BTUO oil-immersed earthing transformer, Znyn11, 250 kVA to 4 MVA
The BTUO is a three-phase oil-immersed earthing transformer that provides an artificial neutral point on compensated and resistor-earthed networks. Znyn11 windings, 250 kVA to 4 MVA, up to 36 kV.
- Type
- three-phase oil-immersed earthing transformer
- Rated power
- 250 kVA up to 4 MVA
- Rated voltage
- up to 36 kV
- Vector group
- Znyn11
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The BTUO earthing transformer gives compensated and resistor-earthed networks an artificial neutral point. It is a three-phase, oil-immersed unit. While no earth fault is present it also supplies the unit auxiliaries of the substation.
The windings are in a Znyn11 arrangement, which shares current between the phases and cuts the current in a line hit by an earth fault or short circuit. The secondary winding can run continuously at rated conditions, even when the primary carries compensating current.
On a resistor-earthed network the neutral of the unit goes to an earthing resistor, which injects the active component of the current. On a compensated network it is normally paired with an arc-suppression reactor, which adds the reactance needed to extinguish the arc and compensate earth-fault currents.
The core is cold-rolled steel sheet with inorganic insulation. The winding is electrolytic copper wire, enamelled round or profiled, in paper insulation. Voltage adjustment is manual in 5 steps. The tank is steel sheet, powder coated or hot-dip galvanised, and sits on an undercarriage whose wheels can be repositioned.
Standard equipment covers a manual drive for the tap changer, HV and LV porcelain bushings, oil level indicator, rating plate, earth terminals, transport, lifting and pulling lugs, a bi-directional undercarriage and a thermometer pocket. Options are DMCR® or DGPT2 protection relays, connector bushings and heads, surge arresters, terminal clamps for the bushings, vibration dampers under the tank and a thermometer.
The range runs from 250 kVA up to 4 MVA at voltages up to 36 kV. Altitude is limited to 1000 m above sea level, ambient temperature is -25 to 40 °C and frequency is 50 Hz or 60 Hz. Manufacture, testing and tolerances follow PN EN 60076-1 and PN EN 60289. Units with other parameters are agreed individually.
Technical specifications
| Type | three-phase oil-immersed earthing transformer |
|---|---|
| Rated power | 250 kVA up to 4 MVA |
| Rated voltage | up to 36 kV |
| Vector group | Znyn11 |
| Voltage adjustment | 5-step manual |
| Core | cold-rolled steel sheet with inorganic insulation |
| Winding | electrolytic copper wire, enamelled round or profiled, in paper insulation |
| Tank | steel sheet, powder coated or hot-dip galvanised, undercarriage with wheels |
| Rated frequency | 50 Hz or 60 Hz |
| Altitude | up to 1000 m above sea level |
| Ambient temperature | -25 to 40 °C |
| Standards | PN EN 60076-1, PN EN 60289 |
How it compares with similar models
| Parameter | BTUO oil-immersed earthing transformer, Znyn11, 250 kVA to 4 MVA | Dry resin reactive power compensation reactor, 150 kVAr to 4 MVAr | TTDUO oil-immersed arc-suppression transformer-reactor, tap-adjusted, 516 to 3182 kVAr | TTDUOR oil-immersed arc-suppression transformer-reactor, continuous adjustment, 516 to 3182 kVAr |
|---|---|---|---|---|
| Type | three-phase oil-immersed earthing transformer | dry vacuum-resin reactive power compensation reactor | TTDUO oil-immersed arc-suppression transformer-reactor with tap adjustment | TTDUOR oil-immersed arc-suppression transformer-reactor with continuous adjustment |
| Core | cold-rolled steel sheet with inorganic insulation | cold-rolled transformer steel with inorganic insulation | cold-rolled transformer steel with inorganic insulation | cold-rolled transformer steel with inorganic insulation |
| Tank | steel sheet, powder coated or hot-dip galvanised, undercarriage with wheels | — | hermetically sealed (no conservator) or with conservator, steel powder coated or hot-dip galvanised; radiator tank also possible | radiator tank with conservator, powder coated with C4 or C5 anti-corrosion system, wheeled undercarriage |
| Rated frequency | 50 Hz or 60 Hz | 50 Hz or 60 Hz | 50 Hz | 50 Hz |
| Standards | PN EN 60076-1, PN EN 60289 | PN EN 60076-1, PN EN 60076-6 | PN EN 60076-1, PN EN 60076-6 | PN EN 60076-1, PN EN 60076-6 |
Request a price and lead time
BTUO oil-immersed earthing transformer, Znyn11, 250 kVA to 4 MVA. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What is the BTUO earthing transformer used for?
It creates an artificial neutral point in compensated and resistor-earthed networks and, in normal operation, supplies the unit auxiliaries.
What is it paired with on compensated and resistor-earthed networks?
On a compensated network it normally works with an arc-suppression reactor; on a resistor-earthed network the neutral goes to an earthing resistor.
What power range and operating conditions apply?
250 kVA to 4 MVA at up to 36 kV, altitude up to 1000 m above sea level, -25 to 40 °C, 50 Hz or 60 Hz.