Series 7150/5-V11 load disconnect and manual transfer switches, stainless steel, 15–150 A, Class I Div. 2
Series 7150/5-V11 offers load disconnect and manual transfer switches for 15 - 150 A and up to 600 V AC / 240 V DC, fused and non-fused. The enclosure is stainless steel 1.4404 (AISI 316L), enclosure type 3, 4, 4X, IP66, classified Class I, Div. 2 / AEx Zone 2.
- Series
- 7150/5-V11
- Rated operational current
- 15 - 150 A
- Rated operational voltage
- up to 600 V AC / 240 V DC
- AC voltage
- 480 V, 600 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Series 7150/5-V11 switches are designed for hazardous areas and harsh environments, with a corrosion-resistant enclosure and a wide temperature range. They are installed in the immediate vicinity of field devices such as panels, motors, skids or machines. A disconnector fully interrupts the supply during service or maintenance, while a change-over switch keeps important devices supplied.
The enclosure is stainless steel 1.4404 (AISI 316L) with a brushed finish and a lightweight construction. Enclosure type is 3, 4, 4X, IP66, and no conduit seal is required. Entries are not pre-installed in the standard versions, so size, location and type are left to the user. The rotary actuator is black and can be padlocked in the OFF position in 3 positions.
Current ratings are 15 - 150 A, in 3-pole and 3-pole + N form, fused or non-fused. Rated voltages are AC 480 V and 600 V and DC 60 V, 125 V and 240 V, at 50 – 60 Hz. Horsepower ratings are 10, 15, 20, 40, 60, 75 and 100 hp, with short circuit protection of 10, 20 and 25 kA. Temperature classes are T4 and T5, the connection cross-section is 14 AWG ... 300 kcmil and service life is at least 10^5 operating cycles.
Ambient temperature is -50 °C to +55 °C (-40 °C for some versions). The classification is Class I, Div. 2, Groups A,B,C,D; Zone 2 IIC, with NEC 500, NEC 505, NEC 506 and CE Code Section 18; enclosure type to UL50 and UL50E is 3, 4, 4X. Certificates are USA (FM) and Canada (FM).
Technical specifications
| Series | 7150/5-V11 |
|---|---|
| Rated operational current | 15 - 150 A |
| Rated operational voltage | up to 600 V AC / 240 V DC |
| AC voltage | 480 V, 600 V |
| DC voltage | 60 V, 125 V, 240 V |
| Number of poles | 3-pole, 3-pole + N |
| Version | fused, non-fused |
| Horsepower rating | 10 hp, 15 hp, 20 hp, 40 hp, 60 hp, 75 hp, 100 hp |
| Short circuit protection (sym RMS) | 10 kA, 20 kA, 25 kA |
| Temperature class | T4, T5 |
| Frequency range | 50 – 60 Hz |
| Enclosure type | 3, 4, 4X, IP66 |
| Body material | stainless steel 1.4404 (AISI 316L) |
| Ambient temperature | -50 °C ... +55 °C, -40 °C ... +55 °C |
| Service life | min. 10^5 operating cycles |
| Lockable in | OFF, 3 positions |
| Connection cross section, stranded | 14 AWG ... 300 kcmil |
| Classification | Class I, Div. 2, Groups A,B,C,D; Zone 2 IIC |
| Certificates | USA (FM), Canada (FM) |
Part numbers
Show all part numbers (15)
286697, 286691, 286420, 286693, 286695, 286694, 286701, 286692, 286703, 286712, 286707, 286696, 286713, 286699, 286419
How it compares with similar models
| Parameter | Series 7150/5-V11 load disconnect and manual transfer switches, stainless steel, 15–150 A, Class I Div. 2 | Series 7146/5-V11 load disconnect and manual transfer switches, 15–150 A, GRP, Class I Div. 2 | Series 8150/5-V11 load disconnect and manual transfer switches, stainless steel, 15–150 A | Series 8146/5-V11 load disconnect and manual transfer switches, 15–150 A, up to 600 V AC / 240 V DC |
|---|---|---|---|---|
| Number of poles | 3-pole, 3-pole + N | 3-pole, 3-pole + N | 3-pole, 3-pole + N, 1-pole, 2-pole | 1-pole, 2-pole, 3-pole, 3-pole + N |
| Version | fused, non-fused | fused, non-fused | non-fused | non-fused |
| Horsepower rating | 10 hp, 15 hp, 20 hp, 40 hp, 60 hp, 75 hp, 100 hp | 10 hp, 15 hp, 20 hp, 40 hp, 60 hp, 75 hp, 100 hp | 10 hp ... 100 hp | 10 hp, 15 hp, 20 hp, 40 hp, 60 hp, 75 hp, 100 hp |
| Temperature class | T4, T5 | T4, T5 | T4 / 130 °C, T5 / 95 °C, T6 / 80 °C | — |
| Body material | stainless steel 1.4404 (AISI 316L) | glass fibre reinforced polyester (GRP) | stainless steel 1.4404 (AISI 316L) | glass fibre reinforced polyester (GRP / FRP) |
| Ambient temperature | -50 °C ... +55 °C, -40 °C ... +55 °C | — | -50 °C ... +55 °C, -40 °C ... +55 °C | -50 °C ... +55 °C |
Request a price and lead time
Series 7150/5-V11 load disconnect and manual transfer switches, stainless steel, 15–150 A, Class I Div. 2. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the enclosure made of and what is its type?
Stainless steel 1.4404 (AISI 316L), enclosure type 3, 4, 4X, IP66.
Are fused versions available?
Yes, both fused and non-fused versions, rated 15 - 150 A and up to 600 V AC / 240 V DC.
Which hazardous area classification applies?
Class I, Div. 2, Groups A,B,C,D, and also Zone 2 IIC (AEx Zone 2).