Series 8150/5-V11 load disconnect and manual transfer switches, stainless steel, 15–150 A
Series 8150/5-V11 offers non-fused load disconnect and manual transfer switches for 15 - 150 A and up to 600 V AC / 240 V DC. The enclosure is stainless steel 1.4404 (AISI 316L), enclosure type 3, 4, 4X, IP66, rated down to -50 °C.
- Series
- 8150/5-V11
- Rated operational current
- 15 - 150 A
- Rated operational voltage
- up to 600 V AC / 240 V DC
- AC voltage
- 480 V, 600 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Series 8150/5-V11 switches are engineered for hazardous locations and harsh environments, with a corrosion-resistant enclosure and a wide temperature range. They are fitted close to field equipment such as control panels, motors, skids or machinery. A disconnect switch fully de-energises equipment for service or maintenance, while a transfer switch keeps essential equipment supplied.
The enclosure is stainless steel 1.4404 (AISI 316L) with a brushed finish and is wall-mounted. Enclosure type is 3, 4, 4X, IP66, the seal is foamed silicone and no conduit seal is required. Entries are not pre-installed in the standard versions, so size, location and type are chosen by the user.
Current ratings are 15 - 150 A in 1-pole, 2-pole, 3-pole and 3-pole + N form, all non-fused. Rated voltages are AC 480 V and 600 V and DC 60 V, 125 V and 240 V, at 50 – 60 Hz. Horsepower ratings run from 10 hp to 100 hp, with short circuit protection of 10, 20 and 25 kA. The handle can be padlocked three times in the 0 position, and service life is at least 10^5 operating cycles. Connection cross-sections are 14 AWG ... 8 AWG, 12 AWG ... 6 AWG and 10 AWG ... 300 kcmil.
Ambient temperature is -50 °C to +55 °C (-40 °C for some versions). Markings are Class I, Div. 2, Groups A,B,C,D; Ex db eb IIC T.. Gb; Ex tb IIIC T.. Db, with temperature classes T4 / 130 °C, T5 / 95 °C and T6 / 80 °C. Standards are NEC 500, 505, 506, CE Code Section 18, UL50 and UL50E; certificates are USA (FM), Canada (FM), IECEx (PTB) and ATEX (PTB).
Technical specifications
| Series | 8150/5-V11 |
|---|---|
| Rated operational current | 15 - 150 A |
| Rated operational voltage | up to 600 V AC / 240 V DC |
| AC voltage | 480 V, 600 V |
| DC voltage | 60 V, 125 V, 240 V |
| Number of poles | 3-pole, 3-pole + N, 1-pole, 2-pole |
| Version | non-fused |
| Horsepower rating | 10 hp ... 100 hp |
| Short circuit protection (sym) | 10 kA, 20 kA, 25 kA |
| Temperature class | T4 / 130 °C, T5 / 95 °C, T6 / 80 °C |
| Frequency range | 50 – 60 Hz |
| Enclosure type | 3, 4, 4X, IP66 |
| Body material | stainless steel 1.4404 (AISI 316L) |
| Ambient temperature | -50 °C ... +55 °C, -40 °C ... +55 °C |
| Service life | min. 10^5 operating cycles |
| Lockable in | three times in 0 position |
| Connection cross section, stranded | 14 AWG ... 8 AWG, 12 AWG ... 6 AWG, 10 AWG ... 300 kcmil, 10 AWG ... 1/0 AWG |
| Standards | NEC 500, NEC 505, NEC 506, CE Code Section 18, UL50, UL50E |
| Certificates | USA (FM), Canada (FM), IECEx (PTB), ATEX (PTB) |
Part numbers
Show all part numbers (15)
286715, 286716, 286717, 286718, 286719, 286720, 286721, 286722, 286723, 286724, 286725, 286726, 286727, 286728, 286729
How it compares with similar models
| Parameter | Series 8150/5-V11 load disconnect and manual transfer switches, stainless steel, 15–150 A | Series 7150/5-V11 load disconnect and manual transfer switches, stainless steel, 15–150 A, Class I Div. 2 | Series 8146/5-V11 load disconnect and manual transfer switches, 15–150 A, up to 600 V AC / 240 V DC | Series 7146/5-V11 load disconnect and manual transfer switches, 15–150 A, GRP, Class I Div. 2 |
|---|---|---|---|---|
| Number of poles | 3-pole, 3-pole + N, 1-pole, 2-pole | 3-pole, 3-pole + N | 1-pole, 2-pole, 3-pole, 3-pole + N | 3-pole, 3-pole + N |
| Version | non-fused | fused, non-fused | non-fused | fused, non-fused |
| Horsepower rating | 10 hp ... 100 hp | 10 hp, 15 hp, 20 hp, 40 hp, 60 hp, 75 hp, 100 hp | 10 hp, 15 hp, 20 hp, 40 hp, 60 hp, 75 hp, 100 hp | 10 hp, 15 hp, 20 hp, 40 hp, 60 hp, 75 hp, 100 hp |
| Temperature class | T4 / 130 °C, T5 / 95 °C, T6 / 80 °C | T4, T5 | — | T4, T5 |
| Body material | stainless steel 1.4404 (AISI 316L) | stainless steel 1.4404 (AISI 316L) | glass fibre reinforced polyester (GRP / FRP) | glass fibre reinforced polyester (GRP) |
| Ambient temperature | -50 °C ... +55 °C, -40 °C ... +55 °C | -50 °C ... +55 °C, -40 °C ... +55 °C | -50 °C ... +55 °C | — |
Request a price and lead time
Series 8150/5-V11 load disconnect and manual transfer switches, stainless steel, 15–150 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the enclosure made of?
Stainless steel 1.4404 (AISI 316L) with a brushed finish, enclosure type 3, 4, 4X, IP66.
What voltage and current ratings apply?
15 - 150 A and up to 600 V AC / 240 V DC. All versions are non-fused.
Is a conduit seal required?
No. Entries are not pre-installed in the standard versions, so their size, location and type are chosen by the user.