TTDUO oil-immersed arc-suppression transformer-reactor, tap-adjusted, 516 to 3182 kVAr
The TTDUO combines an earthing transformer, an arc-suppression reactor and an auxiliary transformer in one oil-immersed unit. Compensation is 516 to 3182 kVAr (60 to 350 A), auxiliary supply 63 to 500 kVA, up to 36 kV.
- Type
- TTDUO oil-immersed arc-suppression transformer-reactor with tap adjustment
- Compensation rating
- 516 kVAr to 3182 kVAr (compensation current 60 A to 350 A)
- Auxiliary supply rating
- 63 kVA to 500 kVA
- Resistor secondary winding
- 500 V, 500 A, 60 s
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The TTDUO oil-immersed arc-suppression transformer-reactor combines three roles: an earthing transformer that forms the artificial neutral point, an arc-suppression reactor, and a station auxiliary transformer. The unit holds both the transformer and the reactor part, so it gives a complete compensated neutral for an MV network. The usual arrangement of a separate earthing transformer and arc-suppression reactor takes two bays in the substation, while this unit needs one.
The transformer part has vector group ZNzn0. In an earth fault it spreads the fault current over all phases and lowers its value in the faulted line. The secondary winding can run continuously at rated conditions even when the primary carries compensating current. Bushing leads on the cover connect the transformer part to the reactor part, which adds the reactance needed to extinguish the arc and compensate earth-fault currents. The reactor part has a tap changer for choosing the compensation level.
Compensation rating is 516 kVAr to 3182 kVAr, corresponding to a compensation current of 60 A to 350 A. The auxiliary supply rating is 63 kVA to 500 kVA. Windings include a resistor secondary of 500 V, 500 A, 60 s (other ratings on request), a measuring winding of 500 V, 100 A, 120 s and an additional winding of 100 V, 3 A, 60 s. Permitted loading with compensation current is 100% for 2 h, 87.5% for 4 h, 75% for 8 h and 60% continuous.
The tank is either hermetically sealed without a conservator or fitted with one. It is made of steel sheet, powder coated or hot-dip galvanised, and stands on an undercarriage whose wheels can be set for longitudinal or transverse travel. A radiator tank is also possible.
Standard equipment includes two off-circuit tap changers (for transformer ratio and for compensation), HV porcelain bushings to DIN 42531 or EN 50180:2010 or connector bushings, LV bushings to DIN 42530 or EN 50386:2010 or connector type, oil level indicator, rating plate, earthing terminals, lifting and transport lugs, thermometer pocket, oil filler and a drain valve to EN 50216-4 or DIN 42551. The finish is RAL 7033. Options are a 7-position off-circuit tap changer, integrated gas, temperature and pressure protection, surge arresters, a contact thermometer, vibration pads and a cable box. The conservator version adds a Buchholz relay, a conservator oil level indicator, a dehydrating breather and a drain plug.
Altitude is limited to 1000 m above sea level, ambient temperature is -25 to 40 °C and frequency is 50 Hz. Manufacture, testing and tolerances follow PN EN 60076-1 and PN EN 60076-6.
Technical specifications
| Type | TTDUO oil-immersed arc-suppression transformer-reactor with tap adjustment |
|---|---|
| Compensation rating | 516 kVAr to 3182 kVAr (compensation current 60 A to 350 A) |
| Auxiliary supply rating | 63 kVA to 500 kVA |
| Resistor secondary winding | 500 V, 500 A, 60 s |
| Measuring winding | 500 V, 100 A, 120 s |
| Additional winding | 100 V, 3 A, 60 s |
| Compensation current, % of rated | 100% for 2 h; 87.5% for 4 h; 75% for 8 h; 60% continuous |
| Rated voltage | up to 36 kV |
| Vector group of the transformer part | ZNzn0 |
| Core | cold-rolled transformer steel with inorganic insulation |
| Windings | round or profiled wire in class H insulation, copper or aluminium |
| Tank | hermetically sealed (no conservator) or with conservator, steel powder coated or hot-dip galvanised; radiator tank also possible |
| Rated frequency | 50 Hz |
| Altitude | up to 1000 m above sea level |
| Ambient temperature | -25 to 40 °C |
| Standards | PN EN 60076-1, PN EN 60076-6 |
How it compares with similar models
| Parameter | TTDUO oil-immersed arc-suppression transformer-reactor, tap-adjusted, 516 to 3182 kVAr | TTDUOR oil-immersed arc-suppression transformer-reactor, continuous adjustment, 516 to 3182 kVAr | TTDUZR dry arc-suppression transformer-reactor, continuous adjustment, 516 to 2273 kVAr | Dry resin reactive power compensation reactor, 150 kVAr to 4 MVAr |
|---|---|---|---|---|
| Type | TTDUO oil-immersed arc-suppression transformer-reactor with tap adjustment | TTDUOR oil-immersed arc-suppression transformer-reactor with continuous adjustment | TTDUZR dry arc-suppression transformer-reactor with continuous adjustment | dry vacuum-resin reactive power compensation reactor |
| Compensation rating | 516 kVAr to 3182 kVAr (compensation current 60 A to 350 A) | 516 kVAr to 3182 kVAr (compensation current 60 A to 350 A) | 516 kVAr to 2273 kVAr (compensation current 60 A to 250 A) | — |
| Auxiliary supply rating | 63 kVA to 500 kVA | 63 kVA to 315 kVA | 63 kVA to 315 kVA | — |
| Windings | round or profiled wire in class H insulation, copper or aluminium | round or profiled wire in class H insulation, copper or aluminium | round or profiled wire in class H insulation, copper or aluminium | aluminium or copper |
| Rated frequency | 50 Hz | 50 Hz | 50 Hz | 50 Hz or 60 Hz |
Request a price and lead time
TTDUO oil-immersed arc-suppression transformer-reactor, tap-adjusted, 516 to 3182 kVAr. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What functions does the TTDUO combine?
An earthing transformer for the artificial neutral, an arc-suppression reactor and an auxiliary transformer, needing one bay instead of two.
What compensation and auxiliary ratings are available?
Compensation of 516 kVAr to 3182 kVAr (60 A to 350 A) and auxiliary supply of 63 kVA to 500 kVA, at up to 36 kV.
How long can the unit carry compensating current?
100% for 2 h, 87.5% for 4 h, 75% for 8 h and 60% continuously.