TTDUZR dry arc-suppression transformer-reactor, continuous adjustment, 516 to 2273 kVAr
The TTDUZR combines an earthing transformer, a continuously adjustable arc-suppression reactor and an auxiliary transformer in one dry unit. Compensation is 516 to 2273 kVAr (60 to 250 A), auxiliary supply 63 to 315 kVA, up to 36 kV.
- Type
- TTDUZR dry arc-suppression transformer-reactor with continuous adjustment
- Compensation rating
- 516 kVAr to 2273 kVAr (compensation current 60 A to 250 A)
- Auxiliary supply rating
- 63 kVA to 315 kVA
- Resistor secondary winding
- 500 V, 500 A, 60 s
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The TTDUZR dry transformer-reactor performs three roles: an earthing transformer that forms the artificial neutral point, a continuously adjustable arc-suppression reactor, and a station auxiliary transformer. It contains a transformer part and a steplessly adjustable reactor part, so it gives a complete compensated neutral for an MV network. One bay in the substation is enough, where a separate earthing transformer and arc-suppression reactor would take two.
The transformer part has vector group ZNzn0. In an earth fault it spreads the fault current over all phases and lowers its value in the faulted line. With this group the secondary winding can run continuously at rated conditions, even when the primary carries fault current. The transformer part connects to the terminals of vacuum coils or, in roving construction, directly. The neutral of the transformer can be taken straight from the star point to the phase terminal of the reactor part, or through a circuit breaker. The reactor part has the automatic compensation system BS KKZ or manual control, remote or local.
Compensation rating is 516 kVAr to 2273 kVAr at a compensation current of 60 A to 250 A. The auxiliary supply rating is 63 kVA to 315 kVA. Windings include a resistor secondary of 500 V, 500 A, 60 s (other ratings on request), a measuring winding of 500 V, 100 A, 120 s and an additional winding of 100 V, 3 A, 60 s. Duty is short-time (PK) up to 2 h for the arc-suppression part, and rated voltage is up to 36 kV.
The core is cold-rolled transformer steel with inorganic insulation. Windings are round or profiled wire in class H insulation, copper or aluminium. Standard equipment: HV terminals on the coils (M12 or M16), flat busbar LV terminals for the auxiliary supply, flat HV terminals on the reactor part, rating plate, undercarriage with wheels adjustable for longitudinal and transverse travel, air-gap adjusting drive, earthing terminals on the undercarriage, four PT100 sensors, temperature protection, lifting lugs, an off-circuit tap changer on the transformer part and the BS KKZ control cabinet. The finish is RAL 7033, other colours on request. Options are a 7-position off-circuit adjustment of the earthing transformer, surge arresters, vibration pads and a protection cable box.
Altitude is limited to 1000 m above sea level, ambient temperature is -25 to 40 °C and frequency is 50 Hz. Manufacture, testing and tolerances follow PN EN 60076-1 and PN EN 60076-6.
Technical specifications
| Type | TTDUZR dry arc-suppression transformer-reactor with continuous adjustment |
|---|---|
| Compensation rating | 516 kVAr to 2273 kVAr (compensation current 60 A to 250 A) |
| Auxiliary supply rating | 63 kVA to 315 kVA |
| Resistor secondary winding | 500 V, 500 A, 60 s |
| Measuring winding | 500 V, 100 A, 120 s |
| Additional winding | 100 V, 3 A, 60 s |
| Duty | short-time (PK) up to 2 h for the arc-suppression part |
| Rated voltage | up to 36 kV |
| Vector group of the transformer part | ZNzn0 |
| Core | cold-rolled transformer steel with inorganic insulation |
| Windings | round or profiled wire in class H insulation, copper or aluminium |
| Compensation control | automatic BS KKZ system or manual (remote or local) |
| Sensors | PT100, 4 pcs |
| Rated frequency | 50 Hz |
| Altitude | up to 1000 m above sea level |
| Ambient temperature | -25 to 40 °C |
| Standards | PN EN 60076-1, PN EN 60076-6 |
How it compares with similar models
| Parameter | TTDUZR dry arc-suppression transformer-reactor, continuous adjustment, 516 to 2273 kVAr | TTDUOR oil-immersed arc-suppression transformer-reactor, continuous adjustment, 516 to 3182 kVAr | TTDUO oil-immersed arc-suppression transformer-reactor, tap-adjusted, 516 to 3182 kVAr | Dry resin reactive power compensation reactor, 150 kVAr to 4 MVAr |
|---|---|---|---|---|
| Type | TTDUZR dry arc-suppression transformer-reactor with continuous adjustment | TTDUOR oil-immersed arc-suppression transformer-reactor with continuous adjustment | TTDUO oil-immersed arc-suppression transformer-reactor with tap adjustment | dry vacuum-resin reactive power compensation reactor |
| Compensation rating | 516 kVAr to 2273 kVAr (compensation current 60 A to 250 A) | 516 kVAr to 3182 kVAr (compensation current 60 A to 350 A) | 516 kVAr to 3182 kVAr (compensation current 60 A to 350 A) | — |
| Auxiliary supply rating | 63 kVA to 315 kVA | 63 kVA to 315 kVA | 63 kVA to 500 kVA | — |
| Windings | round or profiled wire in class H insulation, copper or aluminium | round or profiled wire in class H insulation, copper or aluminium | round or profiled wire in class H insulation, copper or aluminium | aluminium or copper |
| Rated frequency | 50 Hz | 50 Hz | 50 Hz | 50 Hz or 60 Hz |
Request a price and lead time
TTDUZR dry arc-suppression transformer-reactor, continuous adjustment, 516 to 2273 kVAr. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is adjusted continuously in the TTDUZR?
The arc-suppression part, through an air-gap drive, automatically by the BS KKZ system or manually, remote or local.
What power ranges are available?
Compensation of 516 kVAr to 2273 kVAr (60 A to 250 A), auxiliary supply of 63 kVA to 315 kVA, up to 36 kV.
What duty does the arc-suppression part have?
Short-time duty (PK) up to 2 h.