Series 8146/5-V11 load disconnect and manual transfer switches, 15–150 A, up to 600 V AC / 240 V DC
Series 8146/5-V11 for NEC and CE Code installations: non-fused load disconnect and manual transfer switches rated 15 - 150 A and up to 600 V AC / 240 V DC. The enclosure is glass fibre reinforced polyester, enclosure type 3, 4, 4X, IP66, down to -50 °C.
- Series
- 8146/5-V11 (NEC / CE Code)
- Rated operational current
- 15 - 150 A
- Rated operational voltage
- up to 600 V AC / 240 V DC
- AC voltage
- 480 V, 600 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Series 8146/5-V11 switches are engineered for hazardous locations and harsh environments, with a corrosion-resistant enclosure and a wide temperature range. They are installed close to field equipment such as control panels, motors, skids or machinery. A disconnect switch fully de-energises equipment for service or maintenance; a transfer switch keeps essential equipment supplied.
Current ratings run from 15 to 150 A (15, 16, 25, 32, 63, 80, 100, 125 and 150 A), in 1-pole, 2-pole, 3-pole and 3-pole + N form. The switches are non-fused, so an additional fuse is necessary. Rated voltages are AC 480 V and 600 V, and DC 60 V, 125 V and 240 V, at 50 – 60 Hz. Horsepower ratings are 10, 15, 20, 40, 60, 75 and 100 hp, with short circuit protection of 10, 20 and 25 kA. The sturdy rotary actuator is padlockable in the OFF position in 3 positions, and service life is at least 10^5 operating cycles.
The body is glass fibre reinforced polyester (GRP / FRP), enclosure type 3, 4, 4X, IP66, with a foamed silicone seal; no conduit seal is required. Ambient temperature is -50 °C (-40 °C for the transfer switch) to +55 °C. Entries are not pre-installed in the standard versions. Connection cross-sections are 14 AWG ... 8 AWG, 12 AWG ... 6 AWG and 10 AWG ... 300 kcmil.
Markings follow NEC 500, 505, 506 and CE Code Section 18: Class I, Div. 2, Groups A,B,C,D; Ex db eb IIC Gb; Ex tb IIIC T.. Db; temperature classes T4, T5 and T6. Certificates are USA (FM), Canada (FM), IECEx (PTB) and ATEX (PTB).
Technical specifications
| Series | 8146/5-V11 (NEC / CE Code) |
|---|---|
| Rated operational current | 15 - 150 A |
| Rated operational voltage | up to 600 V AC / 240 V DC |
| AC voltage | 480 V, 600 V |
| DC voltage | 60 V, 125 V, 240 V |
| Number of poles | 1-pole, 2-pole, 3-pole, 3-pole + N |
| Version | non-fused |
| Horsepower rating | 10 hp, 15 hp, 20 hp, 40 hp, 60 hp, 75 hp, 100 hp |
| Short circuit protection (sym RMS) | 10 kA, 20 kA, 25 kA |
| Temperature class cFMus | T4, T5, T6 |
| Frequency range | 50 – 60 Hz |
| Enclosure type | 3, 4, 4X, IP66 |
| Body material | glass fibre reinforced polyester (GRP / FRP) |
| Ambient temperature | -50 °C ... +55 °C |
| Service life | min. 10^5 operating cycles |
| Lockable in | OFF, 3 positions |
| Connection cross section, stranded | 14 AWG ... 8 AWG, 12 AWG ... 6 AWG, 10 AWG ... 300 kcmil, 1/0 AWG |
| Certificates | USA (FM), Canada (FM), IECEx (PTB), ATEX (PTB) |
Part numbers
Show all part numbers (15)
286758, 286763, 286761, 286756, 286757, 286760, 286759, 286765, 286764, 286768, 286770, 286767, 286766, 286762, 286769
How it compares with similar models
| Parameter | Series 8146/5-V11 load disconnect and manual transfer switches, 15–150 A, up to 600 V AC / 240 V DC | Series 7150/5-V11 load disconnect and manual transfer switches, stainless steel, 15–150 A, Class I Div. 2 | Series 8150/5-V11 load disconnect and manual transfer switches, stainless steel, 15–150 A | Series 7146/5-V11 load disconnect and manual transfer switches, 15–150 A, GRP, Class I Div. 2 |
|---|---|---|---|---|
| Number of poles | 1-pole, 2-pole, 3-pole, 3-pole + N | 3-pole, 3-pole + N | 3-pole, 3-pole + N, 1-pole, 2-pole | 3-pole, 3-pole + N |
| Version | non-fused | fused, non-fused | non-fused | fused, non-fused |
| Horsepower rating | 10 hp, 15 hp, 20 hp, 40 hp, 60 hp, 75 hp, 100 hp | 10 hp, 15 hp, 20 hp, 40 hp, 60 hp, 75 hp, 100 hp | 10 hp ... 100 hp | 10 hp, 15 hp, 20 hp, 40 hp, 60 hp, 75 hp, 100 hp |
| Body material | glass fibre reinforced polyester (GRP / FRP) | stainless steel 1.4404 (AISI 316L) | stainless steel 1.4404 (AISI 316L) | glass fibre reinforced polyester (GRP) |
| Ambient temperature | -50 °C ... +55 °C | -50 °C ... +55 °C, -40 °C ... +55 °C | -50 °C ... +55 °C, -40 °C ... +55 °C | — |
| Lockable in | OFF, 3 positions | OFF, 3 positions | three times in 0 position | — |
Request a price and lead time
Series 8146/5-V11 load disconnect and manual transfer switches, 15–150 A, up to 600 V AC / 240 V DC. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What current and voltage are the switches rated for?
15 - 150 A and up to 600 V AC / 240 V DC. All versions are non-fused.
What enclosure rating applies, and are conduit seals needed?
Enclosure type 3, 4, 4X, IP66 in glass fibre reinforced polyester. No conduit seal is required, and entries are not pre-installed in the standard versions.
How does a disconnect switch differ from a manual transfer switch?
A disconnect switch de-energises equipment for service or maintenance; a manual transfer switch keeps essential equipment supplied.