International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

10–30 AN/BN/CN epoxy indoor post insulators up to 38.5 kV

10–30 AN/BN/CN are cast epoxy post insulators for indoor MV switchgear for voltages up to 12–15, 25 and 38.5 kV. They support busbars and current-carrying parts in 6–35 kV switchgear, KSO cubicles and package substations.

Types
10AN, 10BN, 10CN, 10CS, 12AN (up to 12–15 kV); 20AN, 20AS, 20BN, 20BS, 20CN (up to 25 kV); 30AN, 30BN, 30CN (up to 38.5 kV)
Test voltages 10AN
20/28 kV (50 Hz), 60/75 kV (impulse), 7.5/12 kV
Test voltages 30AN
80 kV / 180 kV at 38.5 kV
10AN
height 193 mm, 8 kN, 0.6 kg, variants -1/-2/-3 by inserts

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The range is divided into three groups by voltage. For 12–15 kV, the 10AN, 10BN, 10CN, 10CS and 12AN are produced, for 25 kV the 20AN, 20AS, 20BN, 20BS and 20CN, and for 38.5 kV the 30AN, 30BN and 30CN. The insulator electrically separates structural parts at different potentials and at the same time connects them mechanically. The post insulators are designed for busbar systems with significant dynamic forces from short-circuit currents.

The 10AN insulator is intended for indoor systems with a rated voltage up to 15 kV. The variants 10AN-1, 10AN-2 and 10AN-3 differ in the position and size of the metal inserts. The rated voltage is 7.5/12 kV, the power-frequency test voltage 20/28 kV, the lightning impulse 60/75 kV, and the frequency 50/60 Hz. Height 193 mm, mechanical load 8 kN, weight 0.6 kg.

10BN, 10CN and 10CS are used in systems up to 12 kV with the same test levels. For 10BN the manufacturer gives a creepage distance of 190 mm, bending force of 16 kN, weight 0.9 kg, insulation thermal class E and an operating temperature of −5 to +40 °C, order code 600 000 027. The 30AN, 30BN and 30CN insulators for systems up to 38.5 kV are tested with 80 kV power frequency and 180 kV impulse voltage.

The insulator body is cast from epoxy resin, on which its thermal, mechanical and electrical resistance depends. The screw inserts are made of brass, and the recommended tightening torques of the threads are given in the manufacturer's table. The design can be modified to customer requirements, and the company also makes other epoxy parts to order.

The post insulators have been tested in the accredited laboratory EGÚ HV Laboratory a. s. They comply with ČSN EN 60660, ČSN IEC 273, IEC 60660, IEC 273 and GOST 28739-90. Technical data sheets with dimensions and order codes are published for each type. The insulators are used by switchgear manufacturers for equipping new units and by maintenance services for repair and modernization of cubicles.

Technical specifications

Types10AN, 10BN, 10CN, 10CS, 12AN (up to 12–15 kV); 20AN, 20AS, 20BN, 20BS, 20CN (up to 25 kV); 30AN, 30BN, 30CN (up to 38.5 kV)
Test voltages 10AN20/28 kV (50 Hz), 60/75 kV (impulse), 7.5/12 kV
Test voltages 30AN80 kV / 180 kV at 38.5 kV
10ANheight 193 mm, 8 kN, 0.6 kg, variants -1/-2/-3 by inserts
Testingaccredited laboratory EGÚ HV Laboratory
StandardsIEC 60660, IEC 273, GOST 28739-90

Request a price and lead time

10–30 AN/BN/CN epoxy indoor post insulators up to 38.5 kV. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8546 90 90 00
HS, 6 digits8546 90
CN (EU)8546 90 90
HTSUS (USA)8546 90 00 00
China customs tariff8546 90 00 00

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

What voltages are the post insulators made for?

Types 10AN–10CS and 12AN for 12–15 kV, group 20 for 25 kV, group 30 for 38.5 kV. All of them are for indoor installation.

What are the parameters of the 10AN insulator?

Rated voltage 7.5/12 kV, test voltage 20/28 kV power frequency and 60/75 kV impulse. Height 193 mm, mechanical load 8 kN, weight 0.6 kg.

Which standards do the insulators comply with?

ČSN EN 60660, ČSN IEC 273, IEC 60660, IEC 273 and GOST 28739-90. The tests were carried out in the EGÚ HV Laboratory.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides