VIT-AFSBY isolated power panels with ATICS® changeover, fault locator and bypass, 5000 to 8000 VA

The VIT-AFSBY supplies socket-outlet circuits in group 2 medical locations such as operating theatres and intensive care units. One cabinet holds an isolating transformer of 5000, 6300 or 8000 VA, an ATICS® changeover module, an insulation fault locator and a bypass switch.

Transformer rating
5000 VA; 6300 VA; 8000 VA
Rated power
3150…8000 VA
Rated input / output voltage
AC 230 V / AC 230/115 V
Rated frequency
50…60 Hz

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

In group 2 medical locations, socket-outlet circuits for medical electrical equipment with a nominal voltage above AC 25 V or DC 60 V must be protected by insulation monitoring with indication in an IT system. The VIT-AFSBY series is built for this duty in operating theatres and intensive care units. A changeover module is also required, so that the supply moves automatically from the safety power source to a second source after a failure.

The IT system cabinet houses an isolating transformer and a UMA710-2-xx-ISO-… changeover and monitoring module with bypass switch, plus the monitoring equipment that DIN VDE 100-710 asks for: changeover control, insulation monitoring, and load and temperature monitoring. The ATICS® device checks incoming and output voltage, operating and changeover times, insulation resistance, load current and transformer temperature. Functional safety follows IEC 61508 (SIL 2) and the changeover time is variable, ≤ 0.5…15 s. With the bypass switch the module can be tested and replaced without a supply interruption.

An insulation fault locator is integrated. While the system runs, it injects a test current of 1 mA and points to the faulty circuit. The cabinet offers 12 or 24 outgoing circuits with 2-pole B16 A circuit breakers. The 6300 and 8000 VA transformers are energy-efficient, with an inrush current < 5 x In, and waste heat leaves by natural convection, without fans, to keep noise down. The 112S measures 374 x 2025 x 425 mm, the 114S 374 x 2325 x 425 mm, and the degree of protection is IP21.

The panel arrives as a ready-to-connect free-standing cabinet with a door and a plinth. Remote alarm indicator and operator panels CP9xx, CP305 and MK2430 connect through the BMS bus (RS-485). The design follows IEC 60364-7-710, IEC 61439-1, -2 and IEC 61558-2-15, and the changeover module can be tested voluntarily by TÜV.

Technical specifications

Transformer rating5000 VA; 6300 VA; 8000 VA
Rated power3150…8000 VA
Rated input / output voltageAC 230 V / AC 230/115 V
Rated frequency50…60 Hz
Rated operational current Ie63 A / 80 A
Rated insulation voltageAC 400 V
Outgoing circuits12 (VIT-AFSBY-112S); 24 (VIT-AFSBY-114S)
Measuring range (insulation)10 k…1 MΩ
Response value Ran150…250 kΩ
Measuring range / response value (current)0…200 A / 1…160 A
Changeover period≤ 0.5 s…15 s
Interface/protocolRS-485/BMS
Operating temperature-10…+55 °C
Degree of protectionIP21
Dimensions 112S / 114S374 x 2025 x 425 mm / 374 x 2325 x 425 mm
Losses at 5000 / 6300 / 8000 VAca. 200 W / ca. 210 W / ca. 230 W

Part numbers

Show all part numbers (6)

VIT-AFSBY-112S-5000VA, VIT-AFSBY-112S-6300VA, VIT-AFSBY-112S-8000VA, VIT-AFSBY-114S-5000VA, VIT-AFSBY-114S-6300VA, VIT-AFSBY-114S-8000VA

How it compares with similar models

ParameterVIT-AFSBY isolated power panels with ATICS® changeover, fault locator and bypass, 5000 to 8000 VAVIT-A isolated power panels with ATICS® changeover for operating theatres, 5000 to 8000 VAATICS®-2-…-ISO automatic transfer switching device with IT system monitoring, 63 and 80 AUMA710-DIO changeover and monitoring module for 80, 125 and 160 A
Operating temperature-10…+55 °C-10…+55 °C-25…+55 °C-10 °C…+55 °C
Degree of protectionIP21IP21IP40—

Request a price and lead time

VIT-AFSBY isolated power panels with ATICS® changeover, fault locator and bypass, 5000 to 8000 VA. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which transformer ratings and circuit counts exist?

Transformers of 5000, 6300 or 8000 VA, with 12 outgoing circuits in the 112S cabinet or 24 in the 114S, using 2-pole B16 A breakers.

Can the changeover module be tested without a shutdown?

Yes. The bypass switch allows the module to be tested and replaced without interrupting the supply.

What are the cabinet dimensions and protection degree?

The VIT-AFSBY-112S measures 374 x 2025 x 425 mm and the VIT-AFSBY-114S 374 x 2325 x 425 mm. Both are rated IP21.