International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

MiniCON 8595/1 NEC/CE Code explosion-protected Ex e plug connectors, 500 V/8 A

The miniCON 8595/1 in NEC/CE Code form covers the Ex e device plug and flange socket with a stainless steel body. Ratings are 500 V AC and 8 A with seven poles and conductors of 24 AWG to 14 AWG (0.25 mm² to 2.5 mm²), IP66/IP67 and enclosure type 3, 4, 4X to UL50 and UL50E.

Type
miniCON NEC/CE Code plug connectors, Ex e
Rated operational voltage AC
500 V
Rated insulation voltage
690 V
Rated operational current AC
8 A

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

The NEC/CE Code version of the miniCON Series 8595/1 plug connectors is intended for Class I, II, Division 2 and for Zones 1 and 21. It comprises an Ex e device plug, an Ex e flange socket and a coupling, with stainless steel bodies; nickel-plated brass versions are available if required.

The connectors have hot swap capability: intrinsically safe signal and power circuits up to 500 V/8 A can be connected and disconnected without a hot work permit. The structure is modular, the connection is made one-handed, and internal coding supports up to three applications.

Ratings are 500 V AC and 8 A, with a switching capacity of AC-3: 550 V/8 A, 690 V rated insulation voltage and 50 - 60 Hz. There are seven poles. Conductor cross-sections span 0.25 mm² to 2.5 mm² (24 AWG to 14 AWG). The data transfer rate is 1000 Mbit/s.

Threads are M20 x 1.5 or M32 x 1.5. Degrees of protection are IP66 and IP67 to IEC 60529 and IP64 to IEC 60079; enclosure type is 3, 4, 4X to UL50 and UL50E. Impact strength is 7 J and the seal is silicone. Ambient temperature is -60 °C ... 75 °C. Dimensions are 110 x 42 x 98 mm for the coupling and 150 x 50 x 138 mm for the plug and receptacle, with 109.10 x 42 x 13 mm and 148.10 x 50 x 13 mm for some versions.

Technical specifications

TypeminiCON NEC/CE Code plug connectors, Ex e
Rated operational voltage AC500 V
Rated insulation voltage690 V
Rated operational current AC8 A
Switching capacityAC-3: 550 V/8 A
No. of poles7
AC frequency range50 - 60 Hz
Connection threadM20 x 1.5; M32 x 1.5
Connection cross-section0.25 mm² to 2.5 mm² (24 AWG to 14 AWG)
Degree of protection (IP)IP66, IP67 (IEC 60529); IP64 (IEC 60079)
Enclosure type (UL50 & UL50E)3, 4, 4X
Impact strength (IEC 60079)7 J
SealSilicone
Ambient temperature-60 °C ... 75 °C
Data transfer rate1000 Mbit/s

Part numbers

Show all part numbers (4)

324646, 324647, 324648, 324649

How it compares with similar models

ParameterMiniCON 8595/1 NEC/CE Code explosion-protected Ex e plug connectors, 500 V/8 AMiniCON 8595/1 flange socket for Ex e enclosures, 500 V/16 A, M32 x 1.5MiniCON 8595/1 explosion-protected plugs, up to 500 V/16 A, 7 P + PE / 8 PMiniCON 8595/1 explosion-protected couplings, up to 500 V/16 A, 7 P + PE / 8 P
TypeminiCON NEC/CE Code plug connectors, Ex eminiCON flange socket for Ex e enclosureminiCON plug, Series 8595/1miniCON coupling, Series 8595/1
Connection threadM20 x 1.5; M32 x 1.5M32 x 1.5—M20 x 1.5; M25 x 1.5
Connection cross-section0.25 mm² to 2.5 mm² (24 AWG to 14 AWG)0.25 mm² to 2.5 mm²0.25 mm² to 2.5 mm² (14 AWG to 24 AWG)0.25 mm² to 2.5 mm² (24 AWG - 16 AWG)

Request a price and lead time

MiniCON 8595/1 NEC/CE Code explosion-protected Ex e plug connectors, 500 V/8 A. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which areas does the NEC/CE Code version cover?

Class I, II, Division 2 and Zones 1 and 21.

What are the rated current and switching capacity?

Rated current is 8 A, with AC-3: 550 V/8 A at 500 V AC.

Which threads, material and protection apply?

M20 x 1.5 and M32 x 1.5 threads, stainless steel bodies, IP66/IP67 and enclosure type 3, 4, 4X to UL50 and UL50E.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides