AN111 switched-mode power supply, DC 24 V, 24 W, AC 400 V input
The AN111 converts AC 400 V line-to-line voltage into DC 24 V at up to 24 W. It supplies monitoring devices in 400 V systems between phases L1 and L2. The unit is compact and screw or DIN rail mounted.
- Rated supply input voltage UIN
- AC 400 V, 50/60 Hz
- Input voltage range
- +10…-10 % acc. to DIN IEC 60038
- Rated supply output voltage
- DC 24 V
- Power consumption
- 24 W
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
This compact switched-mode power supply unit feeds devices that need DC 24 V and draw up to 24 W in total. The primary side is connected line to line (L-L), so devices can be run from 400 V systems between L1 and L2.
The supply voltage UIN goes to terminals L1/L2 and the DC 24 V output is taken from terminals +/-. The input is rated AC 400 V, 50/60 Hz with a tolerance of +10…-10 % to DIN IEC 60038, and the 5 x 20 mm mains fuse is external. The output has double terminals and a varistor for protection, with a 5 x 20 mm, 1.25 A time-lag fuse in the output circuit. Output voltage follows EN 61131-2 Part 2, the permissible continuous output current is DC 1 A and residual ripple is below 5 %. The fuses are fitted for short-circuit protection only, and the rated current of the unit must not be exceeded.
Generously sized capacitors bridge short gaps during temporary voltage fluctuations. A green LED shows the output status. The unit complies with VDE 0570 Part 2-6, EN 61558-2-6 (safety transformers), EN 61000-3-2 and EN 61131-2 Part 2, and carries the CE mark.
It can be mounted in any position, by screws or on a TS 35 x 7.5 rail to IEC 60715. Connection is by screw terminals for flexible conductors up to 2.5 mm², touch-proof. Degree of protection is IP20, it is prepared for protection class II, and the insulation class is E. Approximate dimensions are 77 mm x 62.5 mm x 122 mm (length, width, depth), and weight is 0.95 kg. Ambient temperature is -10…+60 °C.
Technical specifications
| Rated supply input voltage UIN | AC 400 V, 50/60 Hz |
|---|---|
| Input voltage range | +10…-10 % acc. to DIN IEC 60038 |
| Rated supply output voltage | DC 24 V |
| Power consumption | 24 W |
| Permissible continuous output current | DC 1 A |
| Residual ripple | < 5 % |
| Time-lag fuse, output | 5 x 20 mm, 1.25 A |
| Output protection circuit | varistor |
| Ambient temperature | -10…+60 °C |
| Degree of protection | IP20 |
| Dimensions approx. | 77 mm x 62.5 mm x 122 mm |
| Total weight | 0.95 kg |
Part numbers
Show all part numbers (1)
B94053103
Request a price and lead time
AN111 switched-mode power supply, DC 24 V, 24 W, AC 400 V input. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What input voltage does the AN111 use?
AC 400 V, 50/60 Hz, with a tolerance of +10…-10 %. It connects between two phases, L1 and L2.
What power and current does the DC 24 V output deliver?
Up to 24 W, with a permissible continuous output current of DC 1 A. Residual ripple is below 5 %.
How are the input and output protected?
The input has an external 5 x 20 mm mains fuse. The output has a 1.25 A time-lag fuse and a varistor. The fuses protect against short circuits only.