BU-220-01 control unit for ISM15_LD switching modules, 230 V supply
The BU-220-01 closes and trips ISM15_LD switching modules inside relay cabinets (КРП, КРПЗ) and single-sided service chambers (КЗО) of 6-10 kV networks. Nominal supply 230 V (75...300 V), closing time up to 100 ms, tripping time up to 70 ms.
- Type
- Control unit for ISM15_LD switching modules
- Nominal supply voltage
- = 230 V
- Permissible supply voltage range
- 75...300 V
- Current consumption (waiting for closing)
- 11-16 mA
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
BU-220-01 is a control unit that closes and trips switching modules of the ISM15_LD series. It is installed in the relay cabinets of indoor and outdoor switchgear (КРП, КРПЗ) and in single-sided service chambers (КЗО) of 6-10 kV networks.
The unit sits in a closed metal case. Every component of the circuit is mounted on one printed circuit board fixed rigidly inside the case. A spring-clamp connector for wiring is on the side face, with a fuse holder and a blown-fuse indicator above it.
The electromagnetic drive coils of the switching module are connected to the control circuit of the unit. It has closing, tripping and blocking modes: capacitors serve the tripping function and relays block repeated closing. If the supply voltage is lost, the unit can still trip the module from the current circuits.
The unit must be supplied only from the ВР-220-01 power supply; other sources are not permitted. Nominal supply voltage is 230 V and the permissible range is 75...300 V. Closing takes up to 100 ms and tripping up to 70 ms. Mass is up to 2 kg and the dimensions are up to 192×120×68 mm.
Commands are given by closing relay contacts between the closing input (contact 8) or tripping input (contact 9) and the common input ВО (contact 7). Remote control circuits that leave the switchgear building, or run parallel to power circuits at less than 1.2 m, must go through intermediate relays. No extra elements such as resistors, diodes or electronic switches may be placed between the common input and the closing and tripping inputs. Control schemes for the ISM module that differ from the standard ones need the manufacturer's approval.
Technical specifications
| Type | Control unit for ISM15_LD switching modules |
|---|---|
| Nominal supply voltage | = 230 V |
| Permissible supply voltage range | 75...300 V |
| Current consumption (waiting for closing) | 11-16 mA |
| Current consumption (waiting for tripping) | 1.6 mA |
| Current consumption (blocking) | 40 mA |
| Closing time | max 100 ms |
| Tripping time | max 70 ms |
| Mass | max 2 kg |
| Dimensions | max 192×120×68 mm |
Part numbers
Show all part numbers (1)
BU-220-01
How it compares with similar models
| Parameter | BU-220-01 control unit for ISM15_LD switching modules, 230 V supply | ВР-220-01 power supply unit for BU/TEL-220-XX (BU-220-01) control blocks, 230 V output | БРП-01 isolation and noise suppression unit, 60 – 220 V 50 Hz, up to 0.2 A | AN450 power supply unit, AC 20 V, up to 9 VA, for MK2430 |
|---|---|---|---|---|
| Mass | max 2 kg | max 2 kg | max 2,1 kg | — |
| Dimensions | max 192×120×68 mm | 180×132×61 mm | 150х87х122 mm | — |
Request a price and lead time
BU-220-01 control unit for ISM15_LD switching modules, 230 V supply. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What supplies the BU-220-01?
Only the ВР-220-01 power supply; other sources are not permitted. Nominal voltage is 230 V and the permissible range is 75...300 V.
How is a closing or tripping command given?
By closing relay contacts between the closing input (contact 8) or tripping input (contact 9) and the common input ВО (contact 7).
What is the minimum interval between closing operations?
Closing at intervals under 3 s is prohibited, as are more than 5 consecutive closings at intervals under 8 s.
Similar equipment from other manufacturers