DS0107 Three-Phase Isolating Transformers with Reinforced Insulation for Three-Phase Loads
The DS0107 series are three-phase isolating transformers for three-phase loads in medical locations. Reinforced insulation, galvanically isolated windings, an electrostatic screen, vector group Yyn O and a noise level below 35 dB (A).
- Type
- three-phase isolating transformer
- Types
- DS0107/2000, /3150, /4000, /5000, /6300, /8000, /10000 (K, LG, SK2 designs)
- Rated frequency
- 50…60 Hz
- Vector group
- Yyn O
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The DS0107 transformers have reinforced insulation and comply with IEC 61558-1 / DIN EN 61558-1 (VDE 0570-1) and IEC 61558-2-15 / DIN EN 61558-2-15 (VDE 0570-2-15). They supply three-phase loads in medical locations and also meet IEC 60364-7-710 / DIN VDE 0100-710. The windings are galvanically isolated.
An electrostatic screen sits between the primary and secondary windings to reduce electrical interference, and its lead is brought out to an insulated terminal for the equipotential bonding. The fixing angles are insulated from the core, and complete resin impregnation protects against corrosion. For temperature monitoring a PTC thermistor is wound onto each leg and wired to terminals; the built-in sensors follow DIN 44081 (120 °C). Noise level is below 35 dB (A) at no load and at nominal load.
The transformers come for horizontal or vertical installation in dry locations. Types DS0107/2000, /3150, /4000, /5000, /6300, /8000 and /10000 are made in the standard design and in the K, LG and SK2 designs. The SK2 series is completely encapsulated and fulfils protection class II. Rated frequency is 50…60 Hz; the technical data refer to an ambient temperature of up to 40 °C and 50 Hz. Above 40 °C the rated power is reduced, and cooling air must flow freely.
Protection is IP00 (open design), or IP23 with enclosure, in protection class I or II (encapsulated version). Insulation classification is ta40/B, connections are screw terminals and the vector group is Yyn O. Sheet-steel enclosures to IP 23 are available for all standard types. Weight ranges from 16 kg to 155 kg. The documentation notes that DIN VDE 0100-710 calls for single-phase transformers when building medical IT systems, so the DS0107 is not intended for that purpose. The series is discontinued.
Technical specifications
| Type | three-phase isolating transformer |
|---|---|
| Types | DS0107/2000, /3150, /4000, /5000, /6300, /8000, /10000 (K, LG, SK2 designs) |
| Rated frequency | 50…60 Hz |
| Vector group | Yyn O |
| Insulation | reinforced, galvanically isolated windings |
| Screen | electrostatic, with brought-out insulated terminal |
| Insulation classification | ta40/B |
| Temperature sensors | to DIN 44081 (120 °C), PTC on each leg |
| Degree of protection | IP00 (open design), IP23 (with enclosure) |
| Protection class | I, II (encapsulated SK2 version) |
| Connections | screw terminals |
| Noise level | < 35 dB (A) (no load and nominal load) |
| Installation | horizontal and vertical, dry locations |
| Standards | IEC 61558-1, DIN EN 61558-1 (VDE 0570-1), IEC 61558-2-15, DIN EN 61558-2-15 (VDE 0570-2-15), IEC 60364-7-710, DIN VDE 0100-710 |
| Weight | 16…155 kg |
Part numbers
Show all part numbers (7)
B924694 (/2000), B924106 (/3150), B924121 (/4000), B924112 (/5000), B924107 (/6300), B924628 (/8000), B924672 (/10000)
How it compares with similar models
| Parameter | DS0107 Three-Phase Isolating Transformers with Reinforced Insulation for Three-Phase Loads | ES710 Single-Phase Isolating Transformers, 3150…10000 VA, for Medical IT Systems | ESL0107 Single-Phase Isolating Transformers, 120…1000 VA, for Operating Theatre Lights | WS50x80S…WS80x160S split-core current transformers for residual currents of 10 mA…100 A |
|---|---|---|---|---|
| Rated frequency | 50…60 Hz | 50…60 Hz | 50…60 Hz | 50…400 Hz |
| Vector group | Yyn O | IiO | IiO | — |
| Degree of protection | IP00 (open design), IP23 (with enclosure) | IP00 (open design), IP23 (with enclosure) | IP00 (open construction) | IP40 (internal components), IP20 (terminals) |
| Weight | 16…155 kg | from 15 kg | 0.5…5.8 kg | 900 g (WS50x80S), 1050 g (WS80x80S), 1250 g (WS80x120S), 2550 g (WS80x160S) |
Request a price and lead time
DS0107 Three-Phase Isolating Transformers with Reinforced Insulation for Three-Phase Loads. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What are the DS0107 transformers intended for?
Supplying three-phase loads in medical locations; DIN VDE 0100-710 calls for single-phase transformers when building medical IT systems, so the DS0107 is not intended for that.
What temperature monitoring is provided?
A PTC thermistor is wound onto each leg and wired to terminals, and the built-in sensors follow DIN 44081 (120 °C).
Which design is in protection class II?
The SK2 series, which is completely encapsulated; the standard designs are in protection class I.