up to 36 kVTDOK Oil-Immersed Compensation Reactor, 40 kVAr to 10 MVAr, up to 36 kVTDOK C Oil-Filled Shunt Compensation Reactor with Cooler, 10–25 MVAr, up to 36 kVTDOK RO Oil-Immersed Compensation Reactor with On-Load Tap Changer, 546 kVAr – 15 MVAr
Rated power150 kVAr to 13 MVAr (with on-load tap changer)40 kVAr to 10 MVAr10 MVAr – 25 MVAr546 kVAr – 15 MVAr
CoolingONAN, KNANONAN, KNANOFAF or KFAFONAN or KNAN (does not apply to the oil in the on-load tap changer)
Windingscoppercopperround or profiled wire with class H insulation, copper or aluminiumround or profiled wire with class H insulation, copper
Tankhermetic (no conservator) or with conservator, powder-painted or hot-dip galvanisedhermetic (no conservator) or with conservator, powder-painted or hot-dip galvanisedwith oil cooler, powder-painted sheet steel, C4 or C5 anticorrosion systemradiator tank, powder-painted sheet steel, C4 or C5 anticorrosion system

Request a price and lead time

TDOK Oil-Immersed Compensation Reactor, 150 kVAr to 13 MVAr, up to 36 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What power range does this TDOK reactor cover?

From 150 kVAr to 13 MVAr with an on-load tap changer, at a rated voltage of up to 36 kV.

How is the reactor impregnated?

It is dried and impregnated with transformer oil by a vacuum method. The tank is hermetic or has a conservator.

Can it be ordered to a customer specification?

Yes, to order the reactor can be made to the customer's own specification. Auxiliary windings can also be specified.