MiniCON 8595/1 NEC/CE Code explosion-protected Ex e plug connectors, 500 V/8 A
The miniCON 8595/1 in NEC/CE Code form covers the Ex e device plug and flange socket with a stainless steel body. Ratings are 500 V AC and 8 A with seven poles and conductors of 24 AWG to 14 AWG (0.25 mm² to 2.5 mm²), IP66/IP67 and enclosure type 3, 4, 4X to UL50 and UL50E.
- Type
- miniCON NEC/CE Code plug connectors, Ex e
- Rated operational voltage AC
- 500 V
- Rated insulation voltage
- 690 V
- Rated operational current AC
- 8 A
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The NEC/CE Code version of the miniCON Series 8595/1 plug connectors is intended for Class I, II, Division 2 and for Zones 1 and 21. It comprises an Ex e device plug, an Ex e flange socket and a coupling, with stainless steel bodies; nickel-plated brass versions are available if required.
The connectors have hot swap capability: intrinsically safe signal and power circuits up to 500 V/8 A can be connected and disconnected without a hot work permit. The structure is modular, the connection is made one-handed, and internal coding supports up to three applications.
Ratings are 500 V AC and 8 A, with a switching capacity of AC-3: 550 V/8 A, 690 V rated insulation voltage and 50 - 60 Hz. There are seven poles. Conductor cross-sections span 0.25 mm² to 2.5 mm² (24 AWG to 14 AWG). The data transfer rate is 1000 Mbit/s.
Threads are M20 x 1.5 or M32 x 1.5. Degrees of protection are IP66 and IP67 to IEC 60529 and IP64 to IEC 60079; enclosure type is 3, 4, 4X to UL50 and UL50E. Impact strength is 7 J and the seal is silicone. Ambient temperature is -60 °C ... 75 °C. Dimensions are 110 x 42 x 98 mm for the coupling and 150 x 50 x 138 mm for the plug and receptacle, with 109.10 x 42 x 13 mm and 148.10 x 50 x 13 mm for some versions.
Technical specifications
| Type | miniCON NEC/CE Code plug connectors, Ex e |
|---|---|
| Rated operational voltage AC | 500 V |
| Rated insulation voltage | 690 V |
| Rated operational current AC | 8 A |
| Switching capacity | AC-3: 550 V/8 A |
| No. of poles | 7 |
| AC frequency range | 50 - 60 Hz |
| Connection thread | M20 x 1.5; M32 x 1.5 |
| Connection cross-section | 0.25 mm² to 2.5 mm² (24 AWG to 14 AWG) |
| Degree of protection (IP) | IP66, IP67 (IEC 60529); IP64 (IEC 60079) |
| Enclosure type (UL50 & UL50E) | 3, 4, 4X |
| Impact strength (IEC 60079) | 7 J |
| Seal | Silicone |
| Ambient temperature | -60 °C ... 75 °C |
| Data transfer rate | 1000 Mbit/s |
Part numbers
Show all part numbers (4)
324646, 324647, 324648, 324649
How it compares with similar models
| Parameter | MiniCON 8595/1 NEC/CE Code explosion-protected Ex e plug connectors, 500 V/8 A | MiniCON 8595/1 flange socket for Ex e enclosures, 500 V/16 A, M32 x 1.5 | MiniCON 8595/1 explosion-protected plugs, up to 500 V/16 A, 7 P + PE / 8 P | MiniCON 8595/1 explosion-protected couplings, up to 500 V/16 A, 7 P + PE / 8 P |
|---|---|---|---|---|
| Type | miniCON NEC/CE Code plug connectors, Ex e | miniCON flange socket for Ex e enclosure | miniCON plug, Series 8595/1 | miniCON coupling, Series 8595/1 |
| Connection thread | M20 x 1.5; M32 x 1.5 | M32 x 1.5 | — | M20 x 1.5; M25 x 1.5 |
| Connection cross-section | 0.25 mm² to 2.5 mm² (24 AWG to 14 AWG) | 0.25 mm² to 2.5 mm² | 0.25 mm² to 2.5 mm² (14 AWG to 24 AWG) | 0.25 mm² to 2.5 mm² (24 AWG - 16 AWG) |
Request a price and lead time
MiniCON 8595/1 NEC/CE Code explosion-protected Ex e plug connectors, 500 V/8 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which areas does the NEC/CE Code version cover?
Class I, II, Division 2 and Zones 1 and 21.
What are the rated current and switching capacity?
Rated current is 8 A, with AC-3: 550 V/8 A at 500 V AC.
Which threads, material and protection apply?
M20 x 1.5 and M32 x 1.5 threads, stainless steel bodies, IP66/IP67 and enclosure type 3, 4, 4X to UL50 and UL50E.
Similar equipment from other manufacturers