MiniCON 8595/1 explosion-protected plugs, up to 500 V/16 A, 7 P + PE / 8 P
Series 8595/1 miniCON plugs connect cables in hazardous areas of Zones 1, 2, 21 and 22. They are rated 500 V AC and 16 A, with up to eight poles and conductor cross-sections of 0.25 mm² to 2.5 mm². Plastic, stainless steel 1.4404 or nickel-plated brass bodies, IP66/IP67.
- Type
- miniCON plug, Series 8595/1
- Rated operational voltage AC
- 500 V
- Rated operational voltage DC
- max. 110 V
- Rated insulation voltage
- 690 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Series 8595/1 miniCON plugs are explosion-protected connectors for cables in Zones 1, 2, 21 and 22. They have up to eight poles and handle signal and power supplies up to 500 V/16 A. The plug body is plastic or stainless steel.
Hot swap capability means intrinsically safe signal and power circuits up to 500 V/16 A can be connected and disconnected without a hot work permit. The modular structure and logical arrangement of components make mounting quick. A patented single-handed operation joins the plug to its mating part, and internal coding lets the installer define up to three applications.
Electrical ratings are 500 V AC, max. 110 V DC, 690 V rated insulation voltage, 16 A for both AC and DC, at 50 - 60 Hz. Pole configuration is 7 P + PE / 8 P. Conductor cross-sections run from 0.25 mm² to 2.5 mm², with versions for 0.5 mm², 0.75 - 1 mm², 1.5 mm² and 2.5 mm² (14 AWG to 24 AWG).
The cable gland thread is M20 x 1.5 or M25 x 1.5, and body materials are plastic, stainless steel 1.4404 or nickel-plated brass. Reverse versions exist. Degrees of protection are IP66 and IP67 to IEC 60529 and IP64 to IEC 60079, with 7 J impact strength. Ambient temperature is -60 °C ... 75 °C. Length is 148.10 mm and diameter 50 mm, while dimension X depends on the cable gland used. Weight is 174 g or 491 g depending on the version.
Technical specifications
| Type | miniCON plug, Series 8595/1 |
|---|---|
| Rated operational voltage AC | 500 V |
| Rated operational voltage DC | max. 110 V |
| Rated insulation voltage | 690 V |
| Rated operational current AC/DC | 16 A |
| AC frequency range | 50 - 60 Hz |
| Poles | 7 P + PE / 8 P |
| Connection cross-section | 0.25 mm² to 2.5 mm² (14 AWG to 24 AWG) |
| Thread | M20 x 1.5; M25 x 1.5 |
| Body material | Plastic; stainless steel 1.4404; nickel-plated brass |
| Degree of protection | IP66, IP67 (IEC 60529); IP64 (IEC 60079) |
| Impact strength | 7 J |
| Ambient temperature | -60 °C ... 75 °C |
| Zones | 1, 2, 21, 22 |
| Length / diameter | 148.10 mm / Ø 50 mm |
| Weight | 174 g; 491 g |
Part numbers
Show all part numbers (8)
298972, 298963, 298966, 298969, 286547, 286552, 286555, 286594
How it compares with similar models
| Parameter | MiniCON 8595/1 explosion-protected plugs, up to 500 V/16 A, 7 P + PE / 8 P | MiniCON 8595/1 explosion-protected couplings, up to 500 V/16 A, 7 P + PE / 8 P | MiniCON 8595/1 flange socket for Ex e enclosures, 500 V/16 A, M32 x 1.5 | MiniCON 8595/1 device plug for Ex e enclosures, 500 V/16 A, M32 x 1.5 |
|---|---|---|---|---|
| Type | miniCON plug, Series 8595/1 | miniCON coupling, Series 8595/1 | miniCON flange socket for Ex e enclosure | miniCON device plug for Ex e enclosure |
| Connection cross-section | 0.25 mm² to 2.5 mm² (14 AWG to 24 AWG) | 0.25 mm² to 2.5 mm² (24 AWG - 16 AWG) | 0.25 mm² to 2.5 mm² | 0.25 mm² to 2.5 mm² |
| Weight | 174 g; 491 g | up to 323 g | 400 g | 567 g |
Request a price and lead time
MiniCON 8595/1 explosion-protected plugs, up to 500 V/16 A, 7 P + PE / 8 P. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What are the electrical ratings of the 8595/1 plugs?
500 V AC, max. 110 V DC, 690 V insulation voltage, 16 A, 50 - 60 Hz, 7 P + PE / 8 P.
Which conductor cross-sections and cable gland threads are offered?
Cross-sections of 0.5 mm², 0.75 - 1 mm², 1.5 mm² and 2.5 mm², with M20 x 1.5 and M25 x 1.5 threads.
What degree of protection and temperature range apply?
IP66 and IP67 to IEC 60529, IP64 to IEC 60079, and -60 °C ... 75 °C ambient.