International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

LINETRAXX® NGRM750 neutral grounding resistor monitor for LRG systems

The NGRM750 watches the neutral grounding resistor (NGR) in low-resistance grounded (LRG) networks. It detects an open NGR and ground faults, operates at up to 5000 m above sea level and talks Modbus TCP/IP and RTU.

Supply voltage / frequency
AC 24…240 V, 40…70 Hz; DC 24…240 V
Rated voltage
690 V
Capabilities
up to 25 kV and 2000 A
Altitude
up to 5000 m above sea level

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Commercial and industrial LRG power systems are the home of the LINETRAXX® NGRM750, a monitor for the neutral grounding resistor (NGR). It finds the NGR value with passive and active measurement, and it follows the current through the NGR, the voltage across it and the line-to-line and line-to-ground voltages. NGR failure (open) and ground faults are detected, and an alarm or trip signal is given through configurable relays.

Typical uses are generator and transformer grounding. The monitor can be retrofitted to an existing LRG application or installed at the factory in a new LRG package. Capabilities extend to 25 kV and 2000 A, and operation is possible up to 5000 m above sea level.

The menus come in English, German, Spanish and French. Settings are made on a detachable HMI that can be panel or door mounted, or through the built-in webserver. Communication runs over Modbus TCP/IP or Modbus RTU on Ethernet or RS-485 (A/B), and an analogue output of 0…10 V or 4…20 mA is fitted.

The supply is AC 24…240 V, 40…70 Hz, or DC 24…240 V, drawing no more than 6.5 W / 13 VA. Rated voltage is 690 V. Relay contacts are rated AC 250 V/250 V at 5 A/3 A and DC 220/110/24 V at 0.1/0.2/1 A. Operating temperature is -40…+70 °C, and -40…+60 °C for UL applications.

CD-series coupling devices and CTAC, CTAS, CTUB or CTB measuring current transformers connect the monitor to the system, with STEP-PS units to supply the transformers. UL file numbers E493737 and E173157 are listed, and the monitor conforms to AS/NZS 2081.

Technical specifications

Supply voltage / frequencyAC 24…240 V, 40…70 Hz; DC 24…240 V
Rated voltage690 V
Capabilitiesup to 25 kV and 2000 A
Altitudeup to 5000 m above sea level
Operating temperature-40…+70 °C
UL application temperature-40…+60 °C
Consumption≤ 6.5 W / 13 VA
Relay rated operating voltage ACAC 250 V/250 V
Relay rated operating current AC5 A/3 A
Relay rated operating voltage DC220/110/24 V
Relay rated operating current DC0.1/0.2/1 A
InterfacesEthernet, RS-485 (A/B)
ProtocolsModbus TCP/IP, Modbus RTU
Analogue output0…10 V, 4…20 mA

Part numbers

Show all part numbers (1)

B94013750

How it compares with similar models

ParameterLINETRAXX® NGRM750 neutral grounding resistor monitor for LRG systemsLINETRAXX® NGRM550 neutral grounding resistor monitor for LRG, up to 25 kVLINETRAXX® NGRM700 neutral grounding resistance monitor for HRG systemsLINETRAXX® NGRM500 neutral grounding resistance monitor for HRG systems
Altitudeup to 5000 m above sea levelup to 2000 m AMSLup to 5000 m AMSL2000 m AMSL
Operating temperature-40…+70 °C-40…+70 °C-40…+70 °C (-40…160 °F)-40…+60 °C (-40…140 °F)
Analogue output0…10 V, 4…20 mA0…10 V, 4…20 mA—4…20 mA, 0…10 V, 0…20 mA, 2…10 V

Request a price and lead time

LINETRAXX® NGRM750 neutral grounding resistor monitor for LRG systems. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which systems is the NGRM750 meant for?

Low-resistance grounded (LRG) systems, including generator and transformer grounding.

What interfaces and protocols does it have?

Ethernet and RS-485 (A/B) with Modbus TCP/IP and Modbus RTU, plus a 0…10 V, 4…20 mA analogue output.

What supply voltage does it accept?

AC 24…240 V (40…70 Hz) or DC 24…240 V, drawing up to 6.5 W / 13 VA.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides