International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

UMA710-DIO changeover and monitoring module for 80, 125 and 160 A

The UMA710-DIO changes a load over between two independent supplies and monitors voltage, switch position, switching times and load current. It comes as a 2-pole 80 A unit or a 4-pole unit for 80, 125 and 160 A, with or without a bypass switch.

Nominal current (AC3)
80 A; 125 A; 160 A
Upstream fuse, max
100 A gG; 125 A gG; 160 A gG
Consumption
28 W; 31 W; 39 W; 87 W; 119 W
Rated operational voltage Ue
AC 230 V (160…276 V)

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Two independent supplies feed the UMA710-DIO, and it decides which of them carries the load. It is built around the ATICS® transfer switching device, which puts the electronics and the switching elements in one flat housing. That saves space in the cabinet, cuts the amount of wiring and leaves fewer places for wiring faults. The 2-pole version is rated 80 A and the 4-pole version 80, 125 or 160 A.

The module watches the voltage of both incoming supplies, the output voltage, the switch position, the switching times and the load current. If the preferred supply fails or leaves the permitted voltage range, the load moves to the redundant line, and it returns to the preferred line once the voltage recovers. A switch-back interlock can be programmed. Short-circuit monitoring at the output, or in the distribution board downstream, prevents damaging switching operations. Changeover takes ≤ 0.5 s, the variable changeover period runs ≤ 0.5…15 s, and either line can be assigned as preferred.

The switching system is patented and combines mechanical and electrical interlocking. The contacts resist welding and use circuit-breaker mechanics, and the switch position stays stable under voltage fluctuations and vibration. Functional safety follows IEC 61508 (SIL 2). Manual operation sits on the device and can be locked with a padlock. On the BP version a bypass switch allows testing without interrupting the supply, and connectors on every cable make a replacement possible without a voltage break.

A graphic display shows the operating status together with operating, warning and alarm messages. A history memory records events, messages, tests and parameter changes, and the unit reminds the user of required tests and service. Data exchange and parameter setting run over the BMS bus (RS-485), which also links the TM800, MK800, MK2430 and CP9xx alarm indicator and operator panels. The 4-pole version has 4 programmable output relays and 4 programmable digital inputs. Connections are screwless, mounting is on a DIN rail and the operating temperature is -10 °C…+55 °C. A TÜV test of the device is available as an option. Applicable standards include IEC 61508, DIN VDE 0100-710, EN 61000-6-2 and EN 61000-6-4.

Technical specifications

Nominal current (AC3)80 A; 125 A; 160 A
Upstream fuse, max100 A gG; 125 A gG; 160 A gG
Consumption28 W; 31 W; 39 W; 87 W; 119 W
Rated operational voltage UeAC 230 V (160…276 V)
Nominal system voltage Un3N/AC 400/230 V
Frequency range fn48…62 Hz
Changeover time t≤ 0.5 s
Variable changeover period≤ 0.5…15 s
Operating temperature-10 °C…+55 °C
Overvoltage categoryIII
MountingDIN rail
Digital inputs1 (2-pole); 4 (4-pole)
Outputs3x N/O, 1x changeover (2-pole); 4x programmable (4-pole)
Interface/protocolRS-485/BMS
Functional safetySIL 2 (IEC 61508)

Part numbers

Show all part numbers (8)

B22040182, B22040183, B22040184, B22040185, B22040186, B22040187, B22040188, B22040189

How it compares with similar models

ParameterUMA710-DIO changeover and monitoring module for 80, 125 and 160 AUFA/UMA710-ISO two-pole changeover and IT system monitoring modules, 63 and 80 AATICS®-2/4-…-DIO automatic transfer switching devices for safety power supplies, 63 to 160 ALINETRAXX® VME421H voltage and frequency monitoring relay for AC/DC, no separate supply
MountingDIN railDIN railDIN rail or mounting plate (M5 screws)—
Functional safetySIL 2 (IEC 61508)SIL 2 (IEC 61508)SIL 2—

Request a price and lead time

UMA710-DIO changeover and monitoring module for 80, 125 and 160 A. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which current ratings and pole numbers are available?

A 2-pole version rated 80 A and a 4-pole version rated 80, 125 or 160 A, each with or without a bypass switch (BP).

How fast does it change over, and can the delay be adjusted?

Changeover takes ≤ 0.5 s. The variable changeover period can be set within ≤ 0.5…15 s.

Can the unit be tested without switching the load off?

Yes. On the BP version the bypass switch allows testing without a supply interruption, and connectors on the cables allow a quick replacement.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides