International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

LINETRAXX® NGRM700 neutral grounding resistance monitor for HRG systems

The NGRM700 monitors NGR resistance and fault current continuously in high-resistance grounded (HRG) systems. It detects AC and DC ground faults and resistor failure, with a web server, Modbus TCP/RTU and a 1000-event memory.

Supply voltage
AC 24…240 V, DC 24…240 V
Frequency
40…70 Hz
Power consumption
6.5 W/13 VA
Altitude
up to 5000 m AMSL

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

Round-the-clock supervision of the neutral grounding resistor (NGR) and the fault current in an HRG system is the job of the LINETRAXX® NGRM700. The NGR resistance is found with passive and active measurement. The relay detects ground faults and resistor failures and signals them for protection.

Both AC and DC ground faults are detected. Ethernet and the Modbus TCP and Modbus RTU protocols link it to supervision systems and networks, and an integrated web server is included. The event memory holds 1000 events.

Supply is AC 24…240 V (40…70 Hz) or DC 24…240 V at 6.5 W/13 VA. The monitor operates up to 5000 m AMSL without derating, in an ambient range of -40…+70 °C (-40 to 160 °F).

The chassis is mounted on a panel, while the HMI can be detached and fitted in a door. The chassis is rated NEMA 1 (IP30) and its terminals IP20/NEMA 1; the HMI is NEMA 1 (IP30) or, with an optional cover, NEMA 4 (IP65). It was designed for easy retrofitting into existing installations.

CD-series coupling devices and CT-series measuring current transformers connect it to the system, and a voltage supply for the transformers is available. Ordering number B94013700. Installation and wiring are for electrically skilled persons.

Technical specifications

Supply voltageAC 24…240 V, DC 24…240 V
Frequency40…70 Hz
Power consumption6.5 W/13 VA
Altitudeup to 5000 m AMSL
Operating temperature-40…+70 °C (-40…160 °F)
Event memory1000 events
Terminal ratingIP20/NEMA 1
Chassis enclosureNEMA 1 (IP30)
HMI enclosureNEMA 1 (IP30) or NEMA 4 (IP65)
CommunicationEthernet, web server, Modbus TCP/RTU

Part numbers

Show all part numbers (1)

B94013700

How it compares with similar models

ParameterLINETRAXX® NGRM700 neutral grounding resistance monitor for HRG systemsLINETRAXX® NGRM500 neutral grounding resistance monitor for HRG systemsLINETRAXX® NGRM750 neutral grounding resistor monitor for LRG systemsLINETRAXX® NGRM550 neutral grounding resistor monitor for LRG, up to 25 kV
Supply voltageAC 24…240 V, DC 24…240 VAC/DC 24…240 V—AC 48…240 V, 40…70 Hz; DC 48…240 V
Altitudeup to 5000 m AMSL2000 m AMSLup to 5000 m above sea levelup to 2000 m AMSL
Operating temperature-40…+70 °C (-40…160 °F)-40…+60 °C (-40…140 °F)-40…+70 °C-40…+70 °C

Request a price and lead time

LINETRAXX® NGRM700 neutral grounding resistance monitor for HRG systems. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

Which systems is the NGRM700 designed for?

High-resistance grounded (HRG) systems.

What communication does the monitor support?

Ethernet with a web server, Modbus TCP and Modbus RTU.

What altitude can it operate at?

Up to 5000 m AMSL without derating.

Similar equipment from other manufacturers

LET’S CONNECT

Let’s start with your challenge.

Complete a short brief. We will prepare an email you can send from your own email app.

Call us044 339-50-2009:00–18:00
USK ENERGY / SEARCH

Search

Solutions, specialist directions and guides