LINETRAXX® NGRM550 neutral grounding resistor monitor for LRG, up to 25 kV
The NGRM550 measures the current through the NGR and the voltage between the star point and ground in low-resistance grounded (LRG) systems. It detects an open NGR and ground faults, with a webserver and Modbus TCP/IP or RTU.
- Supply voltage
- AC 48…240 V, 40…70 Hz; DC 48…240 V
- Maximum voltage
- 25 kV
- Maximum current
- 2000 A
- Operating temperature
- -40…+70 °C
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Low-resistance grounded (LRG) transformers and generators in commercial and industrial power systems are what the LINETRAXX® NGRM550 is built to protect. It continuously monitors the current flowing through the neutral grounding resistor (NGR) and the voltage between the transformer star point and ground. NGR failure (open), connection failures and ground faults are detected, and an alarm or trip follows from the thresholds you configure.
Capabilities extend to 25 kV and 2000 A. The monitor can be retrofitted into an existing LRG application or installed at the factory in a new package. A commissioning wizard is available, and the user interface is multilingual (English, German, Spanish, French). Programming is done through the built-in webserver.
A supervisory system connects by Modbus TCP/IP or Modbus RTU over Ethernet or RS 485. The measuring signals undergo FFT analysis, and measured values are output on an analogue output of 0…10 V or 4…20 mA.
The supply is AC 48…240 V, 40…70 Hz, or DC 48…240 V, drawing up to 7 W / 16 VA. Overvoltage category is III. Relay contacts are rated AC 250 V/250 V with 5 A/3 A on AC and 0.1/0.2/1 A on DC. Operating temperature is -40…+70 °C (-40…+60 °C for UL) and altitude up to 2000 m AMSL.
Coupling devices are chosen from the CD100, CD1000, CD5000, CD14400 and CD25000 series, with CTAC, CTAS or CTUB measuring current transformers, and STEP-PS supplies for the transformers. UL file numbers E493737 and E173157 apply.
Technical specifications
| Supply voltage | AC 48…240 V, 40…70 Hz; DC 48…240 V |
|---|---|
| Maximum voltage | 25 kV |
| Maximum current | 2000 A |
| Operating temperature | -40…+70 °C |
| UL operating temperature | -40…+60 °C |
| Altitude | up to 2000 m AMSL |
| Maximum power consumption | ≤ 7 W / 16 VA |
| Overvoltage category | III |
| Relay rated operating voltage | AC 250 V/250 V |
| Relay rated current AC | 5 A/3 A |
| Relay rated current DC | 0.1/0.2/1 A |
| Interfaces | Ethernet, RS 485 |
| Protocols | Modbus TCP/IP, Modbus RTU |
| Analogue output | 0…10 V, 4…20 mA |
Part numbers
Show all part numbers (1)
B94013500
How it compares with similar models
| Parameter | LINETRAXX® NGRM550 neutral grounding resistor monitor for LRG, up to 25 kV | LINETRAXX® NGRM750 neutral grounding resistor monitor for LRG systems | LINETRAXX® NGRM500 neutral grounding resistance monitor for HRG systems | LINETRAXX® NGRM700 neutral grounding resistance monitor for HRG systems |
|---|---|---|---|---|
| Supply voltage | AC 48…240 V, 40…70 Hz; DC 48…240 V | — | AC/DC 24…240 V | AC 24…240 V, DC 24…240 V |
| Operating temperature | -40…+70 °C | -40…+70 °C | -40…+60 °C (-40…140 °F) | -40…+70 °C (-40…160 °F) |
| Altitude | up to 2000 m AMSL | up to 5000 m above sea level | 2000 m AMSL | up to 5000 m AMSL |
| Analogue output | 0…10 V, 4…20 mA | 0…10 V, 4…20 mA | 4…20 mA, 0…10 V, 0…20 mA, 2…10 V | — |
Request a price and lead time
LINETRAXX® NGRM550 neutral grounding resistor monitor for LRG, up to 25 kV. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which systems is the NGRM550 intended for?
LRG transformers and generators in commercial and industrial power systems.
What does the monitor measure?
The current through the NGR and the voltage between the transformer star point and ground; it detects an open NGR and ground faults.
What is the maximum operating altitude?
Up to 2000 m AMSL.