AL-5 two-phase overcurrent relay (АЛ-5), self-powered, 1-99 A
АЛ-5 (AL-5) relays give two-phase, two-stage overcurrent protection (instantaneous trip plus time-delayed stage) and take power from the monitored current circuits. Current range is 1-99 A, the time-delayed stage is set from 0.1 to 99 s.
- Operating current range
- 1-99 A
- Delayed-stage time setting
- 0.1-99 s, step 0.1 s
- Ratio of instantaneous to delayed setting
- 2-20, step 0.25
- Output relays
- 2
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The АЛ-5 series are microprocessor overcurrent relays for relay protection and emergency automation. For the main protection functions the circuit is powered solely from the monitored current circuits, so no auxiliary supply is connected.
The time-delayed stage has one independent and two dependent characteristics, chosen with microswitches on the front panel, and the unit also has an instantaneous trip stage. The delayed stage is set from 0.1 to 99 s in 0.1 s steps; the ratio of the instantaneous setting to the delayed setting is 2 to 20 in steps of 0.25. LED indication keeps a memory of operation.
Typical uses are protection of cable and overhead lines, transformers (for example backup protection) and motors against short circuits, including in 6-35 kV networks.
There are 20 modifications, АЛ-5-1 to АЛ-5-20, differing in the output combination (trip plus delayed stage, trip, delayed stage, delayed-stage start, shunting), in blocking, and in a delay of 50 or 100 ms or of 200 or 400 ms. Each of the two output relays has one normally open contact rated up to 5 A AC or 1 A DC, up to 250 V, 700 VA (cosφ = 0.5) and 60 W (τ up to 0.015 s).
Operate time is not more than 60 ms at 1.2 times the setting and not more than 50 ms at 3 times, and reset time is not more than 60 ms. Continuous thermal withstand is 2 Ін and one-second withstand is 20Iн. Mass is not more than 0.5 kg and service life not less than 12 years. Mounting is on a DIN rail or protruding. A БШД-01 block handles breaker shunting at currents up to 150 (200) A.
Technical specifications
| Operating current range | 1-99 A |
|---|---|
| Delayed-stage time setting | 0.1-99 s, step 0.1 s |
| Ratio of instantaneous to delayed setting | 2-20, step 0.25 |
| Output relays | 2 |
| Contacts of each output relay | 1 normally open |
| Switched current, AC / DC | up to 5 A / up to 1 A |
| Switched voltage | up to 250 V |
| Switched power | up to 700 VA (cosφ = 0.5); up to 60 W (τ up to 0.015 s) |
| Operate time at 1.2 times setting | not more than 60 ms |
| Operate time at 3 times setting | not more than 50 ms |
| Reset time | not more than 60 ms |
| Continuous thermal withstand | 2 Ін |
| One-second thermal withstand | 20Iн |
| Shunting current (block БШД-01) | up to 150 (200) A |
| Mass | not more than 0.5 kg |
| Service life | not less than 12 years |
Part numbers
Show all part numbers (1)
АЛ-5-1...АЛ-5-20
European equivalents
IPR-A / IPR-A2 / IPR-D / IPR96D overcurrent and earth fault protection relays for MV feeders
selected by purpose and main parameters, please confirm with our manager
Request a price and lead time
AL-5 two-phase overcurrent relay (АЛ-5), self-powered, 1-99 A. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Does the АЛ-5 need a separate power supply?
No. For the main protection functions the circuit is powered only from the monitored current circuits.
Which time characteristics can be selected?
One independent and two dependent characteristics, selected by microswitches on the front panel.
What delays do the modifications use?
The delayed stage is set from 0.1 to 99 s, and the modifications have a delay of 50 or 100 ms or of 200 or 400 ms.