TEF1058 pipe mounted heat tracing junction box, 4 mm², Ex eb IIC T5 Gb, IP66/67
Mounted on a pipe, this TEF1058 junction box connects heating cables in heat tracing systems with a 4 mm² cross-section. Its 1.4404 (AISI 316L) stainless steel enclosure is rated IP66/67 and marked Ex eb IIC T5 Gb, for -40 °C to +40 °C.
- Application
- Pipe mounted junction box for heat tracing
- Enclosure material
- Stainless steel 1.4404 (AISI 316L), electropolished or pickled
- Protection degree
- IP66/67, IP67 without breather
- Connection cross-section
- 4 mm²
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The pipe mounted TEF1058 junction box connects heating cables in heat tracing systems. It is used on oil installations, in the petrochemical industry and in other industries with rough environments. It is recommended for up to 2 heating cables and suits Zone 1 and Zone 2.
The enclosure is acid proof stainless steel 1.4404 (AISI 316L), electropolished or pickled, giving maximum strength and corrosion resistance. A stainless steel type label is spot welded to the cover, and several earthing alternatives are available.
The degree of protection is IP66/67, or IP67 without breather. Connection cross-section is 4 mm². The approximate size is 189 × 189 × 248 mm, and ambient temperature runs from -40 °C to +40 °C. Explosion protection is Ex eb IIC T5 Gb to IECEx and E II 2 G Ex eb IIC T5 Gb to ATEX.
The types differ in their entries. TEF10581136 and TEF10581116 carry 1 cable gland E204/622 M25/D9 (Ø13 - 17 mm), 1 M25 stopping plug and 1 M25 breather. TEF10581126 and TEF10581106 have 4 Ø25 entries. The label kit is not included. The certificate is ATEX (PRE).
Technical specifications
| Application | Pipe mounted junction box for heat tracing |
|---|---|
| Enclosure material | Stainless steel 1.4404 (AISI 316L), electropolished or pickled |
| Protection degree | IP66/67, IP67 without breather |
| Connection cross-section | 4 mm² |
| Dimensions | ~ 189 × ~ 189 × 248 mm |
| Ambient temperature | -40 °C ... +40 °C |
| Explosion protection (IECEx) | Ex eb IIC T5 Gb |
| Explosion protection (ATEX) | E II 2 G Ex eb IIC T5 Gb |
| Heating cables | Up to 2 (recommended) |
| Entries | 1 × E204/622 M25/D9 (Ø13 - 17 mm) or 4 × Ø25 |
Part numbers
Show all part numbers (4)
TEF10581136 (259481), TEF10581126 (259480), TEF10581116 (259479), TEF10581106 (259478)
How it compares with similar models
| Parameter | TEF1058 pipe mounted heat tracing junction box, 4 mm², Ex eb IIC T5 Gb, IP66/67 | TEF1058 wall mounted heat tracing junction box, 4 mm², Ex eb IIC T5 Gb, IP66/67 | TEF1058 pipe mounted junction box for heat tracing, Ex eb IIC T5 Gb, IP66/67 | TEF1058 wall mounted junction box for heat tracing, Ex eb IIC T5 Gb, IP66/67 |
|---|---|---|---|---|
| Application | Pipe mounted junction box for heat tracing | Wall mounted junction box for heat tracing | Pipe mounted junction box for heat tracing and de-ice | Wall mounted junction box for heat tracing and de-ice |
| Protection degree | IP66/67, IP67 without breather | IP66/67, IP67 without breather | IP66/IP67, IP67 without breather | IP66/67, IP67 without breather |
| Connection cross-section | 4 mm² | 4 mm² | 6 mm² | 6 mm² |
| Dimensions | ~ 189 × ~ 189 × 248 mm | 125 × 147 × 112 mm | — | 184 × 184 × 120 mm |
| Ambient temperature | -40 °C ... +40 °C | -40 °C ... +40 °C | — | -50 °C ... +50 °C |
| Entries | 1 × E204/622 M25/D9 (Ø13 - 17 mm) or 4 × Ø25 | 1 × E204/622 M25/D9 (Ø13 - 17 mm) or 4 × Ø25 | 2 × E204/622 M25/D9 (Ø13 - 17 mm) or 5 × Ø25 | 2 × E204/622 M25/D9 (Ø13 - 17 mm) or 7 × Ø25 |
Request a price and lead time
TEF1058 pipe mounted heat tracing junction box, 4 mm², Ex eb IIC T5 Gb, IP66/67. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which entry versions does the pipe mounted box have?
One E204/622 M25/D9 cable gland (Ø13 - 17 mm) with an M25 stopping plug and breather, or 4 Ø25 entries.
What are the connection cross-section and temperature range?
The connection cross-section is 4 mm² and ambient temperature is -40 °C to +40 °C.
How many heating cables are recommended?
Up to 2 heating cables, and the box suits Zone 1 and 2.