International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

NSA3000T substation and distribution automation: gateways, bay controllers, DTU/FTU, secondary systems for renewable plants

The NSA3000T range combines substation and distribution network automation equipment to IEC 61850. It includes station gateways, bay controllers, DTU and FTU terminals, and integrated systems for digital substations and renewable energy plants. The complex is designed for substations of 35 to 1000 kV classes.

Architecture
IEC 61850, three levels and two networks (process, bay, station)
SOE resolution
≤2 ms (station), ≤1 ms (bay controller)
Gateways
real-time and service; Zhaoxin KX-6640, 32 GB RAM, 12 Ethernet, 8 RS-485 / 4 RS-232, 1 TB
Bay controllers
CT 1 A/5 A, U and I measurement accuracy 0.2%, clock <1 ms/h

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Integrated automation of a digital substation is built on the three levels, two networks scheme. The process, bay and station levels are linked by the station bus and the process bus, and all substation information is presented in digital form. The system includes station monitoring, protection, online monitoring of primary equipment, optical and electronic current and voltage transformers, intelligent terminals and merging units. It supports remote equipment control, programmed switching, condition-based maintenance and adaptive modes.

The event recording resolution is not more than 2 ms at the station level and not more than 1 ms at the bay controller level. A changed analog value reaches the station level in not more than 2 s, a change of a status signal in not more than 1 s. From the command to the start of execution takes not more than 1 s, and switching between the main and backup SCADA servers takes not more than 10 s. Bay controllers are built on a single hardware and software platform, accept CTs of 1 or 5 A, measure voltage and current with an accuracy of 0.2%, have a clock error of less than 1 ms/h, and synchronise by IRIG-B, PPS or SNTP.

Communication gateways come in two types. Real-time gateways transmit data, models and graphics to dispatch centres for remote control and telemetry, and service gateways operate alongside them. The hardware base is Chinese, with a Zhaoxin KX-6640 processor, 32 GB of RAM, a 1 TB drive, and domestic operating systems and DBMS. The gateway has 12 Ethernet ports, 8 RS-485 and 4 RS-232, redundant 110/220 V power supply, and supports the main power system protocols.

For distribution networks, NSA3100HD_D30 DTU terminals are intended for RMUs and distribution points with 8 or 16 bays in 4U and 6U enclosures. The 8-bay version has 100 inputs, 22 outputs and battery management. FTU terminals for overhead feeders have a 32-bit industrial processor and an embedded real-time OS, and withstand continuous overload of 2In and 20In for 1 s. The distribution automation system performs SCADA functions, diagnoses and locates faults, isolates the faulted section with network self-healing, and regulates voltage and reactive power.

The secondary system of step-up substations of wind and solar plants combines plant monitoring, primary frequency regulation, active and reactive power regulation and automated operation tools. The software core runs on different platforms, has a high-performance real-time database, supports SVG and CIM/G, redundancy and load balancing.

Technical specifications

ArchitectureIEC 61850, three levels and two networks (process, bay, station)
SOE resolution≤2 ms (station), ≤1 ms (bay controller)
Gatewaysreal-time and service; Zhaoxin KX-6640, 32 GB RAM, 12 Ethernet, 8 RS-485 / 4 RS-232, 1 TB
Bay controllersCT 1 A/5 A, U and I measurement accuracy 0.2%, clock <1 ms/h
DTU NSA3100HD_D308 or 16 bays (4U/6U), 100 inputs, 22 outputs in the 8-bay version
FTUoverhead feeder terminals, overload 2In continuous, 20In for 1 s
Renewablesprimary frequency regulation, plant P and Q regulation
DMSSCADA, fault location and self-healing, AVR

Request a price and lead time

NSA3000T substation and distribution automation: gateways, bay controllers, DTU/FTU, secondary systems for renewable plants. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Customs codes

UKTZED (Ukraine)8537 10 98 00
HS, 6 digits8537 10
CN (EU)8537 10 98
HTSUS (USA)8537 10 91 70
China customs tariff8537 10 90 90

Codes are for reference: the final code is determined at declaration for the specific model.

Questions and answers

What standard is NSA3000T substation automation built to?

To IEC 61850 with the three levels, two networks scheme. The complex is designed for substations from 35 to 1000 kV.

How accurate are the bay controllers?

The error of voltage and current measurement is 0.2%, and of the clock less than 1 ms/h. The controller accepts CTs of 1 or 5 A and records events with a resolution of 1 ms or better.

How many bays does a DTU terminal serve?

NSA3100HD_D30 is available for 8 or 16 bays in 4U and 6U enclosures. The 8-bay version has 100 inputs and 22 outputs.