International supply. Engineering expertise.
office@usk.ua09:00–18:00 · Kyiv

LINETRAXX® NGRM500 neutral grounding resistance monitor for HRG systems

The NGRM500 monitors the current through the NGR, the voltage between the transformer star point and earth, and the condition of the NGR itself. It measures resistance by active and passive methods and has a web server, Modbus TCP and RTU, and three relays.

Supply voltage
AC/DC 24…240 V
Frequency
40…70 Hz
Power consumption
6.5 W/13 VA
Altitude
2000 m AMSL

Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.

Description

For high-resistance grounded (HRG) systems, the LINETRAXX® NGRM500 monitors the current through the neutral grounding resistor (NGR), the voltage between the transformer star point and earth, and the state of the NGR. RNGR is determined by passive and active measurement, selectable by the user as automatic or passive, and monitoring carries on even if the installation is de-energised.

The monitor detects an open NGR, a shorted NGR, AC and DC ground faults and neutral overvoltage, and it calibrates itself to the monitored system. The tolerance on NGR resistance and ground loop resistance can be set from 10 to 200 %. For ground-fault detection a broadband, fundamental-frequency or band-pass filter is selected, with limits from 0 to 1.9 kHz. The measuring signals undergo FFT analysis, and a pulser supports manual location of the fault.

A graphical user interface offers US English, UK English, French, German and Spanish. Ethernet with a web server handles settings and alarm notification, alongside Modbus TCP, Modbus RTU, the BCOM protocol and a 1000-event data logger with date and time stamps.

Three changeover relays serve ground fault, NGR fault and trip, with fail-safe operation selectable. The analogue output (4…20 mA, 0…10 V, 0…20 mA or 2…10 V) can represent 0…100 % of NGR current or 0…200 % of NGR resistance. Two digital outputs and a selectable audible alarm are also provided.

Supply is AC/DC 24…240 V, 50/60 Hz, up to 6.5 W/13 VA. The chassis is rated NEMA 1 (IP30) and the terminals IP20/NEMA 1, with operation up to 2000 m AMSL at -40…+60 °C. It is DIN rail mounted, and for systems up to 25 kV it connects through a CD-series coupling device with measuring current transformers.

Technical specifications

Supply voltageAC/DC 24…240 V
Frequency40…70 Hz
Power consumption6.5 W/13 VA
Altitude2000 m AMSL
Operating temperature-40…+60 °C (-40…140 °F)
EnclosureNEMA 1 (IP30)
Terminal ratingIP20/NEMA 1
Relays3 changeover contacts
Analogue output4…20 mA, 0…10 V, 0…20 mA, 2…10 V
NGR resistance tolerance10…200 %
Band-pass filter range0…1.9 kHz
Event logger1000 events
CommunicationEthernet, web server, Modbus TCP/RTU

Part numbers

Show all part numbers (1)

B94013500

How it compares with similar models

ParameterLINETRAXX® NGRM500 neutral grounding resistance monitor for HRG systemsLINETRAXX® NGRM700 neutral grounding resistance monitor for HRG systemsLINETRAXX® NGRM750 neutral grounding resistor monitor for LRG systemsLINETRAXX® NGRM550 neutral grounding resistor monitor for LRG, up to 25 kV
Supply voltageAC/DC 24…240 VAC 24…240 V, DC 24…240 V—AC 48…240 V, 40…70 Hz; DC 48…240 V
Altitude2000 m AMSLup to 5000 m AMSLup to 5000 m above sea levelup to 2000 m AMSL
Operating temperature-40…+60 °C (-40…140 °F)-40…+70 °C (-40…160 °F)-40…+70 °C-40…+70 °C
Analogue output4…20 mA, 0…10 V, 0…20 mA, 2…10 V—0…10 V, 4…20 mA0…10 V, 4…20 mA

Request a price and lead time

LINETRAXX® NGRM500 neutral grounding resistance monitor for HRG systems. We reply within one business day.

* — required fields

Or email sales@usk.ua or call 044 339-50-20.

Questions and answers

How does the NGRM500 determine NGR resistance?

By passive and active measurement, selectable as automatic or passive, and it continues even when the installation is de-energised.

What outputs does it have?

Three changeover relays, an analogue output of 4…20 mA, 0…10 V, 0…20 mA or 2…10 V, and two digital outputs.

Which interfaces and protocols are supported?

Ethernet with a web server, Modbus TCP and Modbus RTU, plus BCOM.