ISOMETER® IR420-D6 offline insulation monitor for de-energised loads, 100 kΩ…10 MΩ
The IR420-D6 watches the insulation resistance of loads while they are switched off, such as fire pumps, slide-valve drives, lift motors and emergency generators. Two response values within 100 kΩ…10 MΩ, system leakage capacitance up to 10 µF.
- Purpose
- Insulation monitoring of de-energised loads
- Supply systems
- TN, TT, IT
- Supply voltage IR420-D6-1
- DC 9.6…94 V / AC 16…72 V
- Supply voltage IR420-D6-2
- DC 70…300 V / AC 70…300 V, 42…460 Hz
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The IR420-D6 is an offline monitor. It checks insulation resistance on loads that are temporarily or mostly de-energised: fire pumps, slide-valve drives, lift motors, emergency generators, anchor drives and diving pumps. These loads are fed from TN, TT or IT systems.
The device applies a DC measuring voltage to the monitored system through terminals L1 and KE/E. An ohmic insulation fault closes the measuring circuit, and the present insulation resistance appears on the display. To monitor de-energised lines correctly, a low-impedance connection between the active conductors is needed; an inductive star-point coupling device DS2-31 and an inductive load AG70 are available for this. The permissible system leakage capacitance Cemax is 10 µF.
The maximum permissible nominal voltage depends on the nominal contact voltage of the N/C contact of K3, the switch-on contactor. Coupling devices AGH150W, AGH204S-4 and AGH520S extend the nominal voltage range; with the AGH520S it reaches AC 7200 V.
Two response values can be set separately within 100 kΩ…10 MΩ. The front carries a multi-functional LC display, LEDs for Power On, Alarm 1 and Alarm 2, and one combined test/reset button. Two alarm relays each have one changeover contact, and fault memory behaviour is selectable. A self-test runs after the supply is connected and then every 24 hours; holding the test button for more than 1.5 s starts it manually. Error code E01 points to a faulty protective conductor connection.
The IR420-D6-1 is supplied with DC 9.6…94 V / AC 16…72 V, the IR420-D6-2 with DC 70…300 V / AC 70…300 V, 42…460 Hz. Connection is by push-wire terminals. A mounting clip is available for screw mounting, and the mounting frame XM420 for panel installation. Only one insulation monitoring device may be connected in each conductively connected system, and it must be isolated from the IT system during insulation and voltage tests. The device complies with IEC 61557-8 and carries CE and UKCA marks.
Technical specifications
| Purpose | Insulation monitoring of de-energised loads |
|---|---|
| Supply systems | TN, TT, IT |
| Supply voltage IR420-D6-1 | DC 9.6…94 V / AC 16…72 V |
| Supply voltage IR420-D6-2 | DC 70…300 V / AC 70…300 V, 42…460 Hz |
| Response value | 100 kΩ…10 MΩ |
| System leakage capacitance | ≤ 10 µF |
| Alarm relays | 2, one changeover contact each |
| Indication | LC display, LEDs Power On, Alarm 1, Alarm 2 |
| Standard | IEC 61557-8 |
Part numbers
Show all part numbers (4)
FB71016415, B71016415, FB71016407, B91016407
How it compares with similar models
| Parameter | ISOMETER® IR420-D6 offline insulation monitor for de-energised loads, 100 kΩ…10 MΩ | ISOMETER® isoMED527 insulation monitor for medical IT systems, AC 100…240 V, NFC and RS-485 | ISOMETER® isoLR275 with AGH-LR insulation monitor for IT systems, AC 0…793 V / DC 0…1100 V | ISOMETER® isoPV1685DP insulation monitor for PV and BESS, AC 0…1000 V / DC 0…1500 V |
|---|---|---|---|---|
| Purpose | Insulation monitoring of de-energised loads | Insulation monitoring of medical IT systems | Insulation monitoring of unearthed IT systems | Insulation monitoring of IT systems in PV plants and BESS |
| Response value | 100 kΩ…10 MΩ | off, 50…500 kΩ | 0.2 kΩ…100 kΩ | — |
Request a price and lead time
ISOMETER® IR420-D6 offline insulation monitor for de-energised loads, 100 kΩ…10 MΩ. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What system leakage capacitance does the IR420-D6 tolerate?
The maximum permissible system leakage capacitance Cemax is 10 µF.
How is the nominal voltage range extended?
With coupling devices AGH150W, AGH204S-4 or AGH520S; the AGH520S takes it up to AC 7200 V.
How do the IR420-D6-1 and IR420-D6-2 differ?
In supply voltage: the IR420-D6-1 runs on DC 9.6…94 V / AC 16…72 V, the IR420-D6-2 on DC 70…300 V / AC 70…300 V, 42…460 Hz.
Similar equipment from other manufacturers