BDGORs Adjustable Oil-Filled Arc-Suppression Reactor, 546–4850 kVA, up to 21 kV
The BDGORs is an adjustable oil-filled reactor that compensates earth-fault currents automatically on medium voltage networks. It is rated 546 kVA to 4850 kVA for networks up to 21 kV, with a 40-400 A adjustment range.
- Rated power
- 546 kVA to 4850 kVA
- Rated network voltage
- up to 21 kV
- Adjustment range
- 40-400 A
- Rated frequency
- 50 Hz
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
BDGORs reactors compensate earth-fault currents automatically in medium voltage networks whose neutral is earthed through a reactor. One unit carries out the smooth compensation of these currents and at the same time performs measurement, regulation and AWSCz automation.
The earth-fault parameters of the MV network are found by measuring the currents and voltages produced by a controlled pulse, known as current injection. Adjustment is by an electric drive with manual operation as well, and a control cabinet runs the reactor.
Rated power is 546 kVA to 4850 kVA and rated network voltage is up to 21 kV, with an adjustment range of 40-400 A. Frequency is 50 Hz, maximum altitude is 1000 m above sea level and ambient temperature is -25 to 40 °C. The finish is RAL 7033.
The core is low-loss cold-rolled transformer steel with inorganic insulation. Windings are round enamelled wire of electrolytic copper or profiled wire with paper insulation. The conservator-type tank is powder-painted sheet steel in corrosivity category C5-I (high corrosion resistance), mounted on a wheeled chassis whose wheels can be reset to the direction of travel.
The reactor meets PN-EN 60076-6, PN-EN 60071-1, PN-EN 60071-2 and PN-EN 60529. Standard fittings are porcelain HV bushings to DIN 42531 or EN 50180:2010, LV bushings to DIN 42530 or EN 50386:2010, rating plate, earthing terminals on the chassis, lifting and transport lugs, oil level indicator, contact thermometer, Buchholz relay, dehydrating breather, oil filler and a drain valve to EN 50216-4 or DIN 42551. Connector bushings and anti-vibration pads are optional. Manufacture, testing and tolerances follow PN EN 60076-1 and PN EN 60076-6. Units with other parameters are built by individual agreement.
Technical specifications
| Rated power | 546 kVA to 4850 kVA |
|---|---|
| Rated network voltage | up to 21 kV |
| Adjustment range | 40-400 A |
| Rated frequency | 50 Hz |
| Max. operating altitude | 1000 m above sea level |
| Ambient temperature range | -25 to 40 °C |
| Core | low-loss cold-rolled transformer steel with inorganic insulation |
| Windings | round enamelled electrolytic copper wire or profiled wire with paper insulation |
| Tank | with conservator, powder-painted, corrosivity category C5-I |
| Adjustment drive | electric and manual |
| Finish colour | RAL 7033 |
How it compares with similar models
| Parameter | BDGORs Adjustable Oil-Filled Arc-Suppression Reactor, 546–4850 kVA, up to 21 kV | TDOK C Oil-Filled Shunt Compensation Reactor with Cooler, 10–25 MVAr, up to 36 kV | TDOK Oil-Immersed Compensation Reactor, 40 kVAr to 10 MVAr, up to 36 kV | BWR-b Oil-Filled Resistor for Forcing the Active Component (AWSCz), 20 A |
|---|---|---|---|---|
| Rated power | 546 kVA to 4850 kVA | 10 MVAr – 25 MVAr | 40 kVAr to 10 MVAr | — |
| Rated frequency | 50 Hz | 50 or 60 Hz | 50 or 60 Hz | 50 Hz |
| Core | low-loss cold-rolled transformer steel with inorganic insulation | cold-rolled transformer steel with inorganic insulation | cold-rolled transformer steel with inorganic insulation | — |
| Windings | round enamelled electrolytic copper wire or profiled wire with paper insulation | round or profiled wire with class H insulation, copper or aluminium | copper | — |
| Tank | with conservator, powder-painted, corrosivity category C5-I | with oil cooler, powder-painted sheet steel, C4 or C5 anticorrosion system | hermetic (no conservator) or with conservator, powder-painted or hot-dip galvanised | corrugated, powder-painted sheet steel, corrosivity category C5-I |
Request a price and lead time
BDGORs Adjustable Oil-Filled Arc-Suppression Reactor, 546–4850 kVA, up to 21 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the BDGORs reactor used for?
For automatic, smooth compensation of earth-fault currents in medium voltage networks with the neutral earthed through a reactor. It also measures, regulates and provides AWSCz automation.
What are the adjustment range and rating?
The adjustment range is 40-400 A, rated power is 546 kVA to 4850 kVA and network voltage is up to 21 kV.
How does it determine the earth-fault parameters?
It measures the currents and voltages caused by a controlled pulse, called current injection. The MV network parameters are derived from these results.
Similar equipment from other manufacturers