M3 Hookstick Disconnect Switch, Single Insulator, 15/27/38 kV Classes, 600 or 900 A
Hookstick-operated air break disconnects built around a single insulator, intended for overhead distribution feeders. Voltage classes of 15, 27 and 38 kV, BIL levels of 110, 125 and 150 kV and continuous ratings of 600 A or 900 A, fully compliant with ANSI/IEEE C37.30.1.
- Type
- Single-insulator disconnect, hookstick operated
- Voltage classes
- 15, 27 and 38 kV
- BIL levels
- 110, 125 and 150 kV
- Continuous current
- 600 A or 900 A
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
On the M3C design the whole switch sits on one polymer insulator assembly of the Type C pattern, the same as used on Type C cutouts. Field crews therefore carry fewer different spares, and the switch bolts to the cross arm with a standard NEMA B bracket.
Ratings cover three voltage classes, 15, 27 and 38 kV, with insulation levels of 110, 125 and 150 kV BIL. Continuous current is 600 A or 900 A depending on the version. A load break option is offered on selected models, and the range is fully compliant with ANSI/IEEE C37.30.1 for high-voltage air switches.
Operation is by hookstick, so a lineworker opens or closes the switch from the ground or a bucket without any linkage or operating mechanism. Typical duties are sectionalising a feeder, isolating a pole-mounted transformer and giving a visible break before maintenance on the downstream section.
As a reference, M3C156 is the 15 kV, 110 kV BIL, 600 A unit. Installed dimensions are 20 × 4.25 × 21.6 in with a depth of 10.2 in, and it weighs 14 lb. Letter suffixes such as M3C156B, M3C156BC or M3C156BX identify equipment variants, so please quote the full catalogue number in your enquiry together with the system voltage, required BIL and load current.
Technical specifications
| Type | Single-insulator disconnect, hookstick operated |
|---|---|
| Voltage classes | 15, 27 and 38 kV |
| BIL levels | 110, 125 and 150 kV |
| Continuous current | 600 A or 900 A |
| Insulator | Type C polymer insulator assembly |
| Mounting | NEMA B cross arm bracket |
| Load break | Option |
| Standard | ANSI/IEEE C37.30.1 |
| Installed dimensions (M3C156) | 20 × 4.25 × 21.6 in, depth 10.2 in |
| Weight (M3C156) | 14 lb |
Request a price and lead time
M3 Hookstick Disconnect Switch, Single Insulator, 15/27/38 kV Classes, 600 or 900 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which voltage classes and currents are available?
15, 27 and 38 kV classes with 110, 125 and 150 kV BIL, at 600 A or 900 A continuous.
Can the M3 interrupt load current?
As standard it is a disconnect, but a load break option exists on selected versions; the full catalogue number shows whether it is fitted.
How is the switch mounted on the pole?
It fixes to the cross arm with a NEMA B bracket and uses a Type C polymer insulator assembly, as found on Type C cutouts.