RC03 / RC-10 / RC-15 — control cabinets (controllers) for OSM reclosers up to 38 kV
RC03, RC-10 and RC-15 are control cabinets with relay protection, automation and telecontrol functions for OSM reclosers of the 15–38 kV classes. Together with the recloser and the control cable, the controller forms the OSM Recloser System, ready for operation immediately after installation. The IP66 stainless steel enclosure works from −40 to +55 °C without heaters or ventilation.
- Purpose
- control, protection and automation of OSM reclosers up to 38 kV
- Models
- RC03, RC-10, RC-15
- Enclosure
- stainless steel, IP66
- Operating temperature range
- from −40 to +55 °C
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The RC-10 and RC-15 are built on the Relay 10 and Relay 15 relay modules. Inside is an industrial computer with several processors, a separate FPGA for signal processing and a separate protection processor. The models differ only in communications. The RC-15 has a built-in GPS for event time stamps with microsecond accuracy without communication channels, secure Wi-Fi and a 4G/3G/2G modem. The RC03 is built on the RC10 architecture for three-phase applications; it has a compact IP66 stainless steel enclosure and a configurable MUI-01 interface panel.
There are more than 100 protection functions. They include directional overcurrent protection, earth-fault and negative-sequence protection, and sensitive earth-fault protection with a minimum setting of 200 mA. Operating characteristics are per ANSI, IEC 255 or user-defined, with instantaneous and definite-time stages. Broken-conductor protection, admittance-based protection and harmonic protection are implemented separately. The basic configuration offers synchronism check ANSI 25, an auto-synchroniser, over- and undervoltage and frequency protection with load-shedding functions, and power quality monitoring. Smart Grid logic and automation are programmed on the basis of IEC 61499.
The built-in RTU of the RC-10 and RC-15 supports DNP3, DNP3-SA, DNP3 over IP, IEC 61850 MMS and GOOSE, IEC 60870-5-101/104 and the manufacturer's proprietary protocols. The RC03 has the same set but without IEC 61850. The physical interfaces of the cabinet are Ethernet, USB and RS232. For field work, line crews have the manufacturer's app for Android and iOS.
The event log records the type of fault, the current and the distance to the fault; the data is shown on a 40×17 LCD with backlight. A setting-change log and a load profile are kept, and settings are loaded using the CMS software. The control panel can be moved up to 120 m away from the cabinet.
The cabinet contains only three electronic modules. They are replaced with a screwdriver in five minutes, and the built-in software is updated remotely. The cabinet is connected to the recloser by a control cable 4 to 20 m long.
Technical specifications
| Purpose | control, protection and automation of OSM reclosers up to 38 kV |
|---|---|
| Models | RC03, RC-10, RC-15 |
| Enclosure | stainless steel, IP66 |
| Operating temperature range | from −40 to +55 °C |
| Minimum SEF setting | 200 mA |
| Number of protection functions | more than 100 |
| RC-10 / RC-15 protocols | DNP3, DNP3-SA, DNP3 over IP, IEC 61850 MMS and GOOSE, IEC 60870-5-101/104 |
| RC03 protocols | DNP3, DNP3-SA, DNP3 over IP, IEC 60870-5-101/104 |
| RC-15 additional communications | GPS, secure Wi-Fi, 4G/3G/2G |
| Interfaces | Ethernet, USB, RS232 |
| Display | LCD 40 × 17 with backlight |
| Remote panel | up to 120 m |
| Control cable | 4 to 20 m |
Request a price and lead time
RC03 / RC-10 / RC-15 — control cabinets (controllers) for OSM reclosers up to 38 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Customs codes
| UKTZED (Ukraine) | 8537 10 98 90 |
|---|---|
| HS, 6 digits | 8537 10 |
| CN (EU) | 8537 10 98 |
| HTSUS (USA) | 8537 10 91 70 |
| China customs tariff | 8537 10 90 90 |
Codes are for reference: the final code is determined at declaration for the specific model.
Questions and answers
How does the RC-15 differ from the RC-10?
Only in communications. The RC-15 additionally has a built-in GPS, secure Wi-Fi and a 4G/3G/2G modem.
Which telecontrol protocols does the RC03 support?
DNP3, DNP3-SA, DNP3 over IP and IEC 60870-5-101/104. The RC03 has no IEC 61850 protocol, which is available in the RC-10 and RC-15.
What is the minimum setting of sensitive earth-fault protection?
The minimum SEF setting is 200 mA. In total the controller has more than 100 protection functions.
Similar equipment from other manufacturers