ATICS®-2/4-…-DIO automatic transfer switching devices for safety power supplies, 63 to 160 A
The ATICS®-…-DIO series moves a load automatically from the preferred supply to a second independent one. It covers 2-pole devices for 63 and 80 A and 4-pole devices for 80, 125 and 160 A, with 4 digital inputs and 4 relay outputs, and meets SIL 2.
- Number of poles
- 2; 4
- Rated operational current Ie
- 2-pole: AC 63 A, AC 80 A; 4-pole: AC 80 A, AC 125 A, AC 160 A
- Digital inputs
- 4
- Relay outputs
- 4
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Control electronics and switching elements share a single compact housing in the ATICS®-…-DIO series. The devices change a load over between two independent supplies where continuity matters: group 1 and 2 medical locations, computing centres, industry, hospital main distribution boards and emergency power supplies.
If the preferred supply fails, the device switches to the second one automatically. It has 4 digital inputs, 4 relay outputs and short-circuit detection. Bypass switches allow the device to be tested during operation, and it can be repaired without interrupting the supply. The contact covers are sealable and manual operation is provided. Functional safety is rated SIL 2, with certification by TÜV SÜD.
Five versions make up the range. The two-pole ATICS-2-63A-DIO and ATICS-2-80A-DIO are joined by the four-pole ATICS-4-80A-DIO, ATICS-4-125A-DIO and ATICS-4-160A-DIO. The rated operational current Ie is AC 63 A, AC 80 A, AC 125 A or AC 160 A, depending on the version.
Fit the device on a DIN rail or on a mounting plate, which needs M5 screws. A Torx screwdriver, an Allen key and a torque wrench are required for installation. Accessories include bypass switch sets and the measuring current transformers STW3 and STW4.
The series is designed to DIN VDE 0100-710, IEC 60364-7-710 and DIN VDE 0100-718, and its functional safety is stated under DIN VDE 61508.
Technical specifications
| Number of poles | 2; 4 |
|---|---|
| Rated operational current Ie | 2-pole: AC 63 A, AC 80 A; 4-pole: AC 80 A, AC 125 A, AC 160 A |
| Digital inputs | 4 |
| Relay outputs | 4 |
| Functional safety | SIL 2 |
| Certification | TÜV SÜD |
| Mounting | DIN rail or mounting plate (M5 screws) |
| Standards | DIN VDE 0100-710; IEC 60364-7-710; DIN VDE 0100-718; DIN VDE 61508 |
| Versions | ATICS-2-63A-DIO; ATICS-2-80A-DIO; ATICS-4-80A-DIO; ATICS-4-125A-DIO; ATICS-4-160A-DIO |
Part numbers
Show all part numbers (12)
B92057212, B92057213, B92057252, B92057253, B92057222, B92057223, B92057224, B92057260, B92057262, B92057264, B98021000, B98021001
Request a price and lead time
ATICS®-2/4-…-DIO automatic transfer switching devices for safety power supplies, 63 to 160 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which current ratings and pole numbers exist?
Two-pole versions for AC 63 A and AC 80 A, and four-pole versions for AC 80 A, AC 125 A and AC 160 A.
How many inputs and outputs does the device have?
Four digital inputs and four relay outputs, plus short-circuit detection.
How is it mounted, and which tools are needed?
On a DIN rail or a mounting plate with M5 screws. Installation needs a Torx screwdriver, an Allen key and a torque wrench.
Similar equipment from other manufacturers