International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

TEF1058 wall mounted heat tracing junction box, 4 mm², Ex eb IIC T5 Gb, IP66/67

This TEF1058 junction box mounts on a wall and connects heating cables in heat tracing systems, with a 4 mm² connection cross-section. The 1.4404 (AISI 316L) stainless steel enclosure is rated IP66/67 and marked Ex eb IIC T5 Gb, for -40 °C to +40 °C.

Application
Wall mounted junction box for heat tracing
Enclosure material
Stainless steel 1.4404 (AISI 316L), electropolished or pickled
Protection degree
IP66/67, IP67 without breather
Connection cross-section
4 mm²

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

This TEF1058 junction box is made for heat tracing systems in rough environments, and it is fixed to a wall. It is recommended for up to 2 heating cables and suits Zone 1 and Zone 2.

The acid proof stainless steel enclosure, grade 1.4404 (AISI 316L), is electropolished or pickled and gives maximum strength and corrosion resistance. A stainless steel type label is spot welded to the cover. Several earthing alternatives are offered.

The degree of protection is IP66/67, or IP67 without breather. Connection cross-section is 4 mm². The box measures 125 × 147 × 112 mm, and ambient temperature runs from -40 °C to +40 °C. Explosion protection is Ex eb IIC T5 Gb, with ATEX E II 2 G Ex eb IIC T5 Gb, and the standards are IEC 60079-0 and IEC 60079-7.

Four types are listed. TEF10581138 and TEF10581118 carry 1 cable gland E204/622 M25/D9 (Ø13 - 17 mm), 1 M25 stopping plug and 1 M25 breather. TEF10581128 and TEF10581108 have 4 Ø25 entries with temporary plugs. The label kit is not included.

The boxes are used on oil installations, in the petrochemical industry and in other industries with rough environments. Certificates are ATEX (PRE) and IECEx.

Technical specifications

ApplicationWall mounted junction box for heat tracing
Enclosure materialStainless steel 1.4404 (AISI 316L), electropolished or pickled
Protection degreeIP66/67, IP67 without breather
Connection cross-section4 mm²
Dimensions125 × 147 × 112 mm
Ambient temperature-40 °C ... +40 °C
Explosion protection (IECEx)Ex eb IIC T5 Gb
Explosion protection (ATEX)E II 2 G Ex eb IIC T5 Gb
Heating cablesUp to 2 (recommended)
Entries1 × E204/622 M25/D9 (Ø13 - 17 mm) or 4 × Ø25
StandardsIEC 60079-0; IEC 60079-7

Part numbers

Show all part numbers (4)

TEF10581138 (259489), TEF10581128 (259488), TEF10581118 (259487), TEF10581108 (259486)

How it compares with similar models

ParameterTEF1058 wall mounted heat tracing junction box, 4 mm², Ex eb IIC T5 Gb, IP66/67TEF1058 pipe mounted heat tracing junction box, 4 mm², Ex eb IIC T5 Gb, IP66/67TEF1058 wall mounted junction box for heat tracing, Ex eb IIC T5 Gb, IP66/67TEF1058 pipe mounted junction box for heat tracing, Ex eb IIC T5 Gb, IP66/67
ApplicationWall mounted junction box for heat tracingPipe mounted junction box for heat tracingWall mounted junction box for heat tracing and de-icePipe mounted junction box for heat tracing and de-ice
Protection degreeIP66/67, IP67 without breatherIP66/67, IP67 without breatherIP66/67, IP67 without breatherIP66/IP67, IP67 without breather
Connection cross-section4 mm²4 mm²6 mm²6 mm²
Dimensions125 × 147 × 112 mm~ 189 × ~ 189 × 248 mm184 × 184 × 120 mm—
Ambient temperature-40 °C ... +40 °C-40 °C ... +40 °C-50 °C ... +50 °C—
Entries1 × E204/622 M25/D9 (Ø13 - 17 mm) or 4 × Ø251 × E204/622 M25/D9 (Ø13 - 17 mm) or 4 × Ø252 × E204/622 M25/D9 (Ø13 - 17 mm) or 7 × Ø252 × E204/622 M25/D9 (Ø13 - 17 mm) or 5 × Ø25

Request a price and lead time

TEF1058 wall mounted heat tracing junction box, 4 mm², Ex eb IIC T5 Gb, IP66/67. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which entry versions does the wall mounted box have?

One E204/622 M25/D9 cable gland (Ø13 - 17 mm) with an M25 stopping plug and breather, or 4 Ø25 entries with temporary plugs.

What are the connection cross-section and temperature range?

The connection cross-section is 4 mm² and ambient temperature is -40 °C to +40 °C.

What is the explosion protection marking?

Ex eb IIC T5 Gb to IECEx and E II 2 G Ex eb IIC T5 Gb to ATEX, for Zone 1 and 2.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides