HH8, HH6, AVR, AGCH5 and ATR air break substation switches for 7.5 to 362 kV
This range of outdoor air break disconnect switches serves open substation switchyards, from the copper and bronze hookstick switches HH8 and HH6 to the group-operated aluminium switches with vertical, side and centre break. Current ratings run from 600 A to 4000 A.
- Type
- outdoor air break disconnect switch
- Range voltage
- 7.5–362 kV
- Rated current
- 600 A, 1200 A, 2000 A, 3000 A, 4000 A
- BIL
- 95 kV, 110 kV, 150 kV, 200 kV, 250 kV, 350 kV
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The switches in this group are installed on open-air substation switchyards. The manufacturer names typical duties: disconnecting a power transformer, isolating a circuit breaker, bypassing equipment during maintenance and tandem transfer duty. The range includes single-pole units operated with an insulating hookstick, and group-operated switches in which all three poles are moved by one operator.
HH8 and HH6 have live parts of copper and bronze. A large ring for the hookstick and a pulling lever with a 4:1 ratio make the operation easier, and a positive latch holds the blade closed under vibration and short circuit. HH8 covers 8.3 to 72.5 kV and 600 to 2000 A, while HH6 covers 7.5 to 69 kV and 600 to 4000 A. Both units comply with ANSI/IEEE C37.30.1, have a four-hole tin-plated NEMA terminal pad, and are also made in V-shaped, tandem and 45 degree versions, and for bypassing voltage regulators.
The group-operated switches are mainly made of aluminium. AVR, with vertical break, covers 8.3 to 362 kV and 1200 to 3000 A, while its V-shaped counterpart AVRV covers 48.3 to 245 kV. AGCH5 with centre side break covers 8.3 to 362 kV, and AGCH5V in the V-shaped form covers 8.3 to 245 kV. ATR, with double centre break, is intended for 145 to 362 kV, and ASB, with side break, for 8.3 to 72.5 kV.
GCH4 and GCH4V work with centre break. GCH4 has an operator with a high mechanical advantage, whereas GCH4V is mounted on a single beam of the substation structure. It is a two-insulator side-opening switch whose blade turns on a low-profile base as the two insulators rotate. TS2, also known as TU-1TS2, is a two-insulator side break switch whose blade opens by rotating the hinged insulator. Its mounting is standardised, and it is designed to operate under full load.
For the hookstick types the voltage classes are 8.3, 15.5, 27, 38, 48.3 and 72.5 kV, with BIL levels from 95 to 350 kV. Rated currents in the range are 600, 1200, 2000, 3000 and 4000 A. The switches comply with ANSI/IEEE C37.30.1 and C37.30.2, and overall dimensions are given by the manufacturer in the mounted state. To make a selection, state the voltage class, the rated current, the BIL, the break arrangement, the type of support structure and the method of operation.
Technical specifications
| Type | outdoor air break disconnect switch |
|---|---|
| Range voltage | 7.5–362 kV |
| Rated current | 600 A, 1200 A, 2000 A, 3000 A, 4000 A |
| BIL | 95 kV, 110 kV, 150 kV, 200 kV, 250 kV, 350 kV |
| Voltage classes, HH8 and HH6 | 8.3; 15.5; 27; 38; 48.3; 72.5 kV |
| HH8 | hookstick, copper and bronze, 8.3–72.5 kV, 600–2000 A |
| HH6 | hookstick, copper and bronze, 7.5–69 kV, 600–4000 A |
| AVR | vertical break, aluminium, 8.3–362 kV, 1200–3000 A |
| AVRV | vertical break, V-shaped, 48.3–245 kV |
| AGCH5 | centre side break, aluminium, 8.3–362 kV |
| AGCH5V | centre side break, V-shaped, 8.3–245 kV |
| ATR | double centre break, 145–362 kV |
| ASB | side break, aluminium, 8.3–72.5 kV |
| HH8 and HH6 terminal | NEMA pad, 4 holes, tin-plated |
| Standards | ANSI/IEEE C37.30.1, ANSI/IEEE C37.30.2 |
Part numbers
Show all part numbers (11)
HH8, HH6, TS2, GCH4V, GCH4, AVR, ATR, AGCH5, AVRV, ASB, AGCH5V
Request a price and lead time
HH8, HH6, AVR, AGCH5 and ATR air break substation switches for 7.5 to 362 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How do HH8 and HH6 differ?
HH8 covers 8.3 to 72.5 kV and 600 to 2000 A, while HH6 covers 7.5 to 69 kV and currents up to 4000 A. Both have copper and bronze live parts, are operated with a hookstick and comply with ANSI/IEEE C37.30.1.
Which switches suit the 362 kV class?
The group-operated aluminium switches AVR, AGCH5 and ATR cover up to 362 kV. For networks up to 245 kV, the V-shaped AVRV and AGCH5V versions are available.
What should be stated when requesting a selection?
The voltage class, rated current, BIL level, break arrangement (vertical, side or centre), the type of support structure and the method of operation, either hookstick or group operator. For HH8 and HH6 the version is also needed: standard, V-shaped, tandem, 45 degree or for regulator bypass.
Similar equipment from other manufacturers