
AN450 power supply unit, AC 20 V, up to 9 VA, for MK2430
The AN450 delivers AC 20 V at up to 9 VA to supply monitoring devices. Its secondary circuit is protected by a PTC resistor. Two versions cover AC 230 V and AC 127 V inputs.
- Supply voltage
- AN450: AC 230 V, 50…60 Hz; AN450-133: AC 127 V, 50…60 Hz
- Operating range of rated voltage
- 0.85…1.1
- Output voltage
- AC 20 V, 50…60 Hz
- Rated output power
- ≤ 9 VA
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Devices that need AC 20 V and draw no more than 9 VA in total can be supplied from the AN450. A single unit can feed, for example, up to 3 MK2430 alarm indicator and test combinations. The AN450 takes AC 230 V, 50…60 Hz, and the AN450-133 takes AC 127 V, 50…60 Hz.
The supply goes to terminals A1/A2 and the AC 20 V, 50…60 Hz output is taken from terminals U2/V2, which must not be interchanged. Two input and two output terminals are provided, so several AN450 units can be connected in parallel if required. The secondary circuit of the built-in safety transformer is protected by a PTC resistor. The operating range of the rated voltage is 0.85…1.1. A green ON LED lights when the unit is operating.
The number of devices that can be connected depends on the voltage drop in the cable between the AN450 and the device. On long cables the voltage at the terminals of the connected device should be checked, and a point-to-point connection is recommended if the drop is too great. The unit complies with IEC 61558-2-6. Rated voltage is AC 250 V, overvoltage category/pollution degree III/2, rated impulse voltage 4 kV and altitude up to 2000 m.
EMC immunity follows EN 61000-6-2 and emission follows EN 61000-6-4. Climatic classes to IEC 60721 are 3K22 in stationary use, 2K11 in transport and 1K21 in storage. Operating temperature is -10…+55 °C, the degree of protection is IP30/IP20 and the flammability class is UL94V-0.
Mounting is by 2 x M4 screws, in standard distribution panels to DIN 43871 or on a rail to IEC 60715, in any position. Screw terminals take 0.2…4/0.2…2.5 mm² (AWG 24-12) with 0.5 Nm tightening torque and 8 mm stripping length. Weight is up to 400 g.
Technical specifications
| Supply voltage | AN450: AC 230 V, 50…60 Hz; AN450-133: AC 127 V, 50…60 Hz |
|---|---|
| Operating range of rated voltage | 0.85…1.1 |
| Output voltage | AC 20 V, 50…60 Hz |
| Rated output power | ≤ 9 VA |
| Internal secondary protection | PTC resistor |
| Rated voltage | AC 250 V |
| Rated impulse voltage | 4 kV |
| Altitude | ≤ 2000 m |
| Operating temperature | -10…+55 °C |
| Degree of protection | IP30/IP20 |
| Standard | IEC 61558-2-6 |
| Weight | ≤ 400 g |
Part numbers
Show all part numbers (2)
B924201, B924203
How it compares with similar models
| Parameter | AN450 power supply unit, AC 20 V, up to 9 VA, for MK2430 | ISOSCAN® EDS441 insulation fault locator for IT systems, 12 channels | RFID105, RFID114 and RFID117 RFID Reader Modules for EV Charging Stations | VIT-A isolated power panels with ATICS® changeover for operating theatres, 5000 to 8000 VA |
|---|---|---|---|---|
| Operating temperature | -10…+55 °C | -25…+55 °C | −30…+70 °C | -10…+55 °C |
| Degree of protection | IP30/IP20 | IP40 (internal); IP20 (terminals) | IP00 | IP21 |
| Weight | ≤ 400 g | ≤ 450 g | 25 g | — |
Request a price and lead time
AN450 power supply unit, AC 20 V, up to 9 VA, for MK2430. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which versions of the AN450 exist?
The AN450 with AC 230 V, 50…60 Hz input (B924201) and the AN450-133 with AC 127 V, 50…60 Hz input (B924203). Both give AC 20 V output.
How many MK2430 units can one AN450 supply?
Up to 3 MK2430 units within the 9 VA limit. The number also depends on the voltage drop in the cable.
Can several AN450 units run in parallel?
Yes, the unit has two input and two output terminals. Terminals A1/A2 and U2/V2 must not be interchanged.
Similar equipment from other manufacturers






