LINETRAXX® NGRM750 neutral grounding resistor monitor for LRG systems
The NGRM750 watches the neutral grounding resistor (NGR) in low-resistance grounded (LRG) networks. It detects an open NGR and ground faults, operates at up to 5000 m above sea level and talks Modbus TCP/IP and RTU.
- Supply voltage / frequency
- AC 24…240 V, 40…70 Hz; DC 24…240 V
- Rated voltage
- 690 V
- Capabilities
- up to 25 kV and 2000 A
- Altitude
- up to 5000 m above sea level
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Commercial and industrial LRG power systems are the home of the LINETRAXX® NGRM750, a monitor for the neutral grounding resistor (NGR). It finds the NGR value with passive and active measurement, and it follows the current through the NGR, the voltage across it and the line-to-line and line-to-ground voltages. NGR failure (open) and ground faults are detected, and an alarm or trip signal is given through configurable relays.
Typical uses are generator and transformer grounding. The monitor can be retrofitted to an existing LRG application or installed at the factory in a new LRG package. Capabilities extend to 25 kV and 2000 A, and operation is possible up to 5000 m above sea level.
The menus come in English, German, Spanish and French. Settings are made on a detachable HMI that can be panel or door mounted, or through the built-in webserver. Communication runs over Modbus TCP/IP or Modbus RTU on Ethernet or RS-485 (A/B), and an analogue output of 0…10 V or 4…20 mA is fitted.
The supply is AC 24…240 V, 40…70 Hz, or DC 24…240 V, drawing no more than 6.5 W / 13 VA. Rated voltage is 690 V. Relay contacts are rated AC 250 V/250 V at 5 A/3 A and DC 220/110/24 V at 0.1/0.2/1 A. Operating temperature is -40…+70 °C, and -40…+60 °C for UL applications.
CD-series coupling devices and CTAC, CTAS, CTUB or CTB measuring current transformers connect the monitor to the system, with STEP-PS units to supply the transformers. UL file numbers E493737 and E173157 are listed, and the monitor conforms to AS/NZS 2081.
Technical specifications
| Supply voltage / frequency | AC 24…240 V, 40…70 Hz; DC 24…240 V |
|---|---|
| Rated voltage | 690 V |
| Capabilities | up to 25 kV and 2000 A |
| Altitude | up to 5000 m above sea level |
| Operating temperature | -40…+70 °C |
| UL application temperature | -40…+60 °C |
| Consumption | ≤ 6.5 W / 13 VA |
| Relay rated operating voltage AC | AC 250 V/250 V |
| Relay rated operating current AC | 5 A/3 A |
| Relay rated operating voltage DC | 220/110/24 V |
| Relay rated operating current DC | 0.1/0.2/1 A |
| Interfaces | Ethernet, RS-485 (A/B) |
| Protocols | Modbus TCP/IP, Modbus RTU |
| Analogue output | 0…10 V, 4…20 mA |
Part numbers
Show all part numbers (1)
B94013750
How it compares with similar models
| Parameter | LINETRAXX® NGRM750 neutral grounding resistor monitor for LRG systems | LINETRAXX® NGRM550 neutral grounding resistor monitor for LRG, up to 25 kV | LINETRAXX® NGRM700 neutral grounding resistance monitor for HRG systems | LINETRAXX® NGRM500 neutral grounding resistance monitor for HRG systems |
|---|---|---|---|---|
| Altitude | up to 5000 m above sea level | up to 2000 m AMSL | up to 5000 m AMSL | 2000 m AMSL |
| Operating temperature | -40…+70 °C | -40…+70 °C | -40…+70 °C (-40…160 °F) | -40…+60 °C (-40…140 °F) |
| Analogue output | 0…10 V, 4…20 mA | 0…10 V, 4…20 mA | — | 4…20 mA, 0…10 V, 0…20 mA, 2…10 V |
Request a price and lead time
LINETRAXX® NGRM750 neutral grounding resistor monitor for LRG systems. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which systems is the NGRM750 meant for?
Low-resistance grounded (LRG) systems, including generator and transformer grounding.
What interfaces and protocols does it have?
Ethernet and RS-485 (A/B) with Modbus TCP/IP and Modbus RTU, plus a 0…10 V, 4…20 mA analogue output.
What supply voltage does it accept?
AC 24…240 V (40…70 Hz) or DC 24…240 V, drawing up to 6.5 W / 13 VA.
Similar equipment from other manufacturers