TMS-Pro Multi-Gas Transformer Monitoring Package with Cooling and Tap Changer Diagnostics
The middle tier of the transformer monitoring family. TMS-Pro adds multi-gas analysis and a longer fault library than TMS-Core, reaching into the tap changer drive and the whole cooling plant.
- Package
- TMS-Pro
- Method
- multi-gas analysis
- OLTC/DETC
- contact resistance; liquid insulation; motor drive; control
- Windings
- general overheating; paper insulation (moisture, oxygen); local overheating 1
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Cooling faults are a good illustration of what this package brings. Incorrect configuration, failed fans, blocked radiators, failed pumps, pumps running in reverse and faulty temperature sensors are all picked out, so a transformer is not quietly overheating because of an auxiliary problem.
At the heart of TMS-Pro is multi-gas analysis, which separates fault types more clearly than basic monitoring and shortens the time from first indication to an informed decision. Typical users run transmission transformers and generator transformers where outages are costly.
For OLTC and DETC units the package watches contact resistance, liquid insulation deterioration, motor drive failure and failure of the control circuit. Winding checks cover general overheating, paper insulation ageing from moisture and oxygen ingress, and type 1 local overheating from eddy currents, circulating currents or shorted strands in the same turn. Core diagnostics take in over-excitation heating, steel joint opening, loss of shield earthing and loss of core earthing.
The optional bushing module is the same as elsewhere in the family and detects internal contact problems, partial breakdowns, core insulation deterioration, contamination of the inner porcelain surface and discharge across the outer one. Analytics software is supplied with the hardware.
An enquiry should include the nameplate data, the tap changer type and a description or diagram of the cooling arrangement.
Technical specifications
| Package | TMS-Pro |
|---|---|
| Method | multi-gas analysis |
| OLTC/DETC | contact resistance; liquid insulation; motor drive; control |
| Windings | general overheating; paper insulation (moisture, oxygen); local overheating 1 |
| Core | over-excitation; steel joint opening; loss of shield and core earthing |
| Cooling system | configuration; fans; radiators; pumps; temperature sensors |
| Option | bushing monitoring module |
| Applications | transmission transformers, generator transformers |
How it compares with similar models
| Parameter | TMS-Pro Multi-Gas Transformer Monitoring Package with Cooling and Tap Changer Diagnostics | TMS-Elite Transformer Monitoring Package with Partial Discharge and Fibre Optic Sensing | TMS-Core Entry-Level Transformer Condition Monitoring Package | DGA 900 online analyzer of 9 dissolved gases in transformer oil |
|---|---|---|---|---|
| Package | TMS-Pro | TMS-Elite | TMS-Core | — |
| Windings | general overheating; paper insulation (moisture, oxygen); local overheating 1 | general overheating; paper insulation; local overheating 1 and 2 | general overheating; paper insulation ageing (oxygen, moisture); local overheating | — |
Request a price and lead time
TMS-Pro Multi-Gas Transformer Monitoring Package with Cooling and Tap Changer Diagnostics. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
What does TMS-Pro add over TMS-Core?
Multi-gas analysis, tap changer motor drive and control checks, loss of shield and core earthing, and a full cooling system diagnostic block.
Which cooling faults are detected?
Incorrect configuration, fan and pump failure, blocked radiators, pumps running in reverse and temperature sensor failure.
Which transformers is TMS-Pro intended for?
Transmission transformers and generator transformers fitted with an OLTC or DETC.
Similar equipment from other manufacturers