ISOSCAN® EDS551 insulation fault locator for medical IT systems, 4 or 6 channels
The ISOSCAN® EDS551 locates insulation faults in medical IT systems according to IEC 60364-7-710 and IEC 61557-9. It has integrated current transformers, 4 or 6 channels, a response time of 3…5 s and a DC 24 V supply.
- Supply voltage
- DC 24 V
- Measuring channels
- 4 or 6
- Response time tal
- 3…5 s
- Response value Ran (with Function Module A)
- 50…200 kΩ
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Medical IT systems built to IEC 60364-7-710 and IEC 61557-9 are the main field of the ISOSCAN® EDS551, which finds the circuit with an insulation fault. Current transformers are integrated in the device. It also works in control circuits and in AC and AC/DC IT systems.
An ISOMETER® isoMED527 or LIM7 injects the measuring signal. The EDS551 picks it up through its integrated transformers and identifies the faulty circuit within 3…5 s.
The EDS551-4 has 4 measuring channels and the EDS551-6 has 6. Both come as a basic version and with Function Module A. With Module A the response value Ran can be configured between 50…200 kΩ, and the device also measures leakage capacitance and impedance.
Rated frequency is 42…69 Hz, and the permissible system leakage capacitance Ce is ≤ 5 µF. The supply is DC 24 V. Interfaces are RS-485 and NFC. External signalling can be handled by an alarm combination such as the CP305.
The housing measures 245 × 38 × 40 mm and the weight is 290 g. Operating temperature is −25…55 °C and the altitude limit is 3000 m. Part numbers B71080451 and B71080452 belong to the EDS551-4, while B71080651 and B71080652 belong to the EDS551-6.
Technical specifications
| Supply voltage | DC 24 V |
|---|---|
| Measuring channels | 4 or 6 |
| Response time tal | 3…5 s |
| Response value Ran (with Function Module A) | 50…200 kΩ |
| Rated frequency | 42…69 Hz |
| Permissible system leakage capacitance Ce | ≤ 5 µF |
| Operating temperature | −25…55 °C |
| Altitude | ≤ 3000 m |
| Dimensions | 245 × 38 × 40 (mm) |
| Weight | 290 g |
| Interfaces | RS-485, NFC |
Part numbers
Show all part numbers (4)
B71080451, B71080452, B71080651, B71080652
How it compares with similar models
| Parameter | ISOSCAN® EDS551 insulation fault locator for medical IT systems, 4 or 6 channels | ISOSCAN® EDS441 insulation fault locator for IT systems, 12 channels | ISOSCAN® EDS151 insulation fault locator, 6 channels, 0.5 mA sensitivity | ISOSCAN® EDS150 insulation fault locator for main circuits, 6 channels, 5 mA |
|---|---|---|---|---|
| Supply voltage | DC 24 V | AC/DC 24…240 V | — | AC 17…24 V, 50…60 Hz / DC 14…28 V |
| Operating temperature | −25…55 °C | -25…+55 °C | −25…+55 °C | — |
| Weight | 290 g | ≤ 450 g | ≤ 340 g | — |
Request a price and lead time
ISOSCAN® EDS551 insulation fault locator for medical IT systems, 4 or 6 channels. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which channel counts does the EDS551 come in?
The EDS551-4 has 4 channels and the EDS551-6 has 6. Each is offered as a basic version and with Function Module A.
What does Function Module A add?
The response value Ran becomes configurable between 50…200 kΩ. The device also measures leakage capacitance and impedance.
What supply and interfaces does the EDS551 have?
The supply is DC 24 V. The interfaces are RS-485 and NFC.
Similar equipment from other manufacturers