TEF1058 wall mounted capillary tube thermostat for heat tracing, Ex db eb IIC T6, 230 V, 16 A, IP66/67

This TEF1058 capillary tube thermostat is fixed to a wall and has one change-over contact. Ranges are -20 to 50 °C, 0 to 120 °C and 0 to 200 °C, at 230 V AC and 16 A (T6), in a 1.4404 stainless steel enclosure rated IP66/67.

Application
Wall mounted safety temperature monitor, capillary tube thermostat
Measuring ranges
-20 to 50 °C; 0 to 120 °C; 0 to 200 °C
Contacts
1 change-over contact
Rated operational voltage AC
230 V

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The wall mounted TEF1058 capillary tube thermostat is used in heat tracing systems in the petrochemical industry, in industrial plants for frost protection or temperature maintenance, and in hazardous areas. The catalogue lists it as a safety temperature monitor for wall mounting. It is recommended for up to 4 heating cables and suits Zone 1 and 2.

Three measuring ranges are offered, each with one change-over contact: -20 to 50 °C (TEF10582580), 0 to 120 °C (TEF10582581) and 0 to 200 °C (TEF10582582). Rated operational voltage is 230 V AC and rated operational current is 16 A (T6). Maximum output AC load is L-2 16 (2.5) A cos φ 1 (0.6) and L-4 2 (0.4) A cos φ 1 (0.6).

The enclosure is electropolished stainless steel 1.4404 (AISI 316L), measuring 253 × 188 × 140 mm. Protection is IP66/IP67, or IP67 without breather, and ambient temperature runs from -50 °C to +50 °C. A stainless steel type label is spot welded to the cover, and several earthing alternatives exist.

Entries are 1 brass M25 cable gland for Ø13 ... 17 mm, 8 brass M25 × 1.5 stopping plugs and 1 brass M25 × 1.5 breather. Terminals are 3 two-conductor supply terminals of 10 mm², 5 two-conductor output terminals of 2.5 mm² and 4 two-conductor PE terminals of 10 mm².

Explosion protection is Ex db eb IIC T6 (IECEx) and E II 2 G Ex db eb IIC T6 (ATEX). NORSOK requirements apply.

Technical specifications

ApplicationWall mounted safety temperature monitor, capillary tube thermostat
Measuring ranges-20 to 50 °C; 0 to 120 °C; 0 to 200 °C
Contacts1 change-over contact
Rated operational voltage AC230 V
Rated operational current16 A (T6)
Max. output AC load, L-216 (2.5) A cos φ 1 (0.6)
Max. output AC load, L-42 (0.4) A cos φ 1 (0.6)
Degree of protectionIP66/IP67
Enclosure materialStainless steel 1.4404, electropolished
Dimensions253 × 188 × 140 mm
Ambient temperature-50 °C ... +50 °C
Explosion protectionEx db eb IIC T6; E II 2 G Ex db eb IIC T6
Entries1 × cable gland M25 Ø13 ... 17 mm; 8 × stopping plug M25 × 1.5; 1 × breather M25 × 1.5
Terminals3 × supply 10 mm²; 5 × output 2.5 mm²; 4 × PE 10 mm²

Part numbers

Show all part numbers (3)

TEF10582580 (259553), TEF10582581 (259554), TEF10582582 (259555)

How it compares with similar models

ParameterTEF1058 wall mounted capillary tube thermostat for heat tracing, Ex db eb IIC T6, 230 V, 16 A, IP66/67TEF1058 pipe mounted capillary tube thermostat for heat tracing, Ex db eb IIC T6, 230 V, 16 A, IP66/67TEF1058 wall mounted junction box for heat tracing, Ex eb IIC T5 Gb, IP66/67TEF1058 wall mounted heat tracing junction box, 4 mm², Ex eb IIC T5 Gb, IP66/67
ApplicationWall mounted safety temperature monitor, capillary tube thermostatPipe mounted safety temperature monitor, capillary tube thermostatWall mounted junction box for heat tracing and de-iceWall mounted junction box for heat tracing
Enclosure materialStainless steel 1.4404, electropolishedStainless steel 1.4404, electropolishedStainless steel 1.4404 (AISI 316L), electropolished or pickledStainless steel 1.4404 (AISI 316L), electropolished or pickled
Dimensions253 × 188 × 140 mm—184 × 184 × 120 mm125 × 147 × 112 mm
Ambient temperature-50 °C ... +50 °C-50 °C ... +50 °C-50 °C ... +50 °C-40 °C ... +40 °C
Entries1 × cable gland M25 Ø13 ... 17 mm; 8 × stopping plug M25 × 1.5; 1 × breather M25 × 1.51 × cable gland M25 Ø13 ... 17 mm; 6 × stopping plug M25 × 1.5; 1 × breather M25 × 1.5; 2 × transition unit M252 × E204/622 M25/D9 (Ø13 - 17 mm) or 7 × Ø251 × E204/622 M25/D9 (Ø13 - 17 mm) or 4 × Ø25

Request a price and lead time

TEF1058 wall mounted capillary tube thermostat for heat tracing, Ex db eb IIC T6, 230 V, 16 A, IP66/67. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which temperature ranges does the wall mounted thermostat offer?

Three ranges, -20 to 50 °C, 0 to 120 °C and 0 to 200 °C, each with one change-over contact.

What are the switching capacity and protection degree?

230 V AC and 16 A (T6), with up to 2 (0.4) A for L-4 and 16 (2.5) A for L-2. Protection is IP66/IP67.

How many heating cables are recommended?

Up to 4 heating cables. Explosion protection is Ex db eb IIC T6, ATEX E II 2 G.