International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

УРЧ-3М-С frequency relay, 3 channels, 30.0 to 62.0 Hz

The УРЧ-3М-С monitors mains frequency and its rate of change in power system emergency automation. Three independent channels, 30.0 to 62.0 Hz range, 0.01 Hz resolution, operating supply of 60 to 300 V DC or 60 to 264 V AC.

Type
Microprocessor frequency relay
Independent channels
3
Monitored frequency range
30.0…62.0 Hz
Frequency and setting resolution
0.01 Hz

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Relays of the УРЧ-3М-С family measure mains frequency and the rate at which it changes. They are used in emergency automation schemes of power systems and in emergency protection and start-stop automation of hydrogenerators. The range comes in three versions: УРЧ-3М-С, УРЧ-3М-С-01 and УРЧ-3М-С-02.

The relay has three independent channels, each watching for falling and rising frequency. The monitored range is 30.0 to 62.0 Hz, and frequency and settings are displayed in steps of 0.01 Hz. Operating and adjustable reset frequency settings run from 35.00 to 59.99 Hz and time settings from 0.1 to 599.9 s in steps of 0.1 s. Rate-of-change settings are 0.1 to 10.0 Hz/s for the АЧР1 with БССС function and 0.1 to 20.0 Hz/s for the ССЧ and СПЧ functions, in steps of 0.1 Hz/s.

The operating supply is a DC network of 60 to 300 V or an AC network of 60 to 264 V. The monitored network is 35 (50) to 180 V, with the lower values selected by a switch on the front panel. Consumption from the monitored network at 100 V is up to 1.0 VA, from an AC operating supply up to 5.0 VA and from a DC one up to 3.5 VA.

The УРЧ-3М-С-01 monitors 17.0 to 99.9 Hz, with frequency settings of 19.00 to 89.99 Hz and time settings of 0.1 to 899.9 s; the voltages are not combined. The УРЧ-3М-С-02 adds an input for a reserve monitored network F2 and generates a discrete АВР signal; voltage range is 40 (60) to 180 V on F1 and 30 (50) to 180 V on F2, with 1.7 VA drawn from F1 and 1.4 VA from F2.

Output relay contacts switch AC of 6 to 250 V at up to 2 A and DC of up to 250 V at up to 0.1 A. Settings can be executed in continuous or pulse mode; in pulse mode the contacts stay closed for 5 s. A fault is signalled by closing a normally closed contact. Mean time between failures is at least 25000 h, the case is up to 140x85x136 mm and the weight up to 0.9 kg. Operating temperature is -40 to +55 °C. The relay conforms to ТУ У31.2-22965117-008:2007.

Technical specifications

TypeMicroprocessor frequency relay
Independent channels3
Monitored frequency range30.0…62.0 Hz
Frequency and setting resolution0.01 Hz
Operating and reset frequency setting range35.00…59.99 Hz
Time setting range (step)0.1…599.9 s (0.1 s)
Rate-of-change setting, АЧР1 with БССС0.1…10.0 Hz/s
Rate-of-change setting, ССЧ and СПЧ0.1…20.0 Hz/s
Rate setting resolution0.1 Hz/s
DC operating supply60…300 V
AC operating supply60…264 V
Monitored network35 (50)…180 V
Power from monitored network at 100 Vmax. 1.0 VA
Power from operating supplyAC max. 5.0 VA; DC max. 3.5 VA
Output relay switchingAC 6…250 V up to 2 A; DC up to 250 V up to 0.1 A
Mean time between failures (probability at least 0.8)at least 25000 h
Dimensionsmax. 140x85x136 mm
Weightmax. 0.9 kg
Technical specificationТУ У31.2-22965117-008:2007

Part numbers

Show all part numbers (3)

УРЧ-3М-С, УРЧ-3М-С-01, УРЧ-3М-С-02

Request a price and lead time

УРЧ-3М-С frequency relay, 3 channels, 30.0 to 62.0 Hz. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How do the УРЧ-3М-С-01 and УРЧ-3М-С-02 differ from the base relay?

The УРЧ-3М-С-01 monitors 17.0 to 99.9 Hz with frequency settings of 19.00 to 89.99 Hz and time settings of 0.1 to 899.9 s. The УРЧ-3М-С-02 adds an input for a reserve monitored network F2 and generates a discrete АВР signal.

What supply does the relay need?

Operating supply from a DC network of 60 to 300 V or an AC network of 60 to 264 V. The monitored voltage of 60 to 180 V can also serve as the operating supply.

What output modes does the relay have?

Continuous and pulse. In pulse mode the output relay contacts stay closed for 5 s.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides