MiniCON 8595/1 flange socket for Ex e enclosures, 500 V/16 A, M32 x 1.5
The Series 8595/1 miniCON flange socket is fitted into the wall of an Ex e enclosure. It is rated 500 V AC and 16 A with seven poles, an M32 x 1.5 thread, conductors of 0.25 mm² to 2.5 mm², a silicone seal, IP66/IP67 and 7 J impact strength.
- Type
- miniCON flange socket for Ex e enclosure
- Rated operational voltage AC
- 500 V
- Rated operational voltage DC
- max. 110 V
- Rated insulation voltage
- 690 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The flange socket of the miniCON Series 8595/1 is mounted in an Ex e enclosure. It brings the enclosure circuits out to a plug connection that accepts a plug of the same series. Inside the enclosure, conductors are attached by crimping or soldering.
It belongs to the 8595/1 range with hot swap capability: intrinsically safe signal and power circuits up to 500 V/16 A can be connected and disconnected without a hot work permit. The connection is made one-handed, and coding from 1 to 3 can be chosen freely to suit the applications.
Ratings are 500 V AC, max. 110 V DC, 690 V rated insulation voltage and 16 A for AC and DC at 50 - 60 Hz, with seven poles. Conductor cross-sections run from 0.25 mm² to 2.5 mm². Contacts are socket or pin type.
The mounting thread is M32 x 1.5, and the body is nickel-plated brass or stainless steel 1.4404. The seal is silicone. Degrees of protection are IP66, IP67 and IP64, with 7 J impact strength. Dimensions are 110 x 98 x 13 mm and weight is 400 g. The relevant standards are IEC 60529 and IEC 60079.
Technical specifications
| Type | miniCON flange socket for Ex e enclosure |
|---|---|
| Rated operational voltage AC | 500 V |
| Rated operational voltage DC | max. 110 V |
| Rated insulation voltage | 690 V |
| Rated operational current AC/DC | 16 A |
| AC frequency range | 50 - 60 Hz |
| Number of poles | 7 |
| Connection thread | M32 x 1.5 |
| Connection cross-section | 0.25 mm² to 2.5 mm² |
| Contact type | Socket contact, pin contact |
| Enclosure material | Nickel-plated brass; stainless steel 1.4404 |
| Seal | Silicone |
| Degree of protection (IP) | IP66, IP67, IP64 |
| Impact strength | 7 J |
| Coding | 1-3, arbitrary |
| Mounting / Installation | Crimping, soldering |
| Dimensions | 110 x 98 x 13 mm |
| Weight | 400 g |
Part numbers
Show all part numbers (5)
298992, 8595/1-CB1-S-S05-00E, 8595/1-CB1-S-S10-00E, 8595/1-CB1-S-S15-00E, 8595/1-CB1-S-S25-00E
How it compares with similar models
| Parameter | MiniCON 8595/1 flange socket for Ex e enclosures, 500 V/16 A, M32 x 1.5 | MiniCON 8595/1 device plug for Ex e enclosures, 500 V/16 A, M32 x 1.5 | MiniCON 8595/1 explosion-protected plugs, up to 500 V/16 A, 7 P + PE / 8 P | MiniCON 8595/1 explosion-protected couplings, up to 500 V/16 A, 7 P + PE / 8 P |
|---|---|---|---|---|
| Type | miniCON flange socket for Ex e enclosure | miniCON device plug for Ex e enclosure | miniCON plug, Series 8595/1 | miniCON coupling, Series 8595/1 |
| Connection thread | M32 x 1.5 | M32 x 1.5 | — | M20 x 1.5; M25 x 1.5 |
| Connection cross-section | 0.25 mm² to 2.5 mm² | 0.25 mm² to 2.5 mm² | 0.25 mm² to 2.5 mm² (14 AWG to 24 AWG) | 0.25 mm² to 2.5 mm² (24 AWG - 16 AWG) |
| Weight | 400 g | 567 g | 174 g; 491 g | up to 323 g |
Request a price and lead time
MiniCON 8595/1 flange socket for Ex e enclosures, 500 V/16 A, M32 x 1.5. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How are conductors attached to the socket?
By crimping or soldering, for cross-sections of 0.25 mm² to 2.5 mm².
Which thread and body materials are used?
An M32 x 1.5 thread, a nickel-plated brass or stainless steel 1.4404 body, and a silicone seal.
What impact strength and degree of protection apply?
7 J impact strength, with IP66, IP67 and IP64 protection.
Similar equipment from other manufacturers