ВР-220-01 power supply unit for BU/TEL-220-XX (BU-220-01) control blocks, 230 V output
The ВР-220-01 is the power supply for BU/TEL-220-XX (BU-220-01) control blocks in КРУ, КРУН and КСО switchgear of 6-10 kV networks with vacuum breakers. Output is 230±10 V, input is 220 V or a 12...24 V auxiliary source, and mass is up to 2 kg.
- Nominal supply voltage (DC)
- 220 V
- Nominal supply voltage (AC)
- 220 V
- Supply voltage range (DC)
- 75...300 V
- Supply voltage range (AC)
- 75...260 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
ВР-220-01 supplies the BU/TEL-220-XX (BU-220-01) control blocks fitted in indoor and outdoor switchgear cabinets (КРУ, КРУН) and in single-sided service chambers (КСО) of 6-10 kV networks. It is used with vacuum breakers.
The unit is built into a closed metal case. A red «POWER» («МЕРЕЖА») indicator on the front panel shows that supply voltage is present, and a second indicator shows readiness. An impulse flyback converter turns 220 V AC or DC, or a 12...24 V auxiliary source, into a stabilised 230 V DC output.
Supply is 220 V DC within 75...300 V or 220 V AC within 75...260 V, and the shutdown voltage is 440 V (amplitude). Power draw is 120 VA while the voltage is being established and 35 VA in steady state, or 25 VA from the 12...24 V auxiliary source. The 230±10 V output settles in 4 s from 220 V and in 50 s from the auxiliary source, with an output short-circuit current of 0.5 A. Minimum load resistance is 3 kOhm from 220 V and 15 kOhm from the auxiliary source, and the minimum switching period of the vacuum breaker is 2.5 s.
A signalling relay monitors the voltage: overvoltage level 265±15 V with a 10 ms delay, undervoltage level 205±10 V with a 5 s delay. Its contacts switch up to 0.12 A DC (250 V, τ=1 ms) and up to 2 A AC (250 V, cosφ=0.3).
There is no galvanic isolation between the primary supply circuits, the auxiliary source circuits and the 230 V output, so primary and secondary circuits must never be connected together. An earth fault on the output circuits can blow the fuse. Operation from the auxiliary source must not exceed 10…15 min. Storage capacitors of about 5000 µF stay charged to 230 V inside: before installation or servicing, discharge them through a resistor of at least 300 Ohm and at least 5 W, never into a short circuit.
Mean time between failures is 100000 hours and service life is 25 years. Mass is up to 2 kg and dimensions are 180×132×61 mm.
Technical specifications
| Nominal supply voltage (DC) | 220 V |
|---|---|
| Nominal supply voltage (AC) | 220 V |
| Supply voltage range (DC) | 75...300 V |
| Supply voltage range (AC) | 75...260 V |
| Block shutdown voltage (amplitude) | 440 V |
| Power consumption during voltage setting | 120 VA |
| Power consumption in steady state | 35 VA |
| Auxiliary source voltage range | 12...24 V |
| Power consumption from auxiliary source | 25 VA |
| Output voltage | 230±10 V |
| Output voltage setting time (from 220 V / from auxiliary source) | 4 s / 50 s |
| Minimum load resistance (from 220 V / from auxiliary source) | 3 kOhm / 15 kOhm |
| Minimum switching period of vacuum breaker | 2.5 s |
| Overvoltage level / delay | 265±15 V / 10 ms |
| Undervoltage level / delay | 205±10 V / 5 s |
| Mean time between failures | 100000 hours |
| Service life | 25 years |
| Mass | max 2 kg |
| Dimensions | 180×132×61 mm |
Part numbers
Show all part numbers (1)
ВР-220-01 (BP-220-01)
How it compares with similar models
| Parameter | ВР-220-01 power supply unit for BU/TEL-220-XX (BU-220-01) control blocks, 230 V output | BU-220-01 control unit for ISM15_LD switching modules, 230 V supply | AN450 power supply unit, AC 20 V, up to 9 VA, for MK2430 | БРП-01 isolation and noise suppression unit, 60 – 220 V 50 Hz, up to 0.2 A |
|---|---|---|---|---|
| Output voltage | 230±10 V | — | AC 20 V, 50…60 Hz | 60 – 220 V |
| Mass | max 2 kg | max 2 kg | — | max 2,1 kg |
| Dimensions | 180×132×61 mm | max 192×120×68 mm | — | 150х87х122 mm |
Request a price and lead time
ВР-220-01 power supply unit for BU/TEL-220-XX (BU-220-01) control blocks, 230 V output. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What can power the ВР-220-01?
220 V DC (75...300 V), 220 V AC (75...260 V) or a 12...24 V auxiliary source. Running from the auxiliary source is limited to 10…15 min.
What is the output voltage and how quickly does it settle?
230±10 V. It settles in 4 s from 220 V and in 50 s from the auxiliary source.
How does the unit monitor voltage?
A signalling relay responds to overvoltage of 265±15 V with a 10 ms delay and to undervoltage of 205±10 V with a 5 s delay.
Similar equipment from other manufacturers