УРЧ-3М-С frequency relay, 3 channels, 30.0 to 62.0 Hz
The УРЧ-3М-С monitors mains frequency and its rate of change in power system emergency automation. Three independent channels, 30.0 to 62.0 Hz range, 0.01 Hz resolution, operating supply of 60 to 300 V DC or 60 to 264 V AC.
- Type
- Microprocessor frequency relay
- Independent channels
- 3
- Monitored frequency range
- 30.0…62.0 Hz
- Frequency and setting resolution
- 0.01 Hz
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Relays of the УРЧ-3М-С family measure mains frequency and the rate at which it changes. They are used in emergency automation schemes of power systems and in emergency protection and start-stop automation of hydrogenerators. The range comes in three versions: УРЧ-3М-С, УРЧ-3М-С-01 and УРЧ-3М-С-02.
The relay has three independent channels, each watching for falling and rising frequency. The monitored range is 30.0 to 62.0 Hz, and frequency and settings are displayed in steps of 0.01 Hz. Operating and adjustable reset frequency settings run from 35.00 to 59.99 Hz and time settings from 0.1 to 599.9 s in steps of 0.1 s. Rate-of-change settings are 0.1 to 10.0 Hz/s for the АЧР1 with БССС function and 0.1 to 20.0 Hz/s for the ССЧ and СПЧ functions, in steps of 0.1 Hz/s.
The operating supply is a DC network of 60 to 300 V or an AC network of 60 to 264 V. The monitored network is 35 (50) to 180 V, with the lower values selected by a switch on the front panel. Consumption from the monitored network at 100 V is up to 1.0 VA, from an AC operating supply up to 5.0 VA and from a DC one up to 3.5 VA.
The УРЧ-3М-С-01 monitors 17.0 to 99.9 Hz, with frequency settings of 19.00 to 89.99 Hz and time settings of 0.1 to 899.9 s; the voltages are not combined. The УРЧ-3М-С-02 adds an input for a reserve monitored network F2 and generates a discrete АВР signal; voltage range is 40 (60) to 180 V on F1 and 30 (50) to 180 V on F2, with 1.7 VA drawn from F1 and 1.4 VA from F2.
Output relay contacts switch AC of 6 to 250 V at up to 2 A and DC of up to 250 V at up to 0.1 A. Settings can be executed in continuous or pulse mode; in pulse mode the contacts stay closed for 5 s. A fault is signalled by closing a normally closed contact. Mean time between failures is at least 25000 h, the case is up to 140x85x136 mm and the weight up to 0.9 kg. Operating temperature is -40 to +55 °C. The relay conforms to ТУ У31.2-22965117-008:2007.
Technical specifications
| Type | Microprocessor frequency relay |
|---|---|
| Independent channels | 3 |
| Monitored frequency range | 30.0…62.0 Hz |
| Frequency and setting resolution | 0.01 Hz |
| Operating and reset frequency setting range | 35.00…59.99 Hz |
| Time setting range (step) | 0.1…599.9 s (0.1 s) |
| Rate-of-change setting, АЧР1 with БССС | 0.1…10.0 Hz/s |
| Rate-of-change setting, ССЧ and СПЧ | 0.1…20.0 Hz/s |
| Rate setting resolution | 0.1 Hz/s |
| DC operating supply | 60…300 V |
| AC operating supply | 60…264 V |
| Monitored network | 35 (50)…180 V |
| Power from monitored network at 100 V | max. 1.0 VA |
| Power from operating supply | AC max. 5.0 VA; DC max. 3.5 VA |
| Output relay switching | AC 6…250 V up to 2 A; DC up to 250 V up to 0.1 A |
| Mean time between failures (probability at least 0.8) | at least 25000 h |
| Dimensions | max. 140x85x136 mm |
| Weight | max. 0.9 kg |
| Technical specification | ТУ У31.2-22965117-008:2007 |
Part numbers
Show all part numbers (3)
УРЧ-3М-С, УРЧ-3М-С-01, УРЧ-3М-С-02
Request a price and lead time
УРЧ-3М-С frequency relay, 3 channels, 30.0 to 62.0 Hz. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How do the УРЧ-3М-С-01 and УРЧ-3М-С-02 differ from the base relay?
The УРЧ-3М-С-01 monitors 17.0 to 99.9 Hz with frequency settings of 19.00 to 89.99 Hz and time settings of 0.1 to 899.9 s. The УРЧ-3М-С-02 adds an input for a reserve monitored network F2 and generates a discrete АВР signal.
What supply does the relay need?
Operating supply from a DC network of 60 to 300 V or an AC network of 60 to 264 V. The monitored voltage of 60 to 180 V can also serve as the operating supply.
What output modes does the relay have?
Continuous and pulse. In pulse mode the output relay contacts stay closed for 5 s.