Calisto T1 Transformer Monitoring Unit for Bushings, Partial Discharge and I/O
A configurable transformer monitoring system that brings bushing monitoring, partial discharge measurement and an input and output module into one compact enclosure. Its built-in server handles user access, alarms and visualisation, and data passes over Modbus, DNP3 and optionally IEC 61850.
- Type
- complete transformer condition monitoring system
- Functions
- bushing monitoring, partial discharge, I/O
- Partial discharge
- through bushings, neutral and main tank
- PD frequency ranges
- HF, VHF, lower UHF
Price, availability and lead time on request. We help with analogue selection, customs clearance and delivery.
Description
The T1 can be scaled from a single component up to a full transformer monitor that covers partial discharge, bushings and operational data. It connects to dissolved gas analysis monitors and to devices from other suppliers, and it forms part of the manufacturer's monitoring range, exchanging data with its other instruments and with SCADA.
The PD-Guard module monitors partial discharge through the bushings, the neutral and inside the main tank. It raises local alarms, passes data and notifications over standard interface channels to networked supervisory systems, and analyses PD and EMI signals in the HF, VHF and lower UHF ranges with built-in diagnostic tools.
The IDD module detects deterioration in bushings by finding abnormalities in the insulation, and it issues alerts when they appear. For each bushing, up to six in total, it analyses leakage current, phase, capacitance, power factor and harmonics. Where a voltage reference is available, it calculates both relative and true power factor, which helps reveal faults in the bushings and in the voltage reference devices.
The iO module works as a data recorder. It accepts current, voltage, temperature and relay inputs, and combines data from several sensors and sources, including load readings, tap changer position and signals from devices made by other suppliers.
Three alarm levels can be set on each data channel, with adjustable default values, and a built-in audit trail records alarm generation and acknowledgement for review after an event. The unit runs inside the customer's firewall, meets cybersecurity requirements and shows data from several assets through one interface. The hardware can be upgraded in the field, so monitoring can begin with bushings and main tank partial discharge can be added later.
Technical specifications
| Type | complete transformer condition monitoring system |
|---|---|
| Functions | bushing monitoring, partial discharge, I/O |
| Partial discharge | through bushings, neutral and main tank |
| PD frequency ranges | HF, VHF, lower UHF |
| Bushing monitoring | up to six, each monitored separately |
| Bushing parameters | leakage current, phase, capacitance, power factor, harmonics |
| Power factor | relative and true (with voltage reference) |
| iO inputs | current, voltage, temperature, relay |
| Alarm levels | three per data channel |
| Protocols | Modbus, DNP3, IEC 61850 (optional) |
| Interface | built-in server |
| Expansion | hardware, in the field |
Request a price and lead time
Calisto T1 Transformer Monitoring Unit for Bushings, Partial Discharge and I/O. We reply within one business day.
Or email sales@usk.ua or call 044 339-50-20.
Questions and answers
How many bushings can the T1 monitor?
The IDD module covers up to six bushings, and it analyses leakage current, phase, capacitance, power factor and harmonics for each one.
Can the system start small and expand later?
Yes. The hardware can be upgraded in the field, so monitoring can begin with bushings and main tank partial discharge can be added later.
Which frequency ranges does PD-Guard analyse?
PD-Guard analyses partial discharge and EMI signals in the HF, VHF and lower UHF ranges.