TEF1058 wall mounted capillary tube thermostat for heat tracing, Ex db eb IIC T6, 230 V, 16 A, IP66/67
This TEF1058 capillary tube thermostat is fixed to a wall and has one change-over contact. Ranges are -20 to 50 °C, 0 to 120 °C and 0 to 200 °C, at 230 V AC and 16 A (T6), in a 1.4404 stainless steel enclosure rated IP66/67.
- Application
- Wall mounted safety temperature monitor, capillary tube thermostat
- Measuring ranges
- -20 to 50 °C; 0 to 120 °C; 0 to 200 °C
- Contacts
- 1 change-over contact
- Rated operational voltage AC
- 230 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The wall mounted TEF1058 capillary tube thermostat is used in heat tracing systems in the petrochemical industry, in industrial plants for frost protection or temperature maintenance, and in hazardous areas. The catalogue lists it as a safety temperature monitor for wall mounting. It is recommended for up to 4 heating cables and suits Zone 1 and 2.
Three measuring ranges are offered, each with one change-over contact: -20 to 50 °C (TEF10582580), 0 to 120 °C (TEF10582581) and 0 to 200 °C (TEF10582582). Rated operational voltage is 230 V AC and rated operational current is 16 A (T6). Maximum output AC load is L-2 16 (2.5) A cos φ 1 (0.6) and L-4 2 (0.4) A cos φ 1 (0.6).
The enclosure is electropolished stainless steel 1.4404 (AISI 316L), measuring 253 × 188 × 140 mm. Protection is IP66/IP67, or IP67 without breather, and ambient temperature runs from -50 °C to +50 °C. A stainless steel type label is spot welded to the cover, and several earthing alternatives exist.
Entries are 1 brass M25 cable gland for Ø13 ... 17 mm, 8 brass M25 × 1.5 stopping plugs and 1 brass M25 × 1.5 breather. Terminals are 3 two-conductor supply terminals of 10 mm², 5 two-conductor output terminals of 2.5 mm² and 4 two-conductor PE terminals of 10 mm².
Explosion protection is Ex db eb IIC T6 (IECEx) and E II 2 G Ex db eb IIC T6 (ATEX). NORSOK requirements apply.
Technical specifications
| Application | Wall mounted safety temperature monitor, capillary tube thermostat |
|---|---|
| Measuring ranges | -20 to 50 °C; 0 to 120 °C; 0 to 200 °C |
| Contacts | 1 change-over contact |
| Rated operational voltage AC | 230 V |
| Rated operational current | 16 A (T6) |
| Max. output AC load, L-2 | 16 (2.5) A cos φ 1 (0.6) |
| Max. output AC load, L-4 | 2 (0.4) A cos φ 1 (0.6) |
| Degree of protection | IP66/IP67 |
| Enclosure material | Stainless steel 1.4404, electropolished |
| Dimensions | 253 × 188 × 140 mm |
| Ambient temperature | -50 °C ... +50 °C |
| Explosion protection | Ex db eb IIC T6; E II 2 G Ex db eb IIC T6 |
| Entries | 1 × cable gland M25 Ø13 ... 17 mm; 8 × stopping plug M25 × 1.5; 1 × breather M25 × 1.5 |
| Terminals | 3 × supply 10 mm²; 5 × output 2.5 mm²; 4 × PE 10 mm² |
Part numbers
Show all part numbers (3)
TEF10582580 (259553), TEF10582581 (259554), TEF10582582 (259555)
How it compares with similar models
| Parameter | TEF1058 wall mounted capillary tube thermostat for heat tracing, Ex db eb IIC T6, 230 V, 16 A, IP66/67 | TEF1058 pipe mounted capillary tube thermostat for heat tracing, Ex db eb IIC T6, 230 V, 16 A, IP66/67 | TEF1058 wall mounted junction box for heat tracing, Ex eb IIC T5 Gb, IP66/67 | TEF1058 wall mounted heat tracing junction box, 4 mm², Ex eb IIC T5 Gb, IP66/67 |
|---|---|---|---|---|
| Application | Wall mounted safety temperature monitor, capillary tube thermostat | Pipe mounted safety temperature monitor, capillary tube thermostat | Wall mounted junction box for heat tracing and de-ice | Wall mounted junction box for heat tracing |
| Enclosure material | Stainless steel 1.4404, electropolished | Stainless steel 1.4404, electropolished | Stainless steel 1.4404 (AISI 316L), electropolished or pickled | Stainless steel 1.4404 (AISI 316L), electropolished or pickled |
| Dimensions | 253 × 188 × 140 mm | — | 184 × 184 × 120 mm | 125 × 147 × 112 mm |
| Ambient temperature | -50 °C ... +50 °C | -50 °C ... +50 °C | -50 °C ... +50 °C | -40 °C ... +40 °C |
| Entries | 1 × cable gland M25 Ø13 ... 17 mm; 8 × stopping plug M25 × 1.5; 1 × breather M25 × 1.5 | 1 × cable gland M25 Ø13 ... 17 mm; 6 × stopping plug M25 × 1.5; 1 × breather M25 × 1.5; 2 × transition unit M25 | 2 × E204/622 M25/D9 (Ø13 - 17 mm) or 7 × Ø25 | 1 × E204/622 M25/D9 (Ø13 - 17 mm) or 4 × Ø25 |
Request a price and lead time
TEF1058 wall mounted capillary tube thermostat for heat tracing, Ex db eb IIC T6, 230 V, 16 A, IP66/67. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which temperature ranges does the wall mounted thermostat offer?
Three ranges, -20 to 50 °C, 0 to 120 °C and 0 to 200 °C, each with one change-over contact.
What are the switching capacity and protection degree?
230 V AC and 16 A (T6), with up to 2 (0.4) A for L-4 and 16 (2.5) A for L-2. Protection is IP66/IP67.
How many heating cables are recommended?
Up to 4 heating cables. Explosion protection is Ex db eb IIC T6, ATEX E II 2 G.