БРП-01 isolation and noise suppression unit, 60 – 220 V 50 Hz, up to 0.2 A
The БРП-01 provides galvanic isolation and filters switching noise out of the supply to microprocessor and electronic devices. Input and output are 60 – 220 V at 50 Hz, load current is up to 0.2 A and the operating range is -40 to +55 °C.
- Type
- Isolation and noise suppression unit
- Input voltage
- 60 – 220 V
- Output voltage
- 60 – 220 V
- Frequency
- 50 Hz
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The БРП-01 (АЧАБ.468939.004) isolates the mains supply of microprocessor or electronic devices galvanically and suppresses switching noise on it. It suits loads drawing up to 0.2 A at voltages up to 220 V ± 10 % and a frequency of 50 Hz.
Inside are an ОСМ1-0,063 isolating transformer rated 220/220 V and a matching board АЧАБ.687253.054. The secondary winding feeds the load through a noise filter that attenuates switching surge pulses arriving with the input voltage. LEDs indicate the presence of input and output voltage.
Self-resetting fuses protect the primary and secondary windings. They trip at a current above 300 mA and latch. To release them, switch the input voltage off and apply it again after 10 - 30 s.
Input and output voltages are 60 – 220 V at 50 Hz. The output stays within ±10 % of the input at load currents up to 0.10 A (input 60 – 220 V), up to 0.15 A (input 100 – 220 V) and up to 0.20 A (input 140 – 220 V). Insulation resistance between the independent input and output circuits, and to the case, is at least 100 MOhm.
The unit is intended for the УРЧ-3М and УРЧ-3М-С frequency monitoring relays. With AC auxiliary supply of 60 – 220 V it feeds up to two relays. When the relays are fed from the monitored voltage of a voltage transformer with Unom = 100 V, it feeds up to two relays (monitored voltage doubling as auxiliary supply) within 60 – 180 V, or up to four relays with the monitored voltage of 30 – 180 V when auxiliary power comes from another source.
Protection against electric shock is class 0 to ГОСТ 12.2.007.0-75, enclosure protection is IP40 to ГОСТ 14254-96 and terminals are IP20. Climatic version УХЛ3 to ГОСТ 15150-69, operating temperature -40 to +55 °C, installation altitude up to 1000 m, mechanical group М7 to ГОСТ 17516.1-90. Dimensions are 150х87х122 mm and mass is up to 2.1 kg. Mounting position does not matter.
Technical specifications
| Type | Isolation and noise suppression unit |
|---|---|
| Input voltage | 60 – 220 V |
| Output voltage | 60 – 220 V |
| Frequency | 50 Hz |
| Load current | max 0.2 A |
| Output voltage deviation from input | max ±10 % |
| Insulation resistance | min 100 MOhm |
| Fuse trip current | over 300 mA |
| Enclosure protection | IP40 |
| Climatic version | УХЛ3 |
| Operating temperature | -40 to +55 °C |
| Dimensions | 150х87х122 mm |
| Mass | max 2,1 kg |
Part numbers
Show all part numbers (1)
АЧАБ.468939.004
How it compares with similar models
| Parameter | БРП-01 isolation and noise suppression unit, 60 – 220 V 50 Hz, up to 0.2 A | BU-220-01 control unit for ISM15_LD switching modules, 230 V supply | ВР-220-01 power supply unit for BU/TEL-220-XX (BU-220-01) control blocks, 230 V output | AN450 power supply unit, AC 20 V, up to 9 VA, for MK2430 |
|---|---|---|---|---|
| Output voltage | 60 – 220 V | — | 230±10 V | AC 20 V, 50…60 Hz |
| Dimensions | 150х87х122 mm | max 192×120×68 mm | 180×132×61 mm | — |
| Mass | max 2,1 kg | max 2 kg | max 2 kg | — |
Request a price and lead time
БРП-01 isolation and noise suppression unit, 60 – 220 V 50 Hz, up to 0.2 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many УРЧ-3М relays can one unit feed?
Up to two relays on 60 – 220 V auxiliary supply, or up to four relays on a monitored voltage of 30 – 180 V when auxiliary power comes from another source.
How is the unit restored after the fuses trip?
Switch the input voltage off and apply it again after 10 - 30 s. If the trip condition is gone, the unit starts and the input and output voltage indicators light.
What load is permitted at different input voltages?
Up to 0.10 A at 60 – 220 V input, 0.15 A at 100 – 220 V and 0.20 A at 140 – 220 V, with the output within ±10 % of the input.
Similar equipment from other manufacturers