Series 8118 Terminal Boxes with 221 Ex Spring-Lever Terminals, Ex e, 440 V
Series 8118 terminal boxes with 221 Ex spring-lever connection terminals come in two design sizes in glass-fibre-reinforced polyester resin. Clamping range 0.14 to 4 mm², 440 V, -55 °C to +75 °C (T6), tool-free wiring.
- Type of protection
- Ex e (Ex i)
- Enclosure material
- Polyester resin, glass fibre reinforced
- Connection technology
- 221 Ex spring lever
- Clamping cross-section
- 0.14 to 4 mm²
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Series 8118 terminal boxes with 221 Ex connection terminals are made of glass fibre reinforced polyester resin. They come in 2 design sizes and take plastic or metal cable glands. They pair the simple 221 terminal installation technology with proven enclosures of increased safety (Ex e) type of protection.
The compact, impact-resistant enclosure is also offered with an integrated metal bracket for metal cable glands, and a fixing carrier for the 221 Ex terminals is pre-installed. Lines go in quickly with spring lever technology, and each clamping unit takes 0.14 to 4 mm². Core end sleeves are not necessary for stranded or finely stranded conductors. The minimum clamping range is 0.2 mm² (solid, stranded) and 0.14 mm² (finely stranded).
2-, 3- and 5-conductor terminal blocks (221-482, 221-483, 221-485) and the PE terminal 281-607/999-950 are available as accessories. Rated voltage is 440 V, and mounting rails are 35 x 50, 35 x 90, 35 x 100 and 35 x 120 mm.
Marking is Ex eb IIC T6 / T5 Gb, Ex ia ib IIC T6 Gb, Ex tb IIIC T80 °C / T95 °C Db and Ex tb IIIC T80 °C Db, for zones 1, 2, 21 and 22. Certificates are ATEX, IECEx, PESO, NEPSI, KTL, ULB and DNV. Ambient temperature is -55 °C ... +75 °C (T6).
Glands come in M20, M25 and M32 x 1.5 with 8290/3 stopping plugs, and weights run from 500 to 860 g.
Technical specifications
| Type of protection | Ex e (Ex i) |
|---|---|
| Enclosure material | Polyester resin, glass fibre reinforced |
| Connection technology | 221 Ex spring lever |
| Clamping cross-section | 0.14 to 4 mm² |
| Min. clamping range | 0.2 mm² (solid, stranded) / 0.14 mm² (finely stranded) |
| Terminal types | 221-482 (2 conductor); 221-483 (3); 221-485 (5); 281-607/999-950 (PE) |
| AC rated operational voltage | 440 V |
| Mounting rail | 35 x 50 mm; 35 x 90 mm; 35 x 100 mm; 35 x 120 mm |
| Cable glands | 8161/7-M20-1304-LT; 8161/8-M20-1304-LT; 8161/7-M25-1707-LT; 8161/7-M32-2109-LT |
| Stopping plugs | 8290/3-M20; 8290/3-M25; 8290/3-M32 |
| Explosion protection | Ex eb IIC T6 / T5 Gb; Ex ia ib IIC T6 Gb; Ex tb IIIC T80 °C / T95 °C Db |
| Ambient temperature | -55 °C ... +75 °C (T6) |
| Certificates | ATEX, IECEx, PESO, NEPSI, KTL, ULB, DNV |
Part numbers
Show all part numbers (2)
276883, 289846
How it compares with similar models
| Parameter | Series 8118 Terminal Boxes with 221 Ex Spring-Lever Terminals, Ex e, 440 V | Series 8118 Junction Boxes, Ex e / Ex i, 4, 5 or 8 Terminals, IP66, up to 6.3 A | Series 8118 Terminal Boxes, Ex e / Ex i, Three Design Sizes, up to 690 V, IP66 | NEC/IEC Series 8146/2 Ex i Terminal Boxes, Ex ia ib IIC T6 Gb, 60 V, IP66 |
|---|---|---|---|---|
| Enclosure material | Polyester resin, glass fibre reinforced | Glass fibre reinforced polyester resin | Polyester resin, glass fibre reinforced | Polyester resin, glass fibre reinforced |
| AC rated operational voltage | 440 V | 550 V; 750 V; 60 V | 690 V (Ex e); 550 V (Ex e with earth plate); 60 V (Ex i) | — |
| Ambient temperature | -55 °C ... +75 °C (T6) | -60 °C ... +40 °C (T6); -60 °C ... +55 °C (T5) | -40 °C ... +40 °C (T6); -40 °C ... +55 °C (T5) | -50 °C ... +75 °C (-58 °F ... +167 °F) |
| Certificates | ATEX, IECEx, PESO, NEPSI, KTL, ULB, DNV | ATEX, IECEx, NEPSI, PESO, KTL, ULB, DNV | ATEX, IECEx, NEPSI, PESO, KTL, ULB, DNV | UL, ATEX, IECEx, PESO, NEPSI, KGS, ITRI, ULB, BVIS |
Request a price and lead time
Series 8118 Terminal Boxes with 221 Ex Spring-Lever Terminals, Ex e, 440 V. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What conductor cross-section can be clamped?
0.14 to 4 mm². Core end sleeves are not necessary for stranded or finely stranded conductors.
Which terminal blocks does the series use?
2-, 3- and 5-conductor blocks (221-482, 221-483, 221-485) and the PE terminal 281-607/999-950.
What ambient temperature range applies?
-55 °C ... +75 °C (T6), at a rated voltage of 440 V.