BTUZ resin earthing transformer, 150 kVA to 4 MVA, up to 36 kV
The BTUZ earthing transformer creates an artificial neutral point in resistance-earthed and compensated networks. Rated power 150 kVA to 4 MVA, voltage up to 36 kV, vector group ZNyn11, AN cooling.
- Type
- Three-phase resin earthing transformer
- Series
- BTUZ
- Rated power
- 150 kVA to 4 MVA
- Rated voltage
- Up to 36 kV
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
An earthing transformer such as the BTUZ provides an artificial neutral point in networks earthed through a resistor or in compensated networks. Dry earthing transformers are three-phase units, and when no earth fault is present they also supply the auxiliary needs of the substation.
The characteristic vector group of an earthing transformer is ZNyn11. During a fault to earth it spreads the fault current across all phases and so lowers its value in the faulty line. The secondary winding can operate continuously at rated conditions even when the primary winding carries compensation current.
In resistor-earthed networks the neutral point is connected to an earthing resistor that forces the active component. In compensated networks it is usually connected to an arc-suppression reactor, which adds the reactance needed to extinguish the arc and compensate earth-fault currents. The construction of resin earthing transformers allows use in harsh conditions and in places that call for higher safety standards.
Production range: rated power 150 kVA to 4 MVA, rated voltage up to 36 kV, compensation current 15 A to 300 A, vector group ZNyn11, AN cooling, insulation class F or H, frequency 50 or 60 Hz. Operating conditions: altitude up to 1000 m above sea level, ambient temperature from -25 to 40°C, frequency 50 Hz.
The core is cold-rolled transformer sheet steel with inorganic insulation. The windings are copper or aluminium, made by the vacuum or roving technique with glass fibre. The standard enclosure is IP 00, or to the customer's wish a metal enclosure with a stated IP rating (for example IP20, IP21, IP23, IP31, IP33, IP54). Sensors are PT100 or PTC probes with protection.
Technical specifications
| Type | Three-phase resin earthing transformer |
|---|---|
| Series | BTUZ |
| Rated power | 150 kVA to 4 MVA |
| Rated voltage | Up to 36 kV |
| Compensation current | 15 A to 300 A |
| Vector group | ZNyn11 |
| Cooling | AN |
| Insulation class | F or H |
| Rated frequency | 50 or 60 Hz |
| Maximum altitude | 1000 m above sea level |
| Ambient temperature | -25 to 40°C |
| Windings | Copper or aluminium, vacuum or roving technique with glass fibre |
| Enclosure | IP 00 as standard, optional metal enclosure (IP20, IP21, IP23, IP31, IP33, IP54 etc.) |
| Sensors | PT100 or PTC probes with protection |
How it compares with similar models
| Parameter | BTUZ resin earthing transformer, 150 kVA to 4 MVA, up to 36 kV | Dry-type earthing transformers 150 kVA to 4 MVA, up to 36 kV, ZNyn11 | BDGO oil-immersed Petersen coil, 150 kVA to 4 MVA, up to 36 kV | Oil-filled earthing transformers 150 kVA to 4 MVA, up to 36 kV, ZNyn11 |
|---|---|---|---|---|
| Rated voltage | Up to 36 kV | up to 36 kV | Up to 36 kV | up to 36 kV |
| Rated frequency | 50 or 60 Hz | 50 or 60 Hz | 50 Hz | 50 Hz |
| Windings | Copper or aluminium, vacuum or roving technique with glass fibre | copper or aluminium, vacuum technology or roving with glass fibre | Round or profiled wire, class H lacquer insulation, copper or aluminium | round or profiled wire with class H varnish insulation, copper or aluminium |
Request a price and lead time
BTUZ resin earthing transformer, 150 kVA to 4 MVA, up to 36 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the BTUZ earthing transformer used for?
To create an artificial neutral point in resistor-earthed or compensated networks. With no earth fault present it also supplies the auxiliary needs of the substation.
What vector group and compensation current does it have?
Vector group ZNyn11 and compensation current from 15 A to 300 A. In an earth fault the current is spread across all phases.
What enclosure ratings are available?
IP 00 as standard. To the customer's wish, a metal enclosure such as IP20, IP21, IP23, IP31, IP33 or IP54.