TEF1058 pipe mounted capillary tube thermostat for heat tracing, Ex db eb IIC T6, 230 V, 16 A, IP66/67
The TEF1058 capillary tube thermostat mounts on a pipe and has one change-over contact. Ranges are -20 to 50 °C, 0 to 120 °C and 0 to 200 °C, at 230 V AC and 16 A (T6), in a 1.4404 stainless steel enclosure rated IP66/67.
- Application
- Pipe mounted safety temperature monitor, capillary tube thermostat
- Measuring ranges
- -20 to 50 °C; 0 to 120 °C; 0 to 200 °C
- Contacts
- 1 change-over contact
- Rated operational voltage AC
- 230 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The TEF1058 capillary tube thermostat is intended for heat tracing and de-ice systems. The catalogue lists it as a safety temperature monitor for pipe mounting with one change-over contact. It is recommended for up to 4 heating cables and suits Zone 1 and 2.
Three measuring ranges are offered: -20 to 50 °C (TEF10582560), 0 to 120 °C (TEF10582561) and 0 to 200 °C (TEF10582562). Rated operational voltage is 230 V AC and rated operational current is 16 A (T6). Maximum output AC load is L-4 2 (0.4) A cos φ 1 (0.6) and L-2 16 (2.5) A cos φ 1 (0.6).
The enclosure is electropolished stainless steel 1.4404 (AISI 316L), with protection IP66/IP67, or IP67 without breather. A stainless steel type label is spot welded to the cover, and several earthing alternatives exist. Ambient temperature runs from -50 °C to +50 °C.
Entries are 1 brass M25 cable gland for Ø13 ... 17 mm, 6 brass M25 × 1.5 stopping plugs, 1 M25 × 1.5 breather and 2 M25 transition units. Terminals are 3 two-conductor supply terminals of 10 mm², 5 two-conductor output terminals of 2.5 mm² and 4 two-conductor PE terminals of 10 mm².
Explosion protection is Ex db eb IIC T6 (IECEx) and E II 2 G Ex db eb IIC T6 (ATEX). Standards are IEC 60079-0, IEC 60079-1, IEC 60079-31 and NORSOK. The certificate is ATEX (PRE).
Technical specifications
| Application | Pipe mounted safety temperature monitor, capillary tube thermostat |
|---|---|
| Measuring ranges | -20 to 50 °C; 0 to 120 °C; 0 to 200 °C |
| Contacts | 1 change-over contact |
| Rated operational voltage AC | 230 V |
| Rated operational current | 16 A (T6) |
| Max. output AC load, L-4 | 2 (0.4) A cos φ 1 (0.6) |
| Max. output AC load, L-2 | 16 (2.5) A cos φ 1 (0.6) |
| Degree of protection | IP66/IP67 |
| Enclosure material | Stainless steel 1.4404, electropolished |
| Ambient temperature | -50 °C ... +50 °C |
| Explosion protection | Ex db eb IIC T6; E II 2 G Ex db eb IIC T6 |
| Entries | 1 × cable gland M25 Ø13 ... 17 mm; 6 × stopping plug M25 × 1.5; 1 × breather M25 × 1.5; 2 × transition unit M25 |
| Terminals | 3 × supply 10 mm²; 5 × output 2.5 mm²; 4 × PE 10 mm² |
Part numbers
Show all part numbers (3)
TEF10582560 (259549), TEF10582561 (259550), TEF10582562 (259551)
How it compares with similar models
| Parameter | TEF1058 pipe mounted capillary tube thermostat for heat tracing, Ex db eb IIC T6, 230 V, 16 A, IP66/67 | TEF1058 wall mounted capillary tube thermostat for heat tracing, Ex db eb IIC T6, 230 V, 16 A, IP66/67 | TEF1058 pipe mounted heat tracing junction box, 4 mm², Ex eb IIC T5 Gb, IP66/67 | TEF1058 wall mounted junction box for heat tracing, Ex eb IIC T5 Gb, IP66/67 |
|---|---|---|---|---|
| Application | Pipe mounted safety temperature monitor, capillary tube thermostat | Wall mounted safety temperature monitor, capillary tube thermostat | Pipe mounted junction box for heat tracing | Wall mounted junction box for heat tracing and de-ice |
| Enclosure material | Stainless steel 1.4404, electropolished | Stainless steel 1.4404, electropolished | Stainless steel 1.4404 (AISI 316L), electropolished or pickled | Stainless steel 1.4404 (AISI 316L), electropolished or pickled |
| Ambient temperature | -50 °C ... +50 °C | -50 °C ... +50 °C | -40 °C ... +40 °C | -50 °C ... +50 °C |
| Entries | 1 × cable gland M25 Ø13 ... 17 mm; 6 × stopping plug M25 × 1.5; 1 × breather M25 × 1.5; 2 × transition unit M25 | 1 × cable gland M25 Ø13 ... 17 mm; 8 × stopping plug M25 × 1.5; 1 × breather M25 × 1.5 | 1 × E204/622 M25/D9 (Ø13 - 17 mm) or 4 × Ø25 | 2 × E204/622 M25/D9 (Ø13 - 17 mm) or 7 × Ø25 |
Request a price and lead time
TEF1058 pipe mounted capillary tube thermostat for heat tracing, Ex db eb IIC T6, 230 V, 16 A, IP66/67. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which temperature ranges does the series offer?
Three ranges, -20 to 50 °C, 0 to 120 °C and 0 to 200 °C, each with one change-over contact.
What is the switching capacity of the thermostat?
230 V AC and 16 A (T6). Output loads are up to 2 (0.4) A for L-4 and 16 (2.5) A for L-2, at cos φ 1 (0.6).
What are the explosion protection marking and protection degree?
Ex db eb IIC T6 with ATEX E II 2 G, and IP66/IP67.
Similar equipment from other manufacturers