AN410 primary-pulsed power supply, DC 24 V, up to 10 VA, AC 90…264 V input
The AN410 converts AC 90…264 V or DC 120…370 V into DC 24 V for devices drawing up to 10 VA. It tolerates idling, overload and continuous short circuits. With an AN420-R a redundant supply can be built.
- Rated supply input voltage UIN
- AC 90…264 V, 47…63 Hz; DC 120…370 V
- Rated supply output voltage
- DC 24 V (± 1 %)
- Rated output current
- 420 mA
- Total power consumption
- 10 VA
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Devices that run from DC 24 V and draw up to 10 VA in total can be supplied from the AN410. One unit feeds, for example, up to 3 MK2430 alarm indicator and test combinations or up to 2 MK800.
The supply voltage UIN is connected to terminals L/N and the DC 24 V (±1 %) output is taken from terminals +/-. Rated output current is 420 mA, and the input accepts AC 90…264 V, 47…63 Hz or DC 120…370 V. The secondary circuit has electronic overload protection, and the unit withstands idling, overload and permanent short circuits. The DC ON LED lights green when output voltage is present, and the DC LOW LED lights red when it is too low.
Two AN410 units and an AN420-R redundancy unit (DC 9…35 V input and output) form an uninterruptible redundant supply. Input voltages 1 and 2 must come from independent sources for this. Parallel operation is possible only through the redundancy unit.
Self-consumption is up to 3 W, inrush current is up to 30 A for up to 3 ms and the mains failure bridging time is at least 30 ms. Typical consumption is 184 mA/11.62 W at AC 110 V and 120.6 mA/12 W at AC 230 V. The internal input fuse is 1 A time-lag/AC 250 V. Output current is derated by 2.5 %/K between 60 °C < TU ≤ 70 °C. Insulation coordination to IEC 60664-1 gives 3 kV/2 for impulse voltage/pollution degree and 3 kV for Ui input/output.
EMC follows EN 61000-6-2 and EN 61000-6-3, and the ambient temperature for operation/storage is -25…+70 °C/-25…+85 °C. Screw terminals take conductors of 0.2…2 mm² (AWG 24…14), with 6 mm stripping length and 0.36…0.56 Nm tightening torque. On long cables use adequate cross-sections and star wiring, and check the voltage at the device terminals.
Technical specifications
| Rated supply input voltage UIN | AC 90…264 V, 47…63 Hz; DC 120…370 V |
|---|---|
| Rated supply output voltage | DC 24 V (± 1 %) |
| Rated output current | 420 mA |
| Total power consumption | 10 VA |
| Max. connected devices | 3 MK2430 |
| Self-consumption | ≤ 3 W |
| Inrush current | ≤ 30 A, ≤ 3 ms |
| Mains failure bridging time | ≥ 30 ms |
| Primary fuse | 1 A / AC 250 V |
| Rated impulse voltage/pollution degree | 3 kV/2 |
| Ambient temperature, operation/storage | -25…+70 °C/-25…+85 °C |
| Conductor sizes | 0.2…2 mm² (AWG 24…14) |
Part numbers
Show all part numbers (1)
B924209
Request a price and lead time
AN410 primary-pulsed power supply, DC 24 V, up to 10 VA, AC 90…264 V input. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many devices can an AN410 supply?
Up to 3 MK2430 or up to 2 MK800 units within the 10 VA limit. The number also depends on the voltage drop in the cable.
How is a redundant supply built?
With two AN410 units and an AN420-R redundancy unit. Input voltages 1 and 2 must come from independent sources.
Against what is the output protected?
Idling, overload and permanent short circuits. The secondary circuit has electronic overload protection.