Series 8102 Junction Boxes, Ex e / Ex i, Polyester Resin, 5 Terminals 4 mm², IP66
Series 8102 are small Ex e and Ex i junction boxes for conducting and distributing electrical energy in hazardous zones 1, 2, 21 and 22. The enclosure is glass-fibre-reinforced polyester resin rated IP66, with five 4 mm² terminals, one of them PE.
- Version
- Ex e; Ex i
- Enclosure material
- Polyester resin, glass fibre reinforced
- IP rating
- IP66
- Terminals
- 5 x mantle terminal 4 mm² (4 + PE)
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Series 8102 junction boxes are small Ex e enclosures for conducting and distributing electrical energy in hazardous areas, and Ex i versions are listed as well. They are moulded from glass-fibre-reinforced polyester resin, which makes the body strong. The degree of protection is IP66.
Each box has 5 mantle terminals of 4 mm², four for power and one used as a PE connection point. The cable range of the mantle terminals is 2 x 4 mm². Entries are plastic semi-glands or polyamide cable glands. Versions exist with three M20 x 1.5 glands (4 – 13 mm or 7 – 13 mm), with two M20 x 1.5 and one M25 x 1.5 gland (7 – 17 mm), and with an M20 x 1.5 stopping plug. Semi-glands cover 6.5 - 14 mm.
The version descriptions give Zone 1, 2, 21 and 22, and the certificates are ATEX, IECEx and NEPSI. Ambient temperature depends on the version. The minimum is -40 or -50 °C and the maximum is +40, +55 or +70 °C, with +70 °C for the Ex i versions.
The box is light, with weights from 0.200 to 0.330 kg depending on the version. Ex i versions list blue glands and Ex e versions black ones.
Selection comes down to the number of entries, the gland type and the ambient temperature range.
Technical specifications
| Version | Ex e; Ex i |
|---|---|
| Enclosure material | Polyester resin, glass fibre reinforced |
| IP rating | IP66 |
| Terminals | 5 x mantle terminal 4 mm² (4 + PE) |
| Cable entries | M20 x 1.5; M25 x 1.5 |
| Cable range, M20 x 1.5 glands | 4 - 13 mm; 7 - 13 mm |
| Cable range, M25 x 1.5 gland | 7 - 17 mm |
| Cable range, semi-glands | 6.5 - 14 mm |
| Min. ambient temperature | -40 °C; -50 °C |
| Max. ambient temperature | +40 °C; +55 °C; +70 °C |
| Zones | 1, 2, 21, 22 |
| Certificates | ATEX, IECEx, NEPSI |
| Weight | 0.200 - 0.330 kg |
Part numbers
Show all part numbers (7)
132979, 218559, 132973, 132975, 261597, 132989, 132988
How it compares with similar models
| Parameter | Series 8102 Junction Boxes, Ex e / Ex i, Polyester Resin, 5 Terminals 4 mm², IP66 | Series 8118 Junction Boxes, Ex e / Ex i, 4, 5 or 8 Terminals, IP66, up to 6.3 A | Series 8118 Terminal Boxes, Ex e / Ex i, Three Design Sizes, up to 690 V, IP66 | Series 8146 Cable End Boxes, Ex e, Terminals up to 185 mm², up to 690 V, up to 400 A |
|---|---|---|---|---|
| Version | Ex e; Ex i | Ex e; Ex i | Ex e; Ex e with earth plate; Ex i | — |
| Enclosure material | Polyester resin, glass fibre reinforced | Glass fibre reinforced polyester resin | Polyester resin, glass fibre reinforced | Glass fibre reinforced polyester resin |
| Terminals | 5 x mantle terminal 4 mm² (4 + PE) | 4, 5 or 8 mantle terminals; miniature fuses (optional) | — | M12 bolt-type, 1-conductor, 185 mm²; 2-conductor 95 mm² |
| Certificates | ATEX, IECEx, NEPSI | ATEX, IECEx, NEPSI, PESO, KTL, ULB, DNV | ATEX, IECEx, NEPSI, PESO, KTL, ULB, DNV | IECEx, ATEX, UL, INMETRO, GL, RS, DNV, RMRS |
| Weight | 0.200 - 0.330 kg | 280 - 500 g | — | 9.5 - 28.7 kg |
Request a price and lead time
Series 8102 Junction Boxes, Ex e / Ex i, Polyester Resin, 5 Terminals 4 mm², IP66. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which versions does Series 8102 include?
Ex e and Ex i versions with M20 x 1.5 or M25 x 1.5 glands or with semi-glands. Each box has five 4 mm² terminals, one of them PE.
What protection rating and enclosure material apply?
IP66, in glass-fibre-reinforced polyester resin.
What ambient temperature range does the series cover?
The minimum is -40 or -50 °C and the maximum is +40, +55 or +70 °C, depending on the version.
Similar equipment from other manufacturers