BWR-b Oil-Filled Resistor for Forcing the Active Component (AWSCz), 20 A
The BWR-b is a primary oil-filled AWSCz resistor that forces the active component of the earth-fault current in compensated MV networks. Network voltage is up to 30 kV, forcing current 20 A, load time 10 s, 2 cycles.
- Rated network voltage
- up to 30 kV
- Rated forcing current
- 20 A
- Rated resistor load time
- 10 s
- Minimum pause in forcing current flow
- 2 s
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The primary AWSCz resistor forces the active component of the earth-fault current in compensated medium voltage networks and supports the operation of earth-fault protection.
The resistor is oil-filled with a rated current of 20 A. It comes with an MV vacuum contactor, porcelain bushings, a contact thermometer and a pressure relief valve. Rated network voltage is up to 30 kV, rated forcing current is 20 A, rated resistor load time is 10 s, the minimum pause in forcing current flow is 2 s and the number of cycles is 2.
The corrugated resistor tank is made of powder-painted sheet steel in corrosivity category C5-I (high corrosion resistance). It stands on a wheeled chassis whose wheels can be reset to the direction of travel. The finish is RAL 7033. Frequency is 50 Hz, maximum altitude is 1000 m above sea level and ambient temperature is -25 to 40 °C.
Standard fittings are porcelain HV bushings to DIN 42531 or EN 50180:2010, LV bushings to DIN 42530 or EN 50386:2010, rating plate, earthing terminals on the chassis, lifting and transport lugs, oil level indicator, contact thermometer, pressure relief valve, drain valve and the vacuum contactor. A PT100 thermometer and an oil-filled current transformer of 50/5A, class 10P5, 30VA, built into the tank, are optional. Manufacture, testing and tolerances follow PN EN 60076-1 and PN EN 60076-6. Units with other parameters are built by individual agreement.
Technical specifications
| Rated network voltage | up to 30 kV |
|---|---|
| Rated forcing current | 20 A |
| Rated resistor load time | 10 s |
| Minimum pause in forcing current flow | 2 s |
| Number of cycles | 2 cycles |
| Rated frequency | 50 Hz |
| Max. operating altitude | 1000 m above sea level |
| Ambient temperature range | -25 to 40 °C |
| Fitted with | MV vacuum contactor, porcelain bushings, contact thermometer, pressure relief valve |
| Tank | corrugated, powder-painted sheet steel, corrosivity category C5-I |
| Finish colour | RAL 7033 |
How it compares with similar models
| Parameter | BWR-b Oil-Filled Resistor for Forcing the Active Component (AWSCz), 20 A | BDGORs Adjustable Oil-Filled Arc-Suppression Reactor, 546–4850 kVA, up to 21 kV | TDOK C Oil-Filled Shunt Compensation Reactor with Cooler, 10–25 MVAr, up to 36 kV | TDOK Oil-Immersed Compensation Reactor, 40 kVAr to 10 MVAr, up to 36 kV |
|---|---|---|---|---|
| Rated frequency | 50 Hz | 50 Hz | 50 or 60 Hz | 50 or 60 Hz |
| Tank | corrugated, powder-painted sheet steel, corrosivity category C5-I | with conservator, powder-painted, corrosivity category C5-I | with oil cooler, powder-painted sheet steel, C4 or C5 anticorrosion system | hermetic (no conservator) or with conservator, powder-painted or hot-dip galvanised |
Request a price and lead time
BWR-b Oil-Filled Resistor for Forcing the Active Component (AWSCz), 20 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the BWR-b resistor for?
It forces the active component of the earth-fault current in compensated medium voltage networks and supports earth-fault protection.
What is the load duty of the resistor?
Rated current is 20 A, load time is 10 s, the minimum pause in current flow is 2 s and the number of cycles is 2.
Which options can be added?
A PT100 thermometer and an oil-filled current transformer of 50/5A, class 10P5, 30VA, built into the tank.