ISOSCAN® EDS150 insulation fault locator for main circuits, 6 channels, 5 mA
The ISOSCAN® EDS150 localises insulation faults in the main circuits of AC, AC/DC and DC IT systems. It has 6 channels with integrated current transformers, a response sensitivity of 5 mA and up to 528 circuits on the BMS bus.
- Number of measuring channels
- 6
- Response sensitivity
- 5 mA
- Response time in the AC system
- max. 8 s
- Max. devices on the BMS bus
- 88
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The ISOSCAN® EDS150 is an insulation fault locator for the main circuits of unearthed power supplies (IT systems), whether AC, AC/DC or DC. Among its uses are DC main circuits in industrial plants, power stations and ships.
The locating current needed for the search is supplied by an ISOMETER® IRDH575 or a PGH471 locating current injector, and either of them starts the search. After the start, the EDS150 scans all measuring channels 1…6 through its integrated measuring current transformers.
When the response value of 5 mA is exceeded in a channel, the associated alarm LED lights. The alarm message, with address and channel number, leaves through the BMS interface. The faulty circuit is shown on an alarm and test combination or on a BMS master with a display.
Up to 88 EDS150 units connect over the RS-485 interface with the BMS protocol, so up to 528 circuits can be monitored. The BMS address range is 3…90. The response time in an AC system is up to 8 s according to IEC 61557-9, and the device runs a cyclical self test.
The version with part number B91080103 is supplied with AC 17…24 V, 50…60 Hz or DC 14…28 V. External supply comes from the AN410 (AC 90…264 V / DC 120…370 V), AN450 (AC 230 V) or AN450-133 (AC 127 V) power supply units.
Technical specifications
| Number of measuring channels | 6 |
|---|---|
| Response sensitivity | 5 mA |
| Response time in the AC system | max. 8 s |
| Max. devices on the BMS bus | 88 |
| Max. circuits | 528 |
| BMS address range | 3…90 |
| Interface/protocol | RS-485 / BMS |
| Supply voltage | AC 17…24 V, 50…60 Hz / DC 14…28 V |
| Locating current source | ISOMETER® IRDH575 or PGH471 |
Part numbers
Show all part numbers (1)
B91080103
Request a price and lead time
ISOSCAN® EDS150 insulation fault locator for main circuits, 6 channels, 5 mA. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What supplies the locating current for the EDS150?
An ISOMETER® IRDH575 or a PGH471 locating current injector. Either of them also starts the search.
What is the response sensitivity of the EDS150?
The response value is 5 mA. In an AC system the response time is up to 8 s according to IEC 61557-9.
How many circuits can one EDS150 system monitor?
Up to 88 devices with 6 channels each share the BMS bus, which gives up to 528 circuits. BMS addresses run from 3…90.
Similar equipment from other manufacturers