ALTD Single Phase In-Line Tension Disconnect Switch, 38 kV, 200 kV BIL, 600 A and 900 A
The ALTD is a single phase disconnect fitted directly into the cut of an overhead line conductor, where it takes a working tension of 15,000 lb. It is operated with a hookstick and combines ESP polymer insulation with solid copper blades, and loadbreak versions add arc chutes for 600 A.
- Type
- single phase in-line tension disconnect switch
- Voltage
- 34.5 kV, maximum 38 kV
- BIL
- 200 kV
- Continuous current
- 600 A; 900 A
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The 600 A and 900 A basic models are no-load disconnects, while versions with an L in the code add arc chutes that allow 600 A to be broken under load. Model ALTD06200R measures 27 x 5.25 x 26.86 in and weighs 15.68 lb, whereas the loadbreak variants are 16.51 in deep. The 900 A family, ALTD09200, stands 28.86 in high. Dimensions quoted apply to the assembled unit.
Each blade is solid copper, formed as two parallel plates joined in the manner of a truss member, and the contacts are silver and copper. The ESP polymer insulator is dark grey, giving a creepage distance of 31.4 in (797.6 mm) and a dry arc distance of 15.3 in (388.6 mm). Hooks on the switch accept a portable load-break tool.
The rated voltage is 34.5 kV, with a maximum of 38 kV and a BIL of 200 kV. Continuous current is 600 A or 900 A, and the 600 A version withstands an 8-hour emergency overload of 1080 A. It withstands 25 kA symmetrical for 1 s or 40 kA asymmetrical for 10 cycles, and the temperature rise at 600 A stays at or below 28° C. The design conforms to ANSI/IEEE C37.30.1.
Suffix letters describe the fitted options: C adds extension links, B adds terminal bolts, and T adds ATC1343 terminal connectors for conductors from #2 to 500kcmil with galvanised hardware. The switch is operated with a hookstick, and 24 units fit on one pallet, supplied individually.
Technical specifications
| Type | single phase in-line tension disconnect switch |
|---|---|
| Voltage | 34.5 kV, maximum 38 kV |
| BIL | 200 kV |
| Continuous current | 600 A; 900 A |
| 8-hour emergency overload | 1080 A |
| 1 s withstand | 25 kA symmetrical |
| 10-cycle withstand | 40 kA asymmetrical |
| Temperature rise at 600 A | 28° C |
| Working tension | 15000 lb |
| Blade | solid copper, two plates |
| Contacts | silver, copper |
| Insulator | ESP polymer, dark grey |
| Creepage distance | 31.4 in (797.6 mm) |
| Dry arc distance | 15.3 in (388.6 mm) |
| Dimensions ALTD06200R | 27 x 5.25 x 26.86 in |
| Weight ALTD06200R | 15.68 lb |
| Operation | hookstick |
| Standard | ANSI/IEEE C37.30.1 |
Part numbers
Show all part numbers (17)
ALTD06200R, ALTD06200RB, ALTD06200RBC, ALTD06200RC, ALTD06200RCT, ALTD06200RL, ALTD06200RLB, ALTD06200RLBC, ALTD06200RLC, ALTD06200RLCT, ALTD06200RLT, ALTD06200RT, ALTD09200RB, ALTD09200RBC, ALTD09200RC, ALTD09200RCT, ALTD09200RT
Request a price and lead time
ALTD Single Phase In-Line Tension Disconnect Switch, 38 kV, 200 kV BIL, 600 A and 900 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Can the ALTD interrupt load current?
Yes, versions with an L in the code carry arc chutes for breaking 600 A. The basic 600 A and 900 A models are no-load disconnects.
What line tension can the disconnect withstand?
The working load at dead-end is 15,000 lb. The unit is installed directly into the cut of the conductor.
What do the C and T suffixes in the code mean?
C denotes a set of extension links, and T denotes ATC1343 terminal connectors for conductors from #2 to 500kcmil with galvanised hardware.
Similar equipment from other manufacturers