International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

AC/DC bus ducts for switchgear interconnection

AC and DC bus ducts that interconnect groups of metal-enclosed or metal-clad switchgear, power converters and transformers. The AC duct goes up to 1058 V and 3000 A, the DC duct up to 1200 V and 15000 A.

Product type
AC and DC bus ducts for switchgear interconnection
Rated voltage (AC)
up to 1058 V
Rated voltage (DC)
up to 1200 V
Rated current (AC)
up to 3000 A

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

AC and DC bus ducts are designed for interconnecting groups of metal-enclosed or metal-clad switchgear, power converters and transformers. The manufacturer makes both the bus duct and the switchgear, so the components integrate efficiently on site.

The AC bus duct, a non-segregated phase bus, supports voltages up to 1058 VAC and currents up to 3000 A. All phase conductors share one enclosure with air space between them and no metallic barriers, mounted on custom-moulded fibreglass-reinforced polyester blocks. It is designed to connect transformers to 12-pulse or 6-pulse converters.

The DC bus duct supports voltages up to 1200 VDC and currents up to 15000 A, with each pole in a separate enclosure. It is designed to connect converters to the positive and negative DC switchgear assemblies.

Test voltage at power frequency (1 min) is 4.8 kVrms. AC rated frequency is 50-60 Hz, and the rated short-time withstand current is 30/1 kA/s for AC and 69/0.25 kA/s for DC. Width is 915 mm for AC and 420 mm for DC, height is 400 mm and depth follows the requirements. The enclosure is non-ventilated, and ventilated versions can be provided for indoor use. The standard is IEEE C37.23-2015.

Each bus duct is custom engineered for the installation, with indoor or outdoor rated enclosures. Any length can be built from modules up to 2 metres long. Installation is easy because the busbar and enclosure can be adjusted at each junction, and the bus joints are bolted together with splice plates. Removable covers give access when making joints and during inspections. Application is railway electrification.

Technical specifications

Product typeAC and DC bus ducts for switchgear interconnection
Rated voltage (AC)up to 1058 V
Rated voltage (DC)up to 1200 V
Rated current (AC)up to 3000 A
Rated current (DC)up to 15000 A
Test voltage at power frequency (1 min)4.8 kVrms
Rated frequency (AC)50-60 Hz
Rated short-time withstand current (AC)30/1 kA/s
Rated short-time withstand current (DC)69/0.25 kA/s
Width (AC)915 mm
Width (DC)420 mm
Height400 mm
Lengthmodules up to 2 metres
StandardIEEE C37.23-2015

Request a price and lead time

AC/DC bus ducts for switchgear interconnection. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

What voltage and current do the bus ducts carry?

The AC duct is rated up to 1058 V and 3000 A, and the DC duct up to 1200 V and 15000 A.

How do the AC and DC ducts differ in construction?

The AC duct has all phase conductors in one enclosure with air space between them, while the DC duct has each pole in a separate enclosure.

What module length is used?

Any length is built from modules up to 2 metres long.

Similar equipment from other manufacturers