TMS-Core Entry-Level Transformer Condition Monitoring Package
An entry package for moving a power transformer onto condition-based maintenance. TMS-Core watches the commonest failure modes in the windings, core and on-load tap changer, and arrives as hardware plus analytics software under one order.
- Package
- TMS-Core
- Purpose
- condition-based maintenance of power transformers
- Tap changer
- contact resistance; liquid insulation deterioration
- Windings
- general overheating; paper insulation ageing (oxygen, moisture); local overheating
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
Think of TMS-Core as the first step away from calendar-based servicing. Rather than opening a unit because the schedule says so, the operator sees trends building in the data and plans an outage once the condition actually warrants it.
On the windings the package looks for general overheating, ageing of the paper insulation caused by oxygen ingress and moisture in the paper, and local hot spots from eddy current losses, circulating currents or shorted strands within the same turn. The core, electrical screen and flux shunts are checked for steel joint opening and for general overheating when the transformer is over-excited. On the tap changer side it flags rising contact resistance and deterioration of the liquid insulation.
Transmission transformers and generator step-up units are the intended applications. Bushings can be brought in later through an optional module that picks up internal contact problems, partial breakdowns, deterioration of the core insulation, contamination of the inner porcelain surface and discharge across the outer porcelain.
Within the family, TMS-Pro and TMS-Elite sit above this kit with longer lists of detected faults, so Core suits fleets where budget matters and the aim is broad basic cover. The hardware is supplied together with APM software for trend analysis and alarms.
When enquiring, please include the nameplate data, the tap changer type and which bushings you would like to monitor.
Technical specifications
| Package | TMS-Core |
|---|---|
| Purpose | condition-based maintenance of power transformers |
| Tap changer | contact resistance; liquid insulation deterioration |
| Windings | general overheating; paper insulation ageing (oxygen, moisture); local overheating |
| Core, screen, shunts | steel joint opening; overheating when over-excited |
| Option | bushing monitoring module |
| Software | APM |
| Applications | transmission transformers, generator transformers |
How it compares with similar models
| Parameter | TMS-Core Entry-Level Transformer Condition Monitoring Package | TMS-Pro Multi-Gas Transformer Monitoring Package with Cooling and Tap Changer Diagnostics | TMS-Elite Transformer Monitoring Package with Partial Discharge and Fibre Optic Sensing | Calisto T1 Transformer Monitoring Unit for Bushings, Partial Discharge and I/O |
|---|---|---|---|---|
| Package | TMS-Core | TMS-Pro | TMS-Elite | — |
| Windings | general overheating; paper insulation ageing (oxygen, moisture); local overheating | general overheating; paper insulation (moisture, oxygen); local overheating 1 | general overheating; paper insulation; local overheating 1 and 2 | — |
Request a price and lead time
TMS-Core Entry-Level Transformer Condition Monitoring Package. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
Which winding faults does TMS-Core detect?
General overheating, paper insulation ageing from oxygen ingress and moisture, and local hot spots caused by eddy currents, circulating currents or shorted strands in the same turn.
Can bushing monitoring be added?
Yes, through an optional module that detects internal contact problems, partial breakdowns, core insulation deterioration and contamination or discharge on the porcelain.
How does Core compare with TMS-Pro and TMS-Elite?
Core covers the commonest winding, core and tap changer faults. The higher packages add cooling system and tap changer drive checks, and TMS-Elite adds liquid insulation and partial discharge monitoring.