ESL0107 Single-Phase Isolating Transformers, 120…1000 VA, for Operating Theatre Lights
The ESL0107 single-phase isolating transformers supply operating theatre luminaires in Group 2 rooms. Rated power 120…1000 VA, input 230 V, output 23…28 V, reinforced insulation and galvanically isolated windings.
- Rated power
- 120…1000 VA (120, 160, 280, 400, 630, 1000 VA)
- Rated frequency
- 50…60 Hz
- Rated input voltage
- 230 V
- Rated output voltage
- 23…28 V
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The ESL0107 series has reinforced insulation and meets IEC 61558-2-6 / DIN EN 61558-2-6 (VDE 0570-1). The transformers are intended for the power supply of operating theatre luminaires in Group 2 rooms. The windings are galvanically isolated, and tapping points on the primary and secondary sides allow fine-step voltage adaptation.
An electrostatic screen between the primary and secondary windings reduces electrical interference, with its lead brought out to an insulated terminal for the equipotential bonding. The fixing angles are insulated from the core for isolated installation as the standards require. Complete resin impregnation protects against corrosion, and the transformers are designed for dry locations.
The range comprises ESL0107/120, /160, /280, /400, /630 and /1000 for 120, 160, 280, 400, 630 and 1000 VA. Rated input voltage is 230 V, rated output voltage is 23…28 V, frequency is 50…60 Hz and the vector group is IiO. Rated input current runs from 0.6 A to 4.6 A and rated output current from 4.3 A to 35.7 A. The terminals are screw type: 4 mm² flexible and 6 mm² rigid on types /120 to /400, and 10 mm² and 16 mm² on input and output of /630 and /1000.
Degree of protection is IP00 (open construction) and the insulation classification is ta 40/E. Free air circulation must be ensured; an ambient temperature above 40 °C reduces the rated power, and the maximum permissible temperature for insulation class E is 120 °C. Sheet-steel enclosures to IP 23 are available for all standard types, and ESL0107-0 is a sheet-steel enclosure for wall mounting weighing 3.5 kg. Transformer weight is 0.5…5.8 kg and dimensions run from 96 x 96 x 105 mm (ESL0107/120) to 174 x 145 x 175 mm (ESL0107/1000).
Technical specifications
| Rated power | 120…1000 VA (120, 160, 280, 400, 630, 1000 VA) |
|---|---|
| Rated frequency | 50…60 Hz |
| Rated input voltage | 230 V |
| Rated output voltage | 23…28 V |
| Rated input current | 0.6…4.6 A |
| Rated output current | 4.3…35.7 A |
| Vector group | IiO |
| Degree of protection | IP00 (open construction) |
| Insulation classification | ta 40/E |
| Connections | screw terminals |
| Insulation | reinforced, galvanically isolated windings, electrostatic screen |
| Standards | IEC 61558-2-6, DIN EN 61558-2-6 (VDE 0570-1), DIN EN 61558-1, IEC 61558-1 |
| Enclosure (option) | sheet steel, IP 23; ESL0107-0 for wall mounting, 3.5 kg |
| Weight | 0.5…5.8 kg |
| Dimensions | 96 x 96 x 105 mm (ESL0107/120) to 174 x 145 x 175 mm (ESL0107/1000) |
Part numbers
Show all part numbers (6)
B924632 (/120), B924633 (/160), B924634 (/280), B924637 (/400), B924638 (/630), B924639 (/1000)
How it compares with similar models
| Parameter | ESL0107 Single-Phase Isolating Transformers, 120…1000 VA, for Operating Theatre Lights | ES710 Single-Phase Isolating Transformers, 3150…10000 VA, for Medical IT Systems | DS0107 Three-Phase Isolating Transformers with Reinforced Insulation for Three-Phase Loads | WS50x80S…WS80x160S split-core current transformers for residual currents of 10 mA…100 A |
|---|---|---|---|---|
| Rated frequency | 50…60 Hz | 50…60 Hz | 50…60 Hz | 50…400 Hz |
| Vector group | IiO | IiO | Yyn O | — |
| Degree of protection | IP00 (open construction) | IP00 (open design), IP23 (with enclosure) | IP00 (open design), IP23 (with enclosure) | IP40 (internal components), IP20 (terminals) |
| Weight | 0.5…5.8 kg | from 15 kg | 16…155 kg | 900 g (WS50x80S), 1050 g (WS80x80S), 1250 g (WS80x120S), 2550 g (WS80x160S) |
Request a price and lead time
ESL0107 Single-Phase Isolating Transformers, 120…1000 VA, for Operating Theatre Lights. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which power ratings does the ESL0107 series cover?
ESL0107/120, /160, /280, /400, /630 and /1000 for 120, 160, 280, 400, 630 and 1000 VA, with 230 V input and 23…28 V output.
How does ambient temperature affect the rating?
Above 40 °C the rated power is reduced, and the maximum permissible temperature for insulation class E is 120 °C.
Is a protective enclosure available?
Yes, sheet-steel enclosures to IP 23 exist for all standard types, and ESL0107-0 is a wall-mounting sheet-steel enclosure weighing 3.5 kg.